[SHTM 03-01 Part A – PDF page 74]

A readout sufficiently large (25 mm) to be clearly visible from the operating table that shows the temperature of the air at the UCV canopy.

A readout sufficiently large (25 mm) to be clearly visible from the operating table that shows the relative humidity of the air at the UCV canopy.

A red indicator light that will illuminate when either the supply AHU or the UCV canopy fails, or either or both are switched off or the AHU is in “Set back” (legend: “Theatre not to be used in this condition”).

An amber indicator light that will illuminate when the UCV canopy is at low speed and the supply AHU is running at full speed (legend: “Conventional theatre mode”).

A green indicator light that will illuminate when both the supply AHU and UCV canopy are operating at full speed (legend: “UCV theatre mode”).

A blue indicator light that will illuminate when the UCV canopy airflow, as detected by a differential pressure sensor, falls below 80% of the design flow rate (legend: “UCV requires service”).

Note: In touch screen panels the red indicator should be a band across the screen with the statement “Theatre ventilation not operational. Do not use” The amber indicator may be moving arrows representing airflow with the legend “Conventional Theatre mode”. The green indicator may be moving arrows representing airflow with the legend “UCV Theatre mode”. The blue indicator may be a band across the UCV terminal mimic stating “UCV requires servicing”.

When a system is designed to have partial walls with full wall extensions, a volume control facility may be incorporated to allow the system to be run with reduced velocity when the demountable full walls are in place. It would be the responsibility of the user to ensure correct operation of the system. To assist the user, an explanatory notice should be included on the theatre control panel.

The UCV unit manufacturer’s control box should be located in an accessible position preferably in the operating department adjacent to the operating theatre that it serves. A service corridor, if provided, is an ideal location. The control box should be clearly labelled with the identity of the operating theatre that it serves.

Barn and semi-barn theatres

There is no aerobiological reason why two or more UCV systems should not be installed in a common area if adequate spacing is provided. These are known as barn theatres and require special design considerations and operational discipline. The relative positions of the UCV units, temperature control range and location of doors and openings to other areas will all significantly affect the airflow at the operating positions.

A barn theatre has two or more operating positions each ventilated by a UCV canopy all in one open operating theatre. There may be a common scrub trough, SPS preparation room and shared utility, all of which reduce the facility’s footprint. For reasons of privacy and dignity, there is usually a separate anaesthetic room for each operating position. The operating positions may be separated by glass screens to

[SHTM 03-01 Part A – PDF page 75]

prevent bone fragments being propelled from one position to another when high- pressure air-driven surgical tools are being used.

A semi-barn theatre is very similar but would have a full-height dividing wall between the operating positions. The wall will not extend across the full width of the room, only its middle section. This creates a degree of physical separation between the operating positions but allows staff to walk from one to another around the ends of the dividing wall.

It is important that the physical layout and ventilation strategy of the barn or semi- barn are in harmony if the installation is to work successfully. The following points should be resolved with the architect and VSG when considering the design:

in order to reduce the risk of pre- contamination, surgical instruments should not have to pass one operating position in order to get to the one that they are destined for;

staff having scrubbed should not have to pass one operating position in order to get to the one that they are destined for;

waste material being cleared from an operating position should not pass another when being removed from the operating theatre;

the operating positions and their UCV canopies should be placed in line and not staggered or offset, otherwise their airflow patterns will interfere with each other;

while barns and semi-barns have, from the staffing and space utilisation point of view, many advantages, they can create problems with temperature control and energy efficiency. It is not advisable to shut their ventilation off at night or weekends as if the operating theatre temperature drops it can take a considerable time for the ventilation to achieve the required air velocity at the operating position (paragraph 8.96). Because the barn is a large open space, when it becomes cold the warm air supplied by the UCV canopies tends to rise and stratification occurs. As a result, although from the user’s point of view the ventilation appears to be running, the air being delivered does not actually have enough velocity to reach the operating table;

access for service, maintenance and future upgrades or refurbishment will be restricted as this can only be carried out when none of the operating positions is in use.

Ventilation of each UCV canopy and associated anaesthetic room will be by a dedicated AHU; ventilation of the shared spaces and perhaps recovery area would either be shared between the operating position AHUs or provided by a separate AHU.

Hybrid theatres

A designation given to operating theatres that contain scanning equipment on a robotic arm. Major surgical procedures are carried out and the patient is scanned as necessary during the procedure. The scanning equipment may be floor-mounted or ceiling-hung and there will be one or more large monitors, a variety of screens and the medical gas terminal units all ceiling-hung on articulated pendants. The number of pendants and their supporting steelwork can reduce the space available to install