SHTM 03-01 Part A: 9. Equipment Selection Factors – Supply AHUs and associated extract units (pages 93–100)
[SHTM 03-01 Part A – PDF page 93]
greenhouse gas emissions are minimised. Refrigerant gas monitoring must be included where required under BS EN 378.
Chiller selection: size and resilience
There is a tendency to meet the calculated maximum chiller load by specifying multiples of a standard size of chiller (for example, the calculated load to be met by three chillers each capable of 33% and an extra chiller of the same size to achieve the N+1 resilience requirement). This approach does not lend itself to efficient operation. It is preferable to split the load with, for example, two chillers capable of 40% each and two capable of 25% each. This will give an overall minimum capacity of 90% resilience at maximum summer design conditions and allow for the actual part load demand to be met in the most energy-efficient way.
Supply AHUs and associated extract units
Typical sequence of components
The AHU should be arranged so that most of the items are under positive pressure. Cooling coils and humidifiers will require a drain and should be on the positive pressure side of the fan. The following arrangement of components is typical, although in many instances not all elements will be required:
fresh air intake;
motorised isolation damper;
fog coil if energy recovery fitted or frost coil if no energy recovery fitted;
pre-filter;
energy-recovery device (possible location);
attenuator1;
supply fan;
attenuator1;
energy-recovery device (possible location);
cooling coil;
eliminator (for face velocities above 2 m/s);
heater-battery;
humidifier (if required);
final filter;
motorised isolation damper.
AHUs may be configured as horizontal, linear single or double-stacked; or as cabinet type units. For double-stacked supply/extract units, the fans should be located on the bottom deck where possible as it will make them simpler and safer to change (see Figures A1–A3 in Appendix 1 for possible arrangement.).
[SHTM 03-01 Part A – PDF page 94]
Intakes and discharges
Air intakes and discharge points should preferably be located at high level, to minimise the risks of noise nuisance to surrounding buildings, contamination and vandalism.
Intakes and discharges should be designed and located so that wind speed and direction have a minimal effect on the plant throughput.
Helicopter landing pads in the vicinity of ventilation intakes and discharges can result in large short-term pressure changes. This can cause pressure surges in supply systems and reverse airflows in extracts. Exhaust fumes from the helicopter may also be drawn into intakes.
Note: It is not appropriate to “plan to turn the ventilation off when a helicopter lands” as a means of permitting the location of a helipad adjacent to ventilation intakes and discharges.
Intake points should be situated away from cooling towers, heat sources, boiler flues, vents from oil storage tanks, fume cupboards and other sources of contaminated air, vapours and gases and places where vehicle exhaust gases may be drawn in.
Note: Attenuators may be located in the intake and discharge duct if they are of a suitable type and provided with cleaning access both sides (see paragraph 9.116).
Note: Steps should be taken to prevent birds landing or roosting in the vicinity by removing ledges or fitting anti-pigeon spikes.
On the rare occasions where intakes have necessarily to be sited at or near ground level, the surrounding area should be paved or concreted to prevent soil or vegetation being drawn in. In addition, intakes should not be situated near established gardens/trees so as to avoid intake of environmental microorganisms. They should be caged or located within a compound to restrict unauthorised access and prevent rubbish being left in the vicinity. The likely proximity of vehicle exhausts should also be taken into account when determining the protected area around the intake and additional filtration may be required. The VSG should be consulted about the standard of air quality required. There should be a minimum 4 m clear zone around the intake (see paragraph 9.50 and paragraphs 9.63–9.64).
The discharge from an extract system will be located so that vitiated air cannot be drawn back into the supply air intake or any other fresh air inlet. Ideally, the extract discharge will be located on a different face of the building from the supply intake(s). At all times, there has to be a minimum separation of 4 m between them, with the discharge mounted at a higher level than the intake.
Note: Ventilation intakes and discharges cannot face each other across a passageway or courtyard even if they are 4 m or more apart.
Each intake and discharge point should be fitted with a corrosion-resistant weatherproof (BS EN 13030 class B) louvre or cowl to protect the system from
[SHTM 03-01 Part A – PDF page 95]
driving rain. Louvres should be sized based on a maximum face velocity of 1.5 m/s in order to prevent excessive noise generation and pressure loss.
Note: If there is a bend in the ductwork directly behind a louvre, it will affect the air velocity through the louvre. This may result in moisture carry-over or increased noise.
