Home › Scotland (NHS Scotland Assure / HFS) › SHTM 03-01 Part A › Appendix 8: Design of air- movement control schemes for operating theatres – Room temperature estimation / Appendix 8: Design of air- movement control schemes for operating theatres – Relief of excess air from operating theatre when all doors are closed

SHTM 03-01 Part A: Appendix 8: Design of air- movement control schemes for operating theatres – Room temperature estimation / Appendix 8: Design of air- movement control schemes for operating theatres – Relief of excess air from operating theatre when all doors are closed

Ventilation for Healthcare - Design and validation (SHTM 03-01 Part A) · PDF pages 195–199 of 227 · Source file: shtm-03-01-part-a-v30-feb-2022.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHTM 03-01 Part A – PDF page 195]

ignore the door leakage and so reduce the air-flow requirement (see the “designers’ notes” in Appendix 4).

Room temperature estimation

A8.45 The air-flow rate required to prevent back-flow through an open door is dependent on the temperature difference across the door. The design figures shown in Appendix 6 are based on the temperature differences that will normally occur in practice, assuming heat gains and losses in accordance with Appendix 4.

A8.46 At step 11 of the air-flow design process, the temperature differences across the doors of all rooms classed as “sterile” are calculated. Worksheet WS6 is recommended for the calculations, using the following criteria:

a. assume that the operating theatre is being controlled at 20ºC and calculate the incoming air-supply temperature as shown on worksheet WS6;

b. the calculation should be repeated for both summer and winter conditions, with an operation in progress;

c. assume all doors are closed;

d. use the room supply flow rates from WS1;

e. use the inward air flows through air-transfer devices and closed door leakages from WS2a to WS2E;

f. the formula used in worksheet WS6 is as follows:

T = (t1 Q1 + t2 Q2 + . . . + tn Qn) + 0.828H (Q1 + Q2 + . . . Qn)

where:

Q = flow rate from source (m3/s)

t = the temperature of source (ºC)

H = the room heat gain (kW).

A8.47 If the evaluated temperature differences between rooms do not exceed 2ºC, the solution is satisfactory; otherwise proceed as follows:

(i) check the assumption on which the heat gains are based;

(ii) take steps to reduce the heat gains;

(iii) if the door is to a corridor, the flow through the open door will be larger than the value given in Appendix 6. Calculate on WS3, assuming it is the “key door” with door-flow unknown, and the supply as known;

(iv) if the door leads to a room with mechanical supply, install a trimmer heater in the supply to the room controlled by either a differential thermostat or a

[SHTM 03-01 Part A – PDF page 196]

thermostat slaved to the operating theatre thermostat to ensure that T is minimised;

(v) if the door leads to a room with no mechanical supply, increase the door protection flow as follows:

Qnew = Qold 2 [∆T + 1]

A8.48 These options should be considered in this order, and (i), (ii) and (iii) should be investigated thoroughly before proceeding to (iv) or (v). The mechanical supply may need to be increased in order to achieve the desired air-change rates.

Relief of excess air from operating theatre when all doors are closed

A8.49 As the mechanical supply to the operating theatre is sized to provide an appropriate flow outwards through any door which is opened, it follows that when all doors are closed, there will be more air supplied to the operating theatre than can exit from it via leaks etc. This “excess” air can be relieved by either of the two methods described in paragraphs A8.50– 8.54.

By transfer devices via the anaesthetic room

A8.50 The transfer device (pressure stabiliser or transfer grille) between the theatre and anaesthetic room needs to accommodate an air volume of 0.46 m³/s at 20 Pa (see Appendix 6) when the door between the anaesthetic room and corridor is open. An additional 0.11 m³/s will pass through the door gaps of the theatre to anaesthetic door to give a total door flow protection figure of 0.57 m³/s through the open door between the anaesthetic room and corridor. The optimum duty for this device with all the doors closed would be 0.33 m³/s at the room differential of 10 Pa. The following equation shows how this figure is arrived at:

Q = __Q1__ (√∆P2)

∆P1

= __0.46__ (√∆20) ∆10

= 0.33m3/s

where:

Q = excess air to be vented with doors closed

Q1= airflow required for door protection through the transfer device

∆P1= nominal differential pressure with door to operating theatre closed and door to corridor closed

[SHTM 03-01 Part A – PDF page 197]

∆P2= nominal differential pressure between the operating theatre and anaesthetic room when the corridor door is open.

A8.51 If the excess air is less than 0.33 m3/s, a pressure stabiliser is required to ensure that the correct pressure and protection airflow is available to pass through the door.

A8.52 If the excess air is greater than 0.33 m3/s, a transfer grille is acceptable because at all times the airflow will exceed the flow required for pressure and door protection.

By pressure stabilisers to the corridor

A8.53 If it is undesirable to pass all the extra remaining air volume through the anaesthetic room after the door flow- protection volumes have been achieved, it may be passed from the theatre directly to the corridor via a separate pressure stabiliser.

A8.54 If there is sufficient excess air, the transfer grille solution at paragraph A8.52 should be adopted, as it provides the simplest solution and, once set up, will require no further maintenance. With less excess air, it is recommended that the air be passed through the anaesthetic room via the pressure stabilisers as at paragraph A8.51, thus keeping the number of pressure stabilisers to a minimum. Both these solutions increase the air-change rate in the anaesthetic room, but care should be taken to avoid passing excessive amounts through that would cause discomfort to the occupants.

Figure A22: Pressure stabilisers performing two tasks

[SHTM 03-01 Part A – PDF page 198]

Figure A23: An example of an air-flow network

[SHTM 03-01 Part A – PDF page 199]

Figure A24: Air-flow design procedures