SHTM 03-01 Part A: Appendix 8: Design of air- movement control schemes for operating theatres – Calculation sheet for flow rates

Ventilation for Healthcare - Design and validation (SHTM 03-01 Part A) · PDF pages 200–213 of 227 · Source file: shtm-03-01-part-a-v30-feb-2022.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHTM 03-01 Part A – PDF page 200]

Calculation sheet for flow rates

Worksheet WS1 Reference:

Room name

1. Summer temperature control Heat gain kW

m3/s

2. Acceptable ∆t ºC 3. Air flow rate (SG) = Gain_ ∆t × 1.2

4. Winter temperature control Heat loss kW

5. Acceptable ∆t ºC

m3/s

6. Air flow rate (SL) = __Loss__

∆t × 1.2

m3/s

7. Dilution of bacterial contaminants Air flow rate

SD or ED

8. Desired air change rate

AC/hr

AC/hr × room volume (m3)

3600

m3/s

9. Maximum of SG, SL, SD or ED or air change rate from step 8 m3/s

S m3/s

10. Air movement control Air flow rate for air movement control SAMC or EAMC (from WS2, WS3 or WS4)

E m3/s

11. Final supply flow rate (SF) m3/s

12. Final extract m3/s

13. Total supply m3/s

14. Total extract m3/s

Designer ............................................................................................ Date ...............................................

Template A1 Worksheet WS1

[SHTM 03-01 Part A – PDF page 201]

Worksheet WS2a Reference:

Air movement control Peripheral room ................................. type, single flow

Nominal pressure:________Pa

Consider door to .................................. open

Air flow, m3/s

Pa ∆t Out In Remarks

Flow required through doorway to give protection

Total

SAMC ( ∑OUT – ∑IN ) m3/s

or

EAMC ( ∑IN – ∑OUT ) m3/s

Transfer SAMC or EAMC to WS1

Consider door to ................................. closed

Pa ∆t Out In Remarks

Closed door leakage

Total

Return SF and EF to WS1 __________ __________

Flow through transfer grille outward (SF – EF – LOUT) __________

or

Flow through transfer grille inward (EF – SF – LIN) __________

Designer ........................................................................................................... Date ......................................................

Template A2 Worksheet WS2a

[SHTM 03-01 Part A – PDF page 202]

Worksheet WS2b Reference:

Air movement control Peripheral room ................................. type, parallel/series multi-flow

Nominal pressure:________Pa

Door from this room to .............................................................. (room of equal cleanliness) is not to be protected. A transfer grille is located in, or adjacent to, this door

Consider other door to ...................... open.

Room pressure now becomes or or Pa (see Appendix 6)

Air flow, m3/s

Out In Remarks

Flow required through doorway to give protection

At above pressures leaks through closed doors Pa ∆P

Mechanical supply or extract (SF/EF)

Total

X ( ∑OUT – ∑IN ) or Y ( ∑IN – ∑OUT )

Transfer grille required

from high-pressure zone Flow = X

or at ∆Pa

to low-pressure zone Flow = Y

Size of transfer grille (free area) A1

Consider doors and hatch closed – room pressure becomes Pa (nominal)

Closed door leakage from Appendix 4 (assuming no transfer grille) Pa ∆P Out In Remarks

Mechanical supply or extract

Total

Air flow required through transfer grille = IN – OUT = Z´

or OUT – IN = Z ˝ __________

Transfer grille required flow Z´ or Z ˝ __________ @ __________ ∆P

Size of transfer grille (free area) A2 = __________

Select larger of A1 or A2 __________

Designer ........................................................................................................... Date ......................................................

[SHTM 03-01 Part A – PDF page 203]

Template A3 Worksheet WS2b

Worksheet WS2c Reference:

Air movement control Peripheral room ................................. type, parallel multi-flow high/low or series multi-flow (unbalanced)

Nominal pressure:________Pa

Consider door from this room to ...................................... open.

Room pressure now becomes or or Pa (see Appendix 6)

Air flow, m3/s

Out In Remarks

Flow required through open doorway to give protection

At above pressures leaks through closed doors are: Pa ∆P

Total

S1 ( ∑OUT – ∑IN ) or E1 ( ∑IN – ∑OUT )

Consider door from this room to ...................................... open.

Room pressure now becomes or or Pa

Out In Remarks

Flow required through open doorway to give protection

At above pressures leaks through closed doors are: Pa ∆P

Total

S2 ( ∑OUT – ∑IN ) or E2 ( ∑IN – ∑OUT )

Consider doors closed. Closed doors leakage from Appendix 4

Door to: Pa ∆P Out In Remarks

Total

Return SF and EF from WS1 ____________________ Flow through transfer device outward (SF – LOUT) or ____________________ to ..................................................