The inside of the louvres should be fitted with a mesh of not less than 6 mm and not more than 12 mm to prevent infestation by vermin.
The duct behind a louvre should be self-draining. If this is not practicable, it should be tanked and provided with a drainage system.
Cleaning access should be provided either from the outside via hinged louvres or by access doors in the plenum behind the louvre. Where a floor-level common plenum is provided, cleaning access should be via a walk-in door. High-level plenums should be able to be safely accessed by temporary or permanent means
Note: Builders’ work plenums or intake ducts will need to have a smooth finish and be surface-sealed to prevent dust shedding (see paragraph 10.5).
Fans
Direct-drive electronically commutated (EC) fans are the preferred choice for ventilation systems. If necessary, resilience and an increased capacity can be achieved by installing two or more EC fans with gravity or motorised dampers to prevent backflow.
Note: At the time of writing the concept of a “fan wall” made up of multiple small variable speed fans all controlled as a single unit was under development. This concept has several advantages as the failure of one fan can be accommodated by speeding up the rest. Because the fans cover the full area of the duct, it will result in a more uniform air velocity downstream at the battery face. This will increase the heat transfer efficiency and may allow a reduction in battery size. Nothing in this document will preclude the use of such innovation that improves resilience and reduces energy usage.
For an application outside of the capacity range of EC fans, direct-drive plug fans controlled by an inverter mounted externally to the air stream may be selected.
In either case, the fan motor will be protected with a high-temperature safety cut-out.
Whichever type of fan is selected, if it serves a critical area it will be fitted in a way that allows it to be changed within 20 minutes. Mounting the fan unit on slide rails with plug and socket connections for power and control cables will facilitate this. Whenever possible, both supply and extract fans should be located on the bottom deck of a double-stacked AHU.
Selecting fans from a preferred size range will reduce the number of spares held.
Belt- and pulley-driven fans should not be installed in healthcare ventilation systems.
Supply fans should be positioned to blow through the central plant so that the cooling coil and humidifier drains (when fitted) will be under positive pressure. The energy-
[SHTM 03-01 Part A – PDF page 96]
recovery device may be either side of the fan and should have a drainage system on the extracted air discharge side.
In extract systems where the air is potentially contaminated, explosive, aggressive or has a high moisture content, the extract fan motor will be located outside the air stream and be capable of being changed without the need to access or change the fan impeller.
Control
Where two or more fans are fitted in a fan wall, the preferred normal operation is all fans running in parallel. In case of a single fan failure the remaining fan(s) should provide at least 80% of the design output.
For most healthcare applications, the fan output should be set to give a constant volume of air. This should be controlled by measuring the pressure drop across the fan suction nozzle using a sensing ring and associated volume controller that will automatically integrate the fan K factor to determine and control the preset output air volume. The fan output will then in air volume terms remain constant regardless of changes of system resistance. The actual volume delivered will be related to the air- change rate for the application.
Note: Measuring the air pressure in the main supply duct and using that to set the supply fan speed as a percentage of its rated output and using that to set the extract fan speed as a percentage of the supply fan speed is not a satisfactory, accurate or an acceptable way of controlling the desired supply and extract air volumes.
Filters
The purpose of filtration is to reduce the level of airborne contamination in an air stream. It is generally carried out in stages
Filters should be securely mounted in well-fitting frames designed so that the airflow pushes the filter into its housing to minimise air bypass. Vertical supports with seals should be provided to master the joints between filters and eliminate bypass. Mounting frames that withdraw so that the filter can be changed without having to reach into the unit are preferred.
Filters need to be readily accessible, so a hinged access door should be provided. The upstream side of the filter should be visible for inspection through a viewing port with internal illumination.
For AHUs, provided that each filter’s pressure drop is monitored by a sensor linked to the BMS, direct reading gauges or manometers will not be required. Capped pressure tappings should be provided so that a portable manometer can be connected for diagnostic purposes when necessary.
