SHTM 03-01 Part A: 8. Specific Healthcare Department Requirements – Hydrotherapy: general requirements
[SHTM 03-01 Part A – PDF page 82]
Facility Applicable Standards Endoscope Decontamination Unit
These are highly regulated production facilities dictated by:- Planning note - Scottish Health Planning Note 13. Part 3 – Decontamination Facilities: Endoscope Decontamination Units, HFS 2010 Mandated by compliance document - Requirements for Compliant Endoscope Decontamination Units, v2 – GUID 5013 HFS 2014 Equipment manufacturer’s design and installation instructions
Hydrotherapy: general requirements
In a hydrotherapy suite, heat recovery should be via a heat pump.
In general, the quantity of supply air should be calculated as 25 L/s/m2 wetted surface, with the wetted surface taken as 110% of the pool water surface area. (See the Swimming Pool and Allied Trades Association (SPATA) for detailed guidance.)
A recirculation plant is recommended, with fresh air make-up to the standard required by the Building Regulations Part F – Non-domestic Buildings. In practice this may need to be increased to control condensation.
As far as practicable, recirculated pool air should be provided to the ancillary changing and recovery accommodation, with the only extract from the toilets, laundry/utility room and pool hall.
Supply air to the pool hall should be introduced at high level and directed towards the perimeter to mitigate condensation, with extract air taken from directly over the pool.
The ceiling void above the pool may need to be ventilated to prevent condensation.
Control of hydrotherapy pool installations
The supply and extract fans should be interlocked so that the supply fan does not operate until flow is established within the extract system.
Time-clock control should be provided, with a local override switch to extend the normal operating period as required.
Night set-back temperature (in the range of 21–25ºC) and high humidity control (in the range of 60–75% sat) should be provided to override the time clock in order to prevent condensation. The exact set points should be ascertained post- installation.
A remote indication panel should be provided in the pool hall, giving a visual display of the pool water and pool air temperature.
Extract systems
LEV systems
Devices that use an inflow of air to control exposure of staff to hazardous substances are classified as local exhaust ventilation (LEV) systems under the COSHH
[SHTM 03-01 Part A – PDF page 83]
Regulations. Note that the supply or make- up air to a room containing an LEV system may itself be considered to be a part of the LEV system.
An LEV system may comprise a self- contained unit incorporating its own carbon filter such as a simple bench-top fume cupboard. Alternatively, it may be a complete “ventilation system” comprising a make-up air supply, multiple exhaust protected workstations, branch and central extract ductwork, duplex extract fans and a high- level discharge terminal. It may also incorporate a special filtration system appropriate to the hazardous substance being controlled. Such systems could be required for workshops containing woodworking machinery or large centralised pathology laboratories housing multiple safety cabinets, cut-up benches, fume cupboards and specimen stores.
It is important to recognise at the design stage whether an extract is being provided for comfort, to remove odours or as an LEV system. Typical LEV systems in healthcare include:
microbiological safety cabinets and containment level 3 rooms;
fume cupboards;
welding fume extracts;
woodworking-machinery duct collectors;
lead-acid battery charging-bay extracts;
powered plaster and bone saws;
pharmaceutical preparation cabinets and tablet machines;
dissection benches, cut-up tables and some specimen stores;
medium- and high-risk infectious diseases isolation facilities;
dental furnaces, grinders and polishers.
Note: Post-mortem tables may incorporate downflow peripheral ventilation but unless otherwise specified by the equipment supplier, their ventilation is only provided to control odours.
Information on the design of ductwork, fan and discharge stack arrangements will be applicable to all types of LEV system and is given in Chapter 9.
LEV systems are statutory items that will be subject to an independent examination and test at least every 14 months by a competent person holding an in-date P601 certificate.
Note: For AGSS, see Scottish Health Technical Memorandum 02-01.
Bench extract systems
Bench extract ventilation is required in departments such as pathology and mortuary, where activities involve the release of malodorous or toxic fumes which should not be inhaled. They may also be required in central decontamination units and wash-rooms within endoscope reprocessing units to remove airborne biological material liberated when the used items are given a preliminary clean.
[SHTM 03-01 Part A – PDF page 84]
In all cases bench extract systems that create an airflow from the front to the rear are preferred over those that rely on a downflow of air through a perforated surface, as the airflow is easily obstructed when in use.
Typical arrangements
Each ventilated position will usually be accommodated in a continuous run of benching, which should not be more than 650 mm from front to rear and which should be provided with a continuous upstand at the rear. Each position should have a 1200 mm × 150 mm linear extract grille mounted on a purpose-designed plenum box (incorporating guide vanes as necessary), with its face flush with the upstand. The bottom of the grille should be as close as practicable to the level of the working surface (usually 75 mm above, to allow for cleaning). The minimum velocity across any part of the grille should be 1 m/s. The grille should be readily demountable to allow for cleaning.
Control of bench extract systems
Provided that it does not interfere with the operation of the department when not in use, the ventilation system for the bench extract and any associated supply may be shut down. However, a run-on timer with a minimum setting of 30 minutes should be provided. To this end, local control should be provided.
Processes that produce hazardous vapours, fumes, dusts or noxious vapours should be enclosed or semi-enclosed in a suitable cabinet or exhaust-protected workstation (LEV).
Microbiological safety cabinets and fume cupboards
Safety cabinets and fume cupboards are devices that have an inflow of air to control exposure of staff to hazardous substances. The units and their exhaust systems, filters, fans and discharge terminals are all classified as LEV systems under the COSHH Regulations. The make-up air system to a room that contains an LEV system may also be considered as an essential part of the system and be included in the LEV classification.