Flow through transfer device inward (EF – LIN)

Transfer grille ____________________ Pressure relief damper from ..................................................

[SHTM 03-01 Part A – PDF page 204]

Designer ........................................................................................................... Date ......................................................

Template A4 Worksheet WS2c

[SHTM 03-01 Part A – PDF page 205]

Worksheet WS2d Reference:

Air movement control Peripheral room ................................. type, series multi-flow (balanced)

Nominal pressure:________Pa

Note: In this type of room the supply and extract air flow rates are equal and take no part in the air movement control (AMC)

First, open door to higher pressure area.

Room pressure then becomes or or Pa (see Appendix 6)

Air flow, m3/s

Out In Remarks

Flow required through open doorway to give protection. See Appendix 6

At above pressures leaks through closed doors are: Pa ∆P

Total

Q1 ( ∑IN – ∑OUT ) (+ve inwards) ____________________

Next, open door to lower pressure area.

Room pressure then becomes or or Pa

Out In Remarks

Flow required through open doorway to give protection

At above pressures leaks through closed doors are: Pa ∆P

Total

Q2 ( ∑OUT – ∑IN ) (+ve outwards)

[SHTM 03-01 Part A – PDF page 206]

Flow through transfer device (TD1) to protect

door 1 = Q1 ____________________ at resultant

∆P .................................

Flow through transfer device (TD2) to protect

door 2 = Q2 ____________________ at resultant

∆P .................................

Designer ........................................................................................................... Date ......................................................

Template A5 Worksheet WS2d

[SHTM 03-01 Part A – PDF page 207]

Worksheet WS2e Reference:

Air movement control Peripheral room ................................. type bay (semi-open)

Nominal pressure:______Pa

Note: If the room is of the open bay type (ie opening is larger than normal single doorway), the room should be considered part of the main room. No air movement control considerations need then be made, and this sheet can be discarded. Supply and/or extract flow will be based on air distribution considerations.

Consider permanent opening

Air flow, m3/s

Out In Remarks

Flow required through opening to give protection

Leaks through closed doors to: Pa ∆P

Total

EAMC ____________________ or flow outward through transfer device ( ∑IN – ∑OUT ) ____________________

Transfer SAMC or EAMC to WS1

Transfer device – transfer grille ____________________ – pressure stabiliser ____________________

Size select transfer device for flow rate ____________________ @ ∆P ____________________

Note: A door from the bay is considered with the peripheral room to which it leads or, if it leads to the corridor, it is considered with the main room

Designer ........................................................................................................... Date ......................................................

Template A6 Worksheet WS2e

[SHTM 03-01 Part A – PDF page 208]

Air movement control Operating room Worksheet WS3 Reference:

Nominal pressure:______Pa

Note: To avoid considering each door open in turn, the “key door” concept is introduced. This is the door which requires the greatest mechanical flow when open. See paragraph A8.33

Select “key door” (see above).

Consider this door open – room pressure now becomes ____________________ Pa (see Appendix 6)

See Appendix 7 for room pressures

Air flow, m3/s

Out In Remarks

Flow required through doorway to give protection

Air flow “out” or “in” via doors, transfer devices etc Pa ∆P

Mechanical extract

Total

SAMC ( ∑OUT – ∑IN ) ____________________ transfer SAMC to WS1

Consider all doors closed.

Return SF from WS1 ____________________ Room pressure now____________________ Pa (nominal)

Air flow “out” or “in” via door leakage, transfer devices etc Pa ∆P Out In Remarks

Mechanical extract and supply

Total

Flow ( ∑IN – ∑OUT ) through transfer device ____________________ @ ∆P ____________________ to ...............................................

For final selection of transfer device see paragraphs A8.50–A8.54

Designer ........................................................................................................... Date ......................................................

Template A7 Worksheet WS3

[SHTM 03-01 Part A – PDF page 209]

Air movement control Corridor Worksheet WS4 Reference:

Nominal pressure:______Pa

Consider all doors closed

Air flow, m3/s

Out In Remarks

Flow required through doorway to give protection

Leaks through closed doors, transfer devices, permanent openings etc Pa ∆P

Total flow inwards (S1)

Add mechanical input (S2) if necessary to increase S1 to give 7 AC/hr

Total flow outwards and inwards

SAMC = ( ∑OUT – ∑IN + S2) ____________________ Transfer to WS5

or EAMC = ( ∑IN – ∑OUT + S2) ____________________ Transfer to WS5

Note: this sheet to be used for each individual operating theatre suite (or pair of suites if they share a preparation room)

Designer ........................................................................................................... Date ......................................................

