[SHTM 03-01 Part A – PDF page 78]

Other application-specific design guidance

Application: Bronchoscopy, Endoscopy, Dental and General treatment facilities

Table 2: Treatment and procedure facilities

Area/zone Reason for ventilation Typical design factors Bronchoscopy procedure room

Control of exposure of staff to airborne pathogenic material discharged by the patient e.g. multi-drug- resistant tuberculosis (MDR-TB) during the procedure being undertaken. (COSHH Regs) Control of exposure of staff to waste anaesthetic agents when used. (COSHH Regs)

As above and odour control

Endoscopic procedure room

Establish a clean airflow path – Supply terminal at high level at foot end of patient’s chair/couch and extract terminal at patient’s head level behind the chair/couch. Design parameters Air change: 15 per hour Pressure regime: Where patient membranes are breached and the procedure would present an infection risk to the patient, the pressure should be +10 Pa to the corridor. In Bronchoscopy and all other Endoscopy procedure rooms –5 Pa to corridor shall be established. (NOTE The decision as to the preferred pressure regime for each room must be made at design stage. They must not be designed and set up as switchable pressure rooms) Noise level: 40 d(B)A Temp range: 20 to 25ºC must maintain any selected set point in the range via BMS Humidity: Floating; max 70%RH Air quality: BS EN 16798 - SUP2 Extract discharge – Discharge in safe position away from people or open windows. If no suitable position available treat the discharge in the same way as a LEV with a discharge stack at a minimum of 3 m above the roof line.

Dental treatment room Control of exposure of staff to airborne pathogenic material discharged by the patient during the procedure being undertaken. (COSHH Regs) Control of exposure of staff to waste anaesthetic agents when used. (COSHH Regs)

As above

Emergency department resuscitation room

Comfort conditions only

Establish a clean airflow path – Supply terminal at high level and extract terminal at low level near patient’s chair/ couch. Design parameters Air change: 10 per hour Pressure regime: Neutral to corridor Noise level: 40 d(B)A Temp range: 20 to 25ºC must maintain any selected set point in the range via BMS Humidity: Floating; max 70%RH Air quality: BS EN 16798 - SUP2

General treatment room

All of the above rooms are suitable for aerosol-generating procedures (AGPs)

[SHTM 03-01 Part A – PDF page 79]

Applications: Level 2 and 3 critical care areas, bone marrow transplant (BMT), oncology, organ and tissue transplant units

Table 3: Airborne protective facilities

Area/zone Reason for ventilation Typical design factors Note: Level 2 & 3 Critical care areas should be treated identically in terms of service provision as their only difference is the staff- to-patient ratio. Level 2 or 3 critical care individual room

Protection of patients from airborne organisms and fungal spores

As above

Level 2 or 3 critical care open bays

Supply only in patient’s room and cascade air out via door undercut, transfer grille or pressure stabiliser through rooms of a lower classification. Design parameters Air change: ≥10 per hour Pressure regime: +10 Pa to general area Noise level: 35 d(B)A Temp range: 20 to 25ºC must maintain any selected set point in the range via BMS Humidity; Floating; max 60%RH Final filter; BS EN 1822 – EPA10

Bone Marrow Transplant (BMT) unit

Protection of patients from airborne organisms and fungal spores Note: Patient(s) will have a very poor immune system (neutropenia) so will be particularly vulnerable to infection by the airborne route.

As for BMT

Haematology/Oncolog y ward

As for BMT

Organ and Tissue Transplant unit

Supply only in room and cascade air out via door undercut, transfer grilles or pressure stabilisers through rooms of a lower classification. Design parameters Air change: ≥10 per hour Pressure regime: +15 Pa to corridor Noise level: 35 d(B)A Temp range: 20 to 25ºC must maintain any selected set point in the range via BMS Humidity: Floating; max 60%RH Final filter: BS EN 1822 – EPA12

Applications: Isolation rooms category 2 & 3, Infectious disease units, Containment level 3 rooms

Table 4: Airborne isolation facilities

Area/zone Reason for ventilation Typical design factors Category 2 isolation room

Category 3 isolation room

Protection of staff and all other building occupants from airborne organisms dispersed by a patient with an infectious disease. See Scottish Health Planning Note 4 Supplement 1

Extract only in patient’s room and en- suite. Supply air from corridor passing into room via door undercut, transfer grille or pressure stabiliser. Alternatively the patient’s room may have a supply and extract provided they are interlocked to ensure that the room is always at –ve pressure with regard to the corridor. Design parameters: Air change: ≥10 per hour Pressure regime: –5 Pa to general area Noise level: 35 d(B)A Temp range: 20 to 25ºC must maintain any selected set point in the range via BMS Humidity: Floating; max 60%RH Air quality: BS EN 16798 – SUP2

[SHTM 03-01 Part A – PDF page 80]

Area/zone Reason for ventilation Typical design factors Positive pressure ventilated lobby (PPVL) isolation room Universal isolation facility

Protection of building occupants from patients who may be infected and protection of patients who may be immunocompromised and protection for patients with both conditions. See Scottish Health Planning Note 4 Supplement 1