Special requirements
The supply air system should not distort the unidirectional and stable air pattern required for fume cupboards and microbiological safety cabinets. In general, supply air ceiling diffusers should not discharge directly towards fume cupboards or safety cabinets, unless the terminal velocity is such that the airflow pattern at the front of the cabinet is unaffected. The design should ensure that high air-change rates, and/or the opening and closing of doors, do not have any adverse effect on the performance of safety cabinets or fume cupboards. A damped door closure mechanism may help.
Arrangements for safety cabinet installations
The manufacture and installation of microbiological safety cabinets will be in accordance with the relevant national standards and guidance issued by the Advisory Committee on Dangerous Pathogens (ACDP).
A Class 1 microbiological safety cabinet will be specified for routine work involving Group 3 pathogens. It should be housed in a containment level 3 room. Specific
[SHTM 03-01 Part A – PDF page 85]
design information on containment rooms is issued by ACDP in conjunction with the Health and Safety Commission.
Siting and installation of microbiological safety cabinets are of particular importance because:
the protection afforded to the operator by the cabinet depends on a specific and stable unidirectional airflow through the open front;
the protection to the environment by the cabinet depends on the high-efficiency particulate air (HEPA) filters. The exhaust air should never be considered as totally free from microbiological hazard.
Microbiological safety cabinet extract is HEPA filtered prior to being discharged to outside. Current standards permit the installation of microbiological safety cabinets with integral fans, provided that the extract ductwork can be kept short (that is, less than 2 m); such an installation, however, is likely to be noisy and is not recommended for use in new buildings.
Ductwork and discharge arrangements should be as set out in Chapter 9.
Discharge should be to outside but where this is impracticable, discharge into the room via a double HEPA filter will be accepted if approved in writing by the VSG.
Arrangements for fume cupboard installations
The manufacture and installation of fume cupboards will be in accordance with the relevant national standards and associated guidance.
The primary factors which contribute to the effective performance of fume cupboards include:
an adequate volume of supply air and its means of introduction;
an effective exhaust system to promote the safe dispersal of waste products to atmosphere.
The air velocities through sash openings should be enough to prevent hazardous materials from entering the laboratory while avoiding excess flow rates that interfere with the investigation process. Average face velocities should be between 0.5 and 1 m/s, with a minimum at any point within 20% of the average, the upper end of the range being applicable to the containment of materials of high toxicity. The design velocity should be maintained irrespective of whether the sash opening is varied, or whether doors or windows are open or closed (see BS EN 14175).
The possibility of a fire or explosion which may not be contained by a fume cupboard should always be considered. A fume cupboard should not, therefore, be sited in a position where exit to an escape route will necessitate passing directly in front of it.
Control of extract systems
It is desirable to provide local control of safety cabinets in order to maximise the life of the HEPA filter, and to permit the sealing of the cabinet and room for fumigation if spillage occurs.
[SHTM 03-01 Part A – PDF page 86]
To cope with the risk of an accident or spillage outside safety cabinets, a panic button should be provided to switch off the supply to that area and to discharge all extracted air to atmosphere.
In pathology departments, it will always be necessary to have one or more microbiological safety cabinets and one or more fume cupboards available for use, including weekends; therefore, local overriding controls for all these items and any associated ventilation plant will be necessary.
Hood extract systems
Special requirements
Extract canopies will be required over steam-and-heat-emitting appliances, for example sterilisers, catering and washing equipment and for the extraction and removal of unpleasant odours. These installations are for the control of non- hazardous airborne contaminants, they are not LEV systems.
Perimeter drain gulleys and corrosion-proof grease eliminators should be provided on kitchen hoods (see BESA DW 172 – ‘Specification for kitchen ventilation’).
Typical arrangements
The airflow rate should be enough to ensure an adequate capture velocity in the vicinity of the process. Advice from equipment suppliers should be sought, as excessive velocities will be wasteful of power and generate noise.
The lowest edge of the canopy should be 2 m above finished floor level, with a minimum of 300 mm overhang beyond the edge of the equipment on all sides.
A compact arrangement of equipment (but with access for maintenance) will minimise the canopy area, and hence reduce the air volume necessary to achieve the optimum capture velocity.
Hoods required for the control of heat gain and vapours may be connected to the general extract system when it is convenient to do so, but where non- corrosive ductwork materials are necessary, a separate extract system is preferred.
Lighting and internal divider plates are often required to be built into the perimeter of large canopies; however, built-in shelving systems are not recommended, as they interfere with the airflow, and constitute a maintenance problem.
Control of hood extracts
Provided that it does not interfere with the operation of the department when not in use, the ventilation system for the hood extract and any associated supply may be shut down. To this end, local control should be provided.
Plantroom ventilation
General requirements
Plantrooms are required to be ventilated in order to maintain acceptable temperatures for satisfactory operation of the plant and controls, and for maintenance activities. Natural ventilation through louvred openings protected from infestation by a
[SHTM 03-01 Part A – PDF page 87]
mesh with openings of no less than 6 mm and no more than 12 mm are required. Powered plantroom ventilation should only be needed if natural ventilation is not adequate.
Ventilation requirements should consider all heat sources within a plantroom, and where there are large glazing areas, solar gains. The ventilation rate should limit the maximum temperature within the plantroom to 32ºC.
Air handling equipment cannot be located in a fire compartment that houses combustion equipment.
AHUs and other ventilation equipment that serve occupied areas cannot draw their intake air from a plantroom. Neither should extract ventilation plant or medical vacuum pumps discharge air into a plantroom.
Statutory regulations for plantroom ventilation are contained in the Building Regulations, and further guidance in the CIBSE Guide B2. Note the need to assess the risk of services to AHUs freezing in unheated plantrooms.