Template A8 Worksheet WS4

[SHTM 03-01 Part A – PDF page 210]

Air movement control Worksheet WS5

Reference:

Summary of air supply and extract for an operating suite

Air flow to corridor All doors closed Anaesthetic (key door

open)

m3/s m3/s

From preparation

From operating theatre

From scrub

From anaesthetic

Total (a)

Air flow to corridor

From utility

From other source

Total (b)

Other room supplies .................................................................................... Total (c)

Total air supply (a) + (b) + (c)

Consider corridor ventilation (see Appendix 3) and calculate air volume required, based on 7 AC/hr (see Note 1)

Air flow required to ventilate corridor (m3/s)

Air flow required to ventilate service corridor (see Note 2) (m3/s)

If the air flow from the operating suite (a) and (b) is greater than the calculated required volume, no further supply air is necessary

Additional air to ventilate corridor (m3/s)

Additional air to ventilate service corridor (see Note 2) (m3/s)

Air extract (m3/s)

The size of the extract plant should be of the order of 10% below the supply to assist in maintaining the department under positive pressure relative to the outside departments

Extract plant = Supply less leakage (m3/s)

Less 10% of supply

Total extract (see Note 3)

Notes:

1. In the case of a multi-theatre operating department, the air balance for the corridor should be considered as a separate exercise, taking into account the final dispersal of excess air. 2. Omit these if only one corridor in operating suite. 3. The extract volume includes 0.24 m3/s from the anaesthetic room for a balanced condition

Designer ........................................................................................................... Date ......................................................

Template A9 Worksheet WS5

[SHTM 03-01 Part A – PDF page 211]

Room temperature – summer Worksheet WS6a Reference:

Find summer supply temperature TSS = 20 – 0.828H(O/R) ____________________ = TSS ____________________ºC Q(O/R) ____________________

Note: the temperature of a space may be calculated from

t1Q1 + t2Q2 + ........... + tnQn + (0.828H) T = _______________

Q1 + Q2 + . . . Qn

Where t1 is temperature of source 1 (ºC) Q1 is flow from source 1 when all doors are closed (m3/s) H is heat gain in space (kW)

Supply Flows inwards

Room Heat gain

Temperature

From From From From From

kWh

ºC T Q TSS

Q t Q t Q t Q t Q t

Check doors to sterile areas

Maximum ∆T

Door between Calculated room

permitted Remarks

∆T (ºC)

Designer ........................................................................................................... Date ......................................................

Template A10 Worksheet WS6a

[SHTM 03-01 Part A – PDF page 212]

Room temperature – winter Worksheet WS6b Reference:

Find winter supply temperature TSW = 20 – 0.828H(O/R) ____________________ = TSW ____________________ºC Q(O/R) ____________________

Note: the temperature of a space may be calculated from

t1Q1 + t2Q2 + ........... + tnQn + (0.828H) T = Q1 + Q2 + . . . Qn

Where t1 is temperature of source 1 (ºC) Q1 is flow from source 1 when all doors are closed (m3/s) H is heat gain in space (kW)

Supply Flows inwards

Temperature

Room Heat gain

From From From From From

kWh

ºC T Q TSW

Q t Q t Q t Q t Q t

Check doors to sterile areas

Maximum ∆T

Door between Calculated room

permitted Remarks

∆T (ºC)

Designer ........................................................................................................... Date ......................................................

Template A11 Worksheet WS6b

[SHTM 03-01 Part A – PDF page 213]

Transfer grilles, pressure relief dampers and pressure stabilisers Worksheet WS7

Reference:

Transfer grilles – see paragraphs A8.34–A8.38

Pressure difference

No Location

Free area m2 Model Resultant

Flow rate m3/s

∆p Pa Remarks

Pa

Pressure relief dampers – see paragraph A8.39

Pressure difference

No Location

Free area m2 Pressure setting Pa Remarks

Flow rate m3/s

Pa

Pressure stabilisers – see paragraphs A8.40–A8.43

Note: where a stabiliser is acting both as series room door protection and operating pressure control, “pressure difference” and “flow rate” are from WS2d; “pressure setting” is from WS3

Pressure difference

No Location

Free area m2 Pressure setting Pa Remarks

Flow rate m3/s

Pa

Designer ........................................................................................................... Date ......................................................

Template A12 Worksheet WS7