SHTM 03-01 Part A: 8. Specific Healthcare Department Requirements – Neutral pressure theatres for infectious patients / 8. Specific Healthcare Department Requirements – Interventional imaging suites

Ventilation for Healthcare - Design and validation (SHTM 03-01 Part A) · PDF pages 76–77 of 227 · Source file: shtm-03-01-part-a-v30-feb-2022.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHTM 03-01 Part A – PDF page 76]

ventilation ductwork and compromise the location of the supply air terminals. Liaison with the architects at an early stage in the project design is essential to ensure a satisfactory ventilation solution.

Hybrid theatres tend to be significantly larger than conventional theatres and may have a radiation protected control room and an equipment room to house the servers for the scanning equipment and its robotic arm in addition to the standard operating suite of rooms. The ventilation load will therefore be larger and standard solutions should be adapted to suit or the designer will need to return to first principles (see Appendix 8).

Because of the increased airflow requirement, the AHU will be larger than for a standard conventional operating suite.

In all other respects the ventilation design and theatre control panel will be as for a conventional operating suite as above.

Neutral pressure theatres for infectious patients

The client may have a requirement for an operating suite for surgery on infectious patients. This may be a dedicated neutral-pressure operating suite or a standard operating suite that is designed to be easily convertible to a neutral-pressure suite. If airborne microorganisms liberated from a patient during a surgical procedure are allowed to cascade out into the adjacent corridors, they could infect other patients or the staff in the operating department.

The room provision and layout will be as for a conventional operating suite with the following variation to the ventilation scheme:

the operating theatre will have a balanced supply and extract so that it is at the same pressure as the corridor;

air should not cascade from the theatre to the surrounding rooms, so pressure stabilisers and/or transfer grilles should not be fitted. In the case of a convertible operating suite, permanently fitted hinge-down blanking plates with clamps should;

be provided to close the pressure stabiliser/transfer grille openings when required;

the preparation room may be dispensed with to avoid having stock that could become pre-contaminated. Sterile packs, instruments and consumables would be delivered to the theatre on a case by case basis. If a preparation room is required, it should be maintained at 10 Pa to both the theatre and corridor;

the anaesthetic room should have a supply in excess of extract so that is maintained at 10 Pa above both the corridor and the theatre. There should be a pressure stabiliser between the anaesthetic room and the corridor but no transfer device between the anaesthetic room and the theatre;

the scrub should have an active extract as for a conventional operating suite but no pressure stabiliser between it and the corridor;

the utility should be at negative pressure of not less than –5 Pa to the theatre and its corridor;

[SHTM 03-01 Part A – PDF page 77]

the corridor extract will be sized to cater for the air leakage from the preparation and anaesthetic rooms.

Overall, the ventilation scheme should ensure that all air supplied to the operating theatre is removed in the theatre. The theatre should be neutral (at the same pressure) to the corridor so that when the theatre exit door is open there is effectively no interchange of air between them. When the preparation or anaesthetic doors are opened, air flows from them into the theatre and not the other way.

The theatre control panel, automatic control strategy and air handling unit will be as for a conventional operating suite.

Interventional imaging suites

Interventional imaging refers to rooms in which surgical interventions are carried out guided by imaging equipment. The risk of infection by the airborne route is low as the surgical site is small, and sterile instruments tend to be unwrapped immediately before use. Anaesthetic gas or agents are used for pain relief or sedation Patients requiring full anaesthesia will normally be treated in a hybrid or conventional operating suite. The VSG should advise on the likely scope of use.

An interventional image suite may simply be a room containing the imaging equipment, an adjoining radiation protected control room or bay for staff and an equipment room for the imaging server. Support rooms for patient changing, sit recovery, toilets and a utility may also be needed.

Ventilation of the imaging room would be 10 ac/h with the room at a positive pressure to the corridor. Ceiling- mounted steelwork to support the imaging equipment may reduce the space available to install ventilation ductwork and compromise the supply terminal locations. This may mean that sidewall linear terminals are the only viable option. If fitted, their discharge velocity should not cause draughts and the direction vanes should be fixed or capable of being locked to prevent alteration during routine cleaning. Alternatively, a displacement ventilation scheme may be considered.

A full “theatre style” control panel is not required, but a green light to show the ventilation is operational and a red one to show it is not should be provided.

Radiation shielding and warning notices may be required to ductwork where it penetrates ceilings, walls or floors to plantrooms or adjacent spaces to which staff may need access.