General air filters (see Table 9) are divided into four categories, related to the size of particle (in microns (µm)) that they can remove as a percentage of the load.
coarse filters – remove less than 50% of 10 µm particles;
PM10 medium filters – remove 50 to 95% of 10 µm particles;
[SHTM 03-01 Part A – PDF page 97]
Table 9: General filters: typical healthcare selections ISO 16890 Class Notes and typical healthcare ISO Coarse 60% May be used as temporary addition filtration at an air intake when building or demolition works are being undertaken in the vicinity ISO ePM10 ≥50% Panel pre-filter or return air filter to protect the energy-recovery device ISO ePM2.5 ≥50% Supply air filter for areas with temporary occupancy ISO ePM1 ≥50% Supply air filter for areas with permanent occupancy
PM2.5 medium filters – remove 50 to 95% of 2.5 µm particles;
PM1 fine filters – remove 50 to 95% of 1 µm particles.
Note: Ventilation filters can only remove particles from the incoming air. Most particles that could cause an infection originate from the occupants and activities within the building. In AHUs the pre-filter and return air filter will keep the energy- recovery device, cooling coil and heater-batteries clean and working efficiently. The secondary filter will keep the distribution ductwork and supply air terminals clean.
Note: For additional information on filter selection and indoor air quality, see the Specialised Ventilation for Healthcare Society’s (2018) SVHSoc.02 – ‘Change in air filter test and classification standards’.
In areas of high atmospheric pollution, a higher standard of filtration may be required in order to meet the indoor air quality standard (IAQ).
Compact filters are preferred, because bag filters are often incorrectly oriented and prone to damage when changed.
Efficiency and high efficiency particulate air (EPA and HEPA) filters
These filters are designed to provide filtration of particles in the sub-micron size range. EPA and HEPA filters self-select the particle that they are least able to trap and are graded against that “most penetrating particle size” (MPPS) (see Table 10):
efficiency particulate filters (EPA): three grades E10 to E12;
high efficiency particulate filters (HEPA): two grades H13 to H14;
ultra-low particulate air filters (ULPA): three grades U15 to U17.
Table 10: EPA and HEPA filters: typical healthcare selections
Typical healthcare
% Efficiency
application
Minimum filter grade to BS EN 1822 - 2019
EPA – E11 – (EU11) 95
@ MPPS UCV theatre terminal EPA – E10 – (EU10) 85 No standard healthcare application
EPA – E12 – (EU12)
Immunosuppressed and neutropenic patient rooms or wards
[SHTM 03-01 Part A – PDF page 98]
Typical healthcare
% Efficiency
application
Minimum filter grade to BS EN 1822 - 2019
HEPA – H13 – (EU13)
@ MPPS No standard healthcare application
HEPA – H14 – (EU14)
Pharmacy aseptic preparation facility supply Containment level 3 room extract
*Incorporates ISO 29463 tests methods.
Note: ULPA filters are designed to remove particles below a size that is either surgically or aerobiologically significant. There would have to be exceptional circumstances in order to justify their use in a healthcare ventilation system.
EPA and HEPA filters are expensive, so their use should be kept to a minimum. When used they should be of the replaceable panel type with leakproof seals and installed in a manner that permits the validation of the filter and its housing (see Chapter 12).
In supply systems an EPA or HEPA filter will have a non-shedding metal case.
Return air and extract air filters
Return air filtration will always be required where heat recovery devices are installed. Return air filters are also used to reduce the load on EPA filters in recirculating applications such as ultra clean operating suite ventilation canopies and pharmacy aseptic preparation facilities. They should be the same grade as their AHU pre-filter.
EPA or HEPA filters are sometimes fitted in extract systems to capture hazardous substances or organisms. Design provision should be made for the subsequent safe handling of contaminated filters by maintenance staff. This may be achieved by:
sealing the hazardous substance into the filter before it is removed;
providing a system to fumigate the filter to kill any organisms;
housing it in a “safe change” unit that permits the filter to be ejected into a bag and sealed without personnel having to come into direct contact with it.
Notes:
1 In view of the costs and problems associated with placing EPA or HEPA filters in extracts, it is essential that a full risk assessment be carried out at the design stage. This should include defining the true need for a filtered extract, the validation of its performance at installation, the method of safely changing a contaminated filter, and its subsequent disposal.
2 General extracts from mortuaries and post-mortem rooms may contain odours, but these are not in themselves hazardous to health and do not require filtration prior to discharge. In high-risk post-mortems (for example, known or suspected tuberculosis cases), the infected organs will be removed and then dissected in a class 1 microbiological safety cabinet provided under the COSHH Regulations.