Supply in lobby flowing through a pressure stabiliser to patient’s room and on via a door undercut or transfer grille to an extract in the en-suite. Design parameters: Bedroom air change: ≥10 per hour Lobby pressure: +10 Pa to corridor Bedroom pressure: Neutral En-suite pressure: –ve Comfort parameters as above Air quality: BS EN 16798 – SUP2 With facility to fit BS EN 1822 – EPA12 Containment level 3 laboratory

Protection of occupants in adjoining spaces from airborne bio-hazards

For design details see the Medical Research Council’s “Standards for containment level 3 facilities” Category 4 facility Design advice will be provided by the client

Application: Obstetrics theatre, delivery rooms, nursery, neonatal intensive care and special care baby units

Table 5: Maternity facilities

Area/zone Reason for ventilation Typical design factors Obstetrics theatre Protection of patients from airborne organisms and fungal spores. Control of exposure of staff to waste anaesthetic agents (COSHH Regs)

Ventilation design parameters as for a conventional operating suite. System should normally be at "set back” with a minimum temperature of 18ºC and be able to attain full operating conditions within 5 minutes of triggering the system Delivery room Control of exposure of staff to waste anaesthetic agents. (COSHH Regs)

Delivery room with birthing pool

As for standard delivery room above Specials delivery room As for standard delivery room above

Establish a clean airflow path – Supply terminal at high level at foot end of bed and extract terminal at low level at head end of bed. Design parameters: Air change: 15 per hour Pressure regime: Neutral to corridor Noise level: 35 d(B)A Temp range: 20 to 25ºC must maintain any selected set point in the range via local control Humidity: Floating – max 70%RH Air quality: BS EN 16798 – SUP2

Nursery Comfort conditions only Neonatal intensive care unit or special baby care unit (SCBU)

Protection of neonates from airborne organisms and fungal spores. Neonates are kept in incubators but may be removed for feeding, changing etc. so local temperature control and ensuring a draught-free environment is essential.

Standard supply and extract Design parameters: Air change: 10 per hour Pressure regime: +5 Pa to corridor Noise level: 45 d(B)A Temp range: 20 to 28ºC must maintain any selected set point in the range via local control Humidity: Floating – max 70%RH Air quality: BS EN 16798 – SUP1 (Filter grade depends on ODA category – see the Specialised Ventilation for Healthcare Society’s (2018) SVHSoc.02) N.B. This is a critical healthcare facility and consideration should be given to system resilience and/or how suitable alternative accommodation may be provided in the event of a ventilation system failure.

[SHTM 03-01 Part A – PDF page 81]

Applications: pharmacy aseptic suite, gene therapy, radiopharmacy, support rooms

Table 6: Pharmacy facilities

Area/zone Reason for ventilation Typical design factors Aseptic suite Cleanroom

Protection of product during and after processing. Protection of the wider environment from cytotoxic agents and antibiotics. EUGGMP standards (European Commission, 2011) apply and the Medicine Act if the facility is licensed. Control of exposure by the airborne route to staff of substances during and after processing products. (COSHH Regs). Note: While this application is a critical facility, it is usual to have a plan in place to decant to another site in the event of a ventilation system failure

Supply only in cleanroom and cascade air out via pressure stabilisers through rooms of a lower classification or where there are multiple cleanrooms, a balanced supply and stable cascade out. Thimble extract may be provided for class 3 safety cabinets depending on the location of room within the building. Note: Advice from the client’s lead pharmacist should be sought prior to engaging in detailed design. Design parameters: Air change: ≥20 per hour Pressure regime: +15 Pa between unclassified rooms and +10 Pa between classified rooms Noise level: 45 d(B)A Temp range: 20–24ºC must maintain any selected set point in the range via BMS Humidity: Floating – max 60%RH Final filter: BS EN 1822 – HEPA14 Gene therapy cleanroom

As above, plus protection of the wider environment from product

As per cleanroom above

As per cleanroom above plus negative- pressure access lobby and controlled exhaust Radiopharmacy cleanroom

As for standard cleanroom with additional requirements of the Ionising Radiation (Medical Exposure) Regulations

Comfort conditions only

Non-sterile stores and support rooms

Application: decontamination facilities

Table 7: Decontamination unit

Facility Applicable Standards Central Decontamination Unit These are highly regulated production facilities dictated by:- Planning note - Scottish Health Planning Note 13 Part 1: 2010 Decontamination Facilities: Central Decontamination Unit. HFS, 2011 Mandated by compliance document - Requirements for Compliant Central Decontamination Units Version 2 – GUID 5014, HFS 2019 Equipment manufacturer’s design and installation instructions Local Decontamination Unit These are highly regulated production facilities dictated by:- Planning note - Scottish Health Planning Note 13 Part 2 Decontamination Facilities: Local Decontamination Units, HFS 2008 Mandated by two compliance documents - Compliant Dental Local Decontamination Units in Scotland Version 2 – GUID 5005, HFS 2019 and Provision of Compliant Podiatry Instruments – GUID 5007 Version 3.0, HFS 2020. Equipment manufacturer’s design and installation instructions