SHTM 03-01 Part A: Appendix 8: Design of air- movement control schemes for operating theatres – Air-movement control in peripheral rooms
[SHTM 03-01 Part A – PDF page 189]
open bay – the opening is larger than a normal single door opening. The bay may be
considered as part of the main room;
semi-open bay – the opening is no larger than a normal single door opening. In this
case it is possible to protect the bay from the main room by provision of air supply or extract in the bay, or by passing air to or from another area.
Air-movement control in peripheral rooms
A8.12 For the design of air-movement control, two types of air-transfer device are considered. These are transfer grilles and pressure stabilisers. Each has a particular field of application within the design, as described in paragraphs A8.34– A8.43. Air movement is controlled in each of the different room types described in paragraphs A8.13–A8.31.
Figure A14 Key to symbols
Single flow rooms
A8.13 An appropriately-sized transfer grille should be located in or adjacent to the door of each single flow room to relieve the pressure differences across the door when closed.
Figure A15 Single flow room solution high–pressure room
Parallel multi-flow rooms
A8.14 The pressure difference across the closed doors should be relieved, but transfer grilles are not appropriate where two doors lead to areas of different pressures, because reverse flow could occur when the other door is open. For this reason, pressure stabilisers are used.
[SHTM 03-01 Part A – PDF page 190]
Figure A16 Parallel, multi-flow room solution high-pressure
Figure A17 Parallel, multi-flow room solution low-pressure
A8.15 These rooms will be either high- pressure or low-pressure with respect to the adjacent areas (see preparation lay-up room and disposal room, respectively, in standard layout 5 of Appendix 7). The pressure-relief damper is always situated between the room and area, which results in the smaller differential pressure to ensure best use of air.
A8.16 Just as reverse flow can occur if transfer grilles are used, it can similarly occur via door gaps when the other door is opened. It is not possible to avoid this, except by using air locks, but due to the low flow rates and short durations involved, this is not considered to be of importance.
Parallel-series multi-flow rooms
A8.17 These rooms are similar to those in paragraph A8.14 above, but because the room is of equal cleanliness to one of the adjacent rooms, the nominal pressures will be equal and air may flow through the adjoining doorway in either direction (for example the Prep (SPS) in standard layout 6 of Appendix 7).
Figure A18 Parallel, series multi-flow room solution high-pressure
A8.18 Where the nominal room pressure equals that of the higher-pressure adjacent room, the best use of air is by supplying air required for bacterial dilution only and allowing this to exhaust via a transfer grille to the area of equal cleanliness. The doorway to the lower pressure area is protected by the combination of the supply air and the air that will flow inwards through the transfer grille from the area of equal cleanliness.
[SHTM 03-01 Part A – PDF page 191]
Figure A19 Parallel, multi-flow room solution low-pressure
A8.19 Conversely, where the nominal pressure equals that of the lower-pressure adjacent room, extract ventilation and a transfer grille to the lower pressure adjacent room should be provided (for example the disposal room in standard layout 8 of Appendix 7).
Series multi-flow (unbalanced)
A8.20 These rooms are somewhat similar to those in paragraph A8.15 above, but because the pressure lies between that of the rooms on either side, the back-flow problem does not exist.
Figure A20 Series, multi-flow room solution medium-pressure
A8.21 Where the room has a net surplus of mechanical supply air, a transfer grille should be located in or adjacent to the door through which air flows outwards, and the mechanical supply flow rate to the room should be chosen to give protection when this door is open.
A8.22 Where the room has a net surplus of mechanical extract air, a transfer grille should be located adjacent to the door through which the air flows inwards, and the mechanical extract flow rate to the room should be chosen to give protection when this door is open.
A8.23 The grille should be sized for the protection requirement of the opposing door when open. When the room on the high-pressure side depressurises, there is a possibility of back-flow through gaps around the door, but this problem may be ignored.
Series multi-flow (balanced)
A8.24 In these rooms, a transfer device adjacent to each doorway is required in order to provide a flow path for the air required to protect the opposing door when opened.
[SHTM 03-01 Part A – PDF page 192]
Figure A21 Series, multi-flow room solution medium-pressure
A8.25 These transfer devices will normally be pressure stabilisers, although transfer grilles may be used where a large amount of excess air is to be exhausted from the operating theatre when all doors are closed (for example anaesthetic rooms).
A8.26 The calculation procedure is to assume that pressure stabilisers are being used; then – if there is sufficient excess air – change to transfer grilles as described in paragraph A8.50.
Bay
Open bay
A8.27 A bay of the open type (for example scrub-up) is considered to be part of the operating theatre. There should be an active or passive extract/pressure stabiliser under, or directly adjacent to, the scrub trough.
Semi-open bay
A8.28 In a bay of the semi-open type, protection of one area from the other is possible (for example scrub-up).
A8.29 As stated previously, the need for protection between operating theatre and scrub- room is not very great. Better use of air can therefore be achieved in this case by installing a pressure stabiliser between the scrub-room and clean corridor. This will allow a flow of air through the scrub-room at all times, except when a door is opened elsewhere in the suite. The pressure stabiliser will then close and the air will be diverted to the other door. When it is considered necessary to protect the scrub- room at all times, either a transfer grille to the corridor or mechanical extract in the scrub-room should be provided.
Operating theatre
A8.30 Once the peripheral rooms have been considered, the operating theatre requirements may then be decided and the supply flow rate required for air- movement control calculated. This flow rate should be such that, with any one door open, the correct air movement directions are maintained. There will be one door in the suite that will require the largest supply flow rate to the operating theatre for protection when open. This is called the “key door” and is discussed separately in paragraph A8.33. Use of this concept avoids repetitive calculations for each door in turn. Having established the required supply flow rate, a relief route should be provided to the clean corridor for any excess air when the doors are closed. This would be via transfer grilles or pressure stabilisers through a series-flow room or via pressure stabilisers to the clean corridor directly.