[SHTM 03-01 Part A – PDF page 99]
Extracts from infectious disease Isolation rooms or wards do not normally require filtration prior to discharge. However, if the discharge cannot be made in a safe location and it is likely that the vitiated air could be drawn back into the building or there are people in its vicinity (for example, a discharge into a courtyard), filtration would be required
Extract EPA or HEPA filters should have a particleboard or plywood case so that they can be incinerated.
Activated carbon filters
Activated carbon filters can remove gases and vapours from an air stream and are graded according to the range of substances they can remove. They are not normally fitted in air-conditioning supply systems. They are occasionally fitted retrospectively because an air intake has been poorly sited and is drawing in noxious fumes or the outdoor air quality is exceeding WHO levels for NOX/O3 or SOX. Where used they should be protected by or incorporated into a particulate air filter.
Activated carbon filters are more commonly used in specialised fume extraction systems when the location of the discharge means that dilution cannot be relied upon to disperse noxious fumes.
Energy-recovery devices
General requirements
Energy recovery will be fitted to all supply and extract healthcare ventilation systems. It may be omitted only where permitted by the current ErP Directive EU 1253/2014.
For most systems in healthcare premises, a plate heat exchanger, “run- around coil” system or thermal wheel would be appropriate. Selection should be based on the relative locations of the supply and extract units, ease of maintenance and practicality. Cleaning access will be required to both sides of any energy-recovery device.
Note: Plate heat exchangers are the preferred option as they require the least maintenance to retain their energy transfer efficiency. Thermal wheels may be used, as the degree of air transfer from extract to supply is not sufficient to cause aerobiological problems and in any event the air will be filtered before being supplied to the user. Run-around coils are used when the supply and extract units are separate or in case of space problems.
At the time of writing, the following are the minimum energy transfer efficiencies required under EU 1253 for devices handling equal air volumes:
run-around coil – 68%;
plate heat exchanger – 73%;
thermal wheel – 73%;
heat pipe – 73%;
heat pump or any other device – see specific regulations.
[SHTM 03-01 Part A – PDF page 100]
Note: These efficiencies are regularly reviewed and are likely to be increased periodically.
If a plate heat exchanger is chosen, the plates should be constructed of metal; in coastal areas stainless steel is preferred. Plastic should not be used for the plates, internal bypass dampers or gears. (This is in keeping with the reduction in the use of single use plastics.)
If a thermal wheel is selected, only a sensible heat wheel should be used that incorporates a purge sector. In order to reduce bypass leakage, brush seals should not be used; enhanced airtightness seals should be fitted.
Whichever energy-recovery device is chosen, the extract side should be protected by at least an ISO ePM10 ≥50% filter and provided with a drainage system as described in paragraphs 9.105−9.112, to remove condensate. Note that most condensate will occur at intermediate rather than at extreme outside air conditions.
The energy-recovery device should be located downstream of the fog coil and pre- filter, before the cooling coil and main heater-battery. It may be on either side of the supply fan.
It is essential to consider the set points and control of the fog coil, energy- recovery device, cooling coil and heater- battery in order to achieve the most efficient operation for the maximum time. The primary energy provided by the fog coil will directly reduce the heat exchange of the energy-recovery device. To this end, the off- coil setting of the fog coil should be the minimum possible to keep the pre-filter dry (2 to 3 K above intake air temperature) (see paragraph 9.75 onwards for further guidance).
The energy-recovery device should be controlled in sequence with the main heater- battery and should incorporate a control to prevent the transfer of unwanted heat when the air-on condition rises above the required plant set-point.
In instances where the plant is cooling the air, it may be possible to remove heat from the supply air at high ambient conditions, under the dictates of enthalpy sensors in the intake and extract ducts.
Heater-batteries
General requirements
Fog coils are installed to protect the downstream filters from low temperature, high humidity intake air conditions. They should raise the incoming air temperature by 2 K so that it is above its dew-point when it arrives at the filter. As they handle unfiltered air they should be constructed of plain tubing without fins and be as near to the outside as possible to minimise condensation during cold weather. Access for cleaning should be provided to both sides of the coil. In order to prevent them freezing they should be controlled as constant flow variable temperature devices.
Traditionally frost coils were set to raise the incoming air temperature to between +2ºC and +5ºC to protect the batteries downstream. All new AHUs should be equipped with an energy-recovery device (see paragraph 9.65); the greater the temperature difference across this device, the more heat will be recovered. Also, the