SHTM 03-01 Part A: Appendix 9: Design of air- movement control scheme for anaesthetic room

Ventilation for Healthcare - Design and validation (SHTM 03-01 Part A) · PDF pages 214–215 of 227 · Source file: shtm-03-01-part-a-v30-feb-2022.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHTM 03-01 Part A – PDF page 214]

Appendix 9: Design of air- movement control scheme for anaesthetic room

General

Figure A25 Schematic of suitable supply and extract solution

The above shows the typical zones for the positioning of ceiling-mounted supply and low-level extracts in an anaesthetic room. The objective is to comply with the COSHH Regulations and SHTM 03-01 Part A by providing a clean airflow path for staff working in anaesthetic rooms and so reduce their risk of casual exposure to waste/leaking anaesthetic agents.

Note 1: Supply terminals should not be positioned above wall-mounted cupboards as this will prevent their output being measured directly with a balometer. It will also negatively impact on the air distribution within the room.

Note 2: See photographs below for details of the recommended low-level extract installation.

Note 3: Low-level extracts should have a spring-clip-retained pull-off grille face for ease of cleaning.

Low-level extract installation

Traditional installation (not recommended)

Low-level extract easily obstructed by equipment

Extra corners to clean around

[SHTM 03-01 Part A – PDF page 215]

Figure A26 Low level extract traditional installation (not recommended)

Recommended installation

low-level extract cut back at 80º and stops short of the floor;

no added detail to floor covering or coving;

no additional corners to clean around;

not easily obstructed by equipment;

pull-off grille face for ease of cleaning;

grille still accessible for airflow measurement.

Figure A27 Low level extract recommended installation

The photograph is for illustrative purposes only and shows a cutback of approximately 65º. This was found to make airflow measurement quite difficult, hence the change to an 80º cutback so that measurement can be easily taken with a balometer.

Operating theatre to anaesthetic room air-transfer device The air-transfer device between an operating theatre and anaesthetic room may be either by a transfer grille or pressure stabiliser. The choice will be determined by the volume of air to be transferred.

Paragraphs A8.51 and A8.52 in Appendix 8 give details.