SHTM 03-01 Part A: Appendix 8: Design of air- movement control schemes for operating theatres – Transfer grilles / Appendix 8: Design of air- movement control schemes for operating theatres – Pressure-relief dampers
[SHTM 03-01 Part A – PDF page 193]
Corridors
A8.31 All surplus air from the suite, except that lost through structure leakage and any passing to the outer corridor, will arrive in the patient/staff corridor. Should this air be insufficient to achieve the required air- change rate (see Appendix 3), some additional air supply should be provided. (The air balance should take account of structural leakage.)
A8.32 Whereas the resulting pressures are dependent on ductwork layout, room relationships and characteristics of the fan, the generalisations shown in Appendix 6 may be used to estimate the change in room pressure when a door is opened.
A8.33 The “key door” will be the open double door which leaves the operating theatre at the highest pressure, and/or requires the largest air flow. This should be determined using the procedure in worksheet WS3.
Transfer grilles
A8.34 These may be used to limit the pressure differences across the closed door of a single-flow room or, in some instances, for protection of a series-flow or parallel- series-flow room. They allow air flow in both directions and may not be suitable for all applications.
A8.35 The free area of a grille is calculated from the following equation:
A = __Q__ 0.84√∆P where:
A is free area (m2)
Q is flow rate (m3/s)
P is pressure difference (Pa)
0.84 is the grille's resistance- correction factor.
A8.36 The flow through a grille at a different pressure may be found from the following equation:
Q2 = Q1 √ __∆P ∆P12 where:
Q1 and P1 are original flow and differential pressure
Q2 and P2 are new flow and differential pressure.
A8.37 The transfer grille may be replaced by carefully proportioned door undercuts of the equivalent free area.
[SHTM 03-01 Part A – PDF page 194]
A8.38 The function of the transfer grille is to provide a means of air-flow control by which the volume and pressure loss can be established. If a grille is used, it should have an easily removable core to facilitate cleaning.
Pressure-relief dampers
A8.39 The functions of a pressure-relief damper are now carried out by pressure stabilisers. Accordingly, all mention of them has been removed from this document.
Pressure stabilisers
A8.40 Pressure stabilisers can be adjusted to hold the pressure constant over a wide range of flow rates. They are used where requirements exist for accurate room- pressure control or rapid shut-off on pressure fall.
A8.41 The installation of a grille or baffle in association with a stabiliser will alter the operating characteristics. It is recommended that a location be chosen to avoid the need for visual screening, for example, at high level. The location should be chosen to minimise the likelihood of damage.
A8.42 The stabilisers used should be virtually silent in operation, adjustable on site, maintenance-free and of a type which cannot be wrongly inserted. They should not be used in external walls or where the pressure difference is less than 5 Pa. The required size of a pressure stabiliser is dependent on the design pressure difference across it and flow rate through it. The manufacturer should provide data relating pressure difference to mean velocity (or flow rate per unit area). From this, the required area can be calculated and then rounded-up to the nearest size manufactured or nearest combination of smaller sizes.
A8.43 It is sometimes possible to arrange for a pressure stabiliser to perform two tasks. In an anaesthetic room, for example, the two pressure stabilisers may be made to pass the open door protection air, and also control the operating and anaesthetic room pressures with the door closed. To achieve this, the stabilisers are sized for the flow rate required with one of the doors open, but the pressure setting is adjusted to be the value required with the doors closed.
This is shown in Figure A22.
Door leakage flows
A8.44 For an air-movement control scheme to work satisfactorily, it is essential that the estimates of door-gap leakage made at the design stage are closely related to those which are achieved in practice. The calculation of gap-flows is complicated by the fact that such flows generally fall into the transition region between laminar and turbulent flow and hence do not follow the normal flow equations. The gaps assumed are 4 mm along the bottom, 3 mm at the top and sides, and 2 mm between double leaves. Doors should not have wider gaps than these. Tighter gaps would result in lower flow-rate requirements and hence lower fan power, but care should be taken to ensure that all doors in the suite have similar gap dimensions. It may be possible to