Home › Scotland (NHS Scotland Assure / HFS) › SHTM 03-01 Part A › Appendix 10: Example cause-and- effect check-sheets

SHTM 03-01 Part A: Appendix 10: Example cause-and- effect check-sheets

Ventilation for Healthcare - Design and validation (SHTM 03-01 Part A) · PDF pages 216–218 of 227 · Source file: shtm-03-01-part-a-v30-feb-2022.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHTM 03-01 Part A – PDF page 216]

Appendix 10: Example cause-and- effect check-sheets

Example cause-and-effect check-sheet for general theatre or imaging suite

Site Date

Area served System ID

Test AHU Checks Y/N TCP Indication Y/N

1 AHU Off Supply and extract dampers closed Red

2

Supply damper open Extract damper open Red

Switch AHU “On”

Supply fan start and run Extract fan start and run Red

Prove airflow Green

3 Switch AHU to “Set Back” Supply fan slows Extract fan slows Red

4 Switch AHU to Operational speed

Supply fan speeds up Extract fan speeds up Green

Yellow display information

5 End of day 10 minute warning that system will switch to “Set Back” (Not all TCPs have this facility)

box

Do nothing System goes to “Set back” Red

Reset to full speed Green

Yellow display information

6 End of day 10 minute warning that system will switch to “Set Back” (Not all TCPs have this facility)

box

Press “Continue” System stays at full speed for 1 hour Green

7 Supply fan fail System shuts down Red

Reset system to normal Green

Yellow display information

8 Extract fan fails Warning on TCP and BMS. AHU locks out if fault not rectified by following day

box

Reset system to normal Green

9 Theatre/Imaging room temperature to be stable at 20°C at the start of this test.

Reduce set point temperature Chiller battery valve opens fully Set temp: to lowest possible on TCP Record min temp reached and time oC taken to stabilise. Measured: oC Ind (TCP) oC Time taken mins

Set temp:

10 Increase set point temperature to highest possible on TCP

Heater battery valve opens fully. Record max temp reached and time taken to stabilise.

oC

oC Measured: Ind (TCP) Time taken

oC mins

Reset set point to 20oC Green

Red

11 Switch AHU “Off” Extract fan stops Supply fan stops Extract damper closes Supply damper closes

Template A13 Example cause-and-effect check-sheet for general theatre or imaging suite

[SHTM 03-01 Part A – PDF page 217]

Example cause-and-effect check-sheet for ultra-clean theatres

Site Date

Area served System ID

Test AHU/UCV Checks Y/N TCP Indication Y/N

1 AHU Off Supply and extract dampers closed Red

2

Supply damper open Extract damper open Red

Switch AHU “On”

Supply fan start and run Extract fan start and run Red

Prove airflow UCV "Off" Red

3 Switch AHU to “Set Back” Supply fan slows Extract fan slows Red

4 Switch AHU to Operational speed

Supply fan speeds up Extract fan speeds up –

5 AHU at operational speed Switch UCV on in “Low speed” Amber = “Conventional

Theatre mode”

Press “UCV mode” UCV goes to “Full speed” Green “UCV Theatre Mode”

UCV goes to “Low speed” Amber

Press ”Conventional Theatre mode”

6 Switch AHU to “Set Back” UCV goes to “Low speed” or “Off” Red

Reset system to normal UCV stays in “Low speed” Amber

7 Switch UCV “Off” UCV fans stop Red

Reset system to normal with UCV at full speed Green

8 Fail each UCV quadrant fan in turn and Coanda fans (4 + 2) Red

Reset system to normal with UCV at full speed Green

9 Trigger HEPA filter high pressure switch Green plus Blue light

Yellow display information

box

10 End of day 10 minute warning that system will switch to “Set Back” or “Off” (Not all Theatre Control Panels have this facility)

Do nothing AHU & UCV go to “Set back” or “Off” Red

Reset to full speed including UCV Green

Yellow display information

box

11 End of day 10 minute warning that system will switch to “Set Back” or ”Off” (Not all Theatre Control Panels have this facility)

Press “Continue” System stays at full speed for 1 hour Green

12 Supply fan fails System shuts down. UCV to “Low speed or Off” Red

Reset system to normal Green

Yellow display information

box

13 Extract fan fails Warning on TCP and BMS.AHU locks out if fault not rectified by following day

Reset system to normal and UCV to full speed Green

Site Date

Area served System ID

[SHTM 03-01 Part A – PDF page 218]

Test AHU/UCV Checks Y/N TCP Indication Y/N

14 Theatre temperature to be stable at 20°C at the start of this test.

Chiller battery valve opens fully

Reduce set point temperature to lowest possible on TCP

Record min temp reached and time taken to stabilise

Set temp: oC Measured: oC Ind (TP) oC Time taken mins

Heater battery valve opens fully

15 Increase set point temperature to highest possible on TCP

Record max temp reached and time taken to stabilise

Set temp: oC Measured: oC Ind (TP) oC Time taken mins

Reset set point to 20ºC Green

Red

16 Switch AHU “Off” Extract fan stops Supply fan stops Extract damper closes Supply damper closes UCV drops to “Set back”

Note any additional tests or checks below

Template A14 Example cause-and-effect check-sheet for ultra clean theatre