Home › Scotland (NHS Scotland Assure / HFS) › SHTM 03-01 Part A › 3. Legal Requirements – Applicable Legislation

SHTM 03-01 Part A: 3. Legal Requirements – Applicable Legislation

Ventilation for Healthcare - Design and validation (SHTM 03-01 Part A) · PDF pages 20–23 of 227 · Source file: shtm-03-01-part-a-v30-feb-2022.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHTM 03-01 Part A – PDF page 20]

3. Legal Requirements – Applicable Legislation

Health and Safety at Work etc. Act

The Health and Safety at Work etc. Act 1974 is the core legislation that applies to ventilation installations. As these installations are intended to prevent contamination, closely control the environment, dilute contaminants or contain hazards, their very presence indicates that potential risks to health have been identified.

The Act places a duty of care on ALL to provide and maintain a safe workplace. This includes designers and suppliers of goods or services. Those trading as competent designers or suppliers are therefore liable to provide outcomes that meet the client’s needs and are without hazard to staff, patients and others who may be affected by the work activity.

Control of Substances Hazardous to Health Regulations

The Control of Substances Hazardous to Health (COSHH) Regulations 2002 place upon management an obligation to ensure that control measures are in place to protect their staff and others affected by the work activity. These methods may include both safe systems of work and the provision of a specialised ventilation system. In laboratories the requirements are often met by the provision of fume cupboards and microbiological safety cabinets.

Where specialised ventilation plant is provided as part of the control measures, there is a statutory requirement that it be correctly designed, installed, commissioned, operated and maintained. The local exhaust ventilation (LEV) section of COSHH requires that the system be examined and tested at least every 14 months by a competent person (P601 certified) and that management maintain comprehensive records of its performance, repair and maintenance.

Certain substances have workplace exposure limits (WELs) as set out in the Health and Safety Executive’s (2005) Guidance Note EH40 – ‘Workplace exposure limits’. This contains the list of workplace exposure limits for use with the Control of Substances Hazardous to Health Regulations 2002 (as amended). If specialised ventilation systems are provided in order to achieve these standards, they will be subject to the COSHH Regulations.

Workplace (Health, Safety and Welfare) Regulations

These state that:

all enclosed workplaces must be ventilated by natural or artificial means;

any plant provided under this legislation must include an effective device to give an audible or visual warning of plant failure where necessary for health and safety;

the Regulations require that ventilation systems are maintained in an efficient state, in efficient working order and in good repair.

[SHTM 03-01 Part A – PDF page 21]

The Building Regulations

Approved documents L and F:

apply to domestic and non-domestic buildings;

clarify satisfactory methods of providing ventilation and give ventilation rates;

set minimum standards for:

- the protection of the supply position;

- precautions against Legionella;

- the purity of recirculated air;

- access for service and maintenance;

- documentation and proof of performance;

- energy performance.

Health and Social Care Act 2008 (Regulated Activities)

Regulations 2014

Regulation 12(2)(h) of the Act decrees that registered providers must assess the risk of, and prevent, detect and control the spread of, infections, including those that are healthcare associated.

Appropriate standards of cleanliness and hygiene should be maintained in premises used for the regulated activity. DH (2015) issued ‘The Health and Social Care Act 2008 Code of Practice on the prevention and control of infections and related guidance’ (the HCAI Code of Practice), which contains statutory guidance about compliance with regulation 12(2)(h).

Regulation 15 of the Act states that:

All premises and equipment used by the service provider must be:

clean;

secure;

suitable for the purpose for which they are being used;

properly used;

properly maintained; and

appropriately located for the purpose for which they are being used.

The registered person must, in relation to such premises and equipment, maintain standards of hygiene appropriate for the purposes for which they are being used.

[SHTM 03-01 Part A – PDF page 22]

Note: The “registered person” means, in respect of a regulated activity, the person who is the service provider or a registered manager in respect of that activity. A “service provider” means a person registered with the CQC under Chapter 2 of Part 1 of the Health and Social Care Act 2008 as a service provider in respect of that regulated activity.

The Medicines Act 1968 and Human Medicines Regulations 2012

Pharmacy aseptic preparation facilities should conform to the requirements of EudralLex – Volume 4 – Good Manufacturing Practice (GMP) guidelines or equivalent UK legislation, and the requirements of the UK Medicines Inspectorate (MHRA) if a licensed manufacturing unit.

There are specific requirements under the Medicines Act 1968 to maintain accurate records of plant performance, room conditions and maintenance events. Such records would need to be preserved for up to 25 years as part of a quality assurance audit trail.

Specialised ventilation plant installed in laboratories dealing with research, development or testing, whether involving drugs, animals or genetically modified microorganisms, may be subject to legislation regarding their operation in addition to that mentioned above.

Indoor air quality (IAQ)

There is increasing awareness that IAQ has an important impact on health and well- being. The World Health Organization and the Royal College of Paediatrics and Child Health (2020) have produced papers on the importance of IAQ, and the National Institute for Health and Care Excellence (NICE) (2020) has issued guidelines for domestic environments. Indoor and outdoor sources of contaminants are important contributors to IAQ, and designers of ventilation systems should consider both. The Department for Environment, Food and Rural Affairs (Defra) gives data for outdoor air quality by postcode for the UK. This enables designers to choose suitable filter grades by location and application (see the Specialised Ventilation for Healthcare Society’s (2018) SVHSoc.02 – ‘Change in air filter test and classification standards’ for further information).

Other relevant standards and sources of guidance

The Chartered Institution of Building Services Engineers (CIBSE) Guides and associated published documents (TMs) are the principal source of general ventilation specification and design guidance.

ISO 14644 and ISO 17141 provide basic information on cleanrooms used in pharmacy preparation facilities and inspection, assembly and packing (IAP) rooms for the processing of medical devices in central decontamination units.

BS EN 15780 applies to both new and existing ventilation and air-conditioning systems and specifies the assessment criteria of cleanliness and cleaning procedures of these systems.

[SHTM 03-01 Part A – PDF page 23]

HSG 258 issued by the Health & Safety Executive provides guidance on the design of local exhaust ventilation (LEV) systems.

Other relevant guidance is listed in the References.

The Board and their supply chain must ensure that the competence of all parties is considered at the point of their introduction and on an ongoing basis. The philosophies that are included in the HSE leaflet INDG368 (current revision), "Using Contractors" should be adopted. In addition, the outputs from the "Setting the Bar" report should be adopted as they are introduced through legislation. Evidence that the recommendations of "Setting the Bar" are being implemented in advance of the legislation would be considered to be good practice, particularly for high risk buildings. BSI Flex 8670 “Built environment. Core criteria for building safety in competence frameworks. Code of practice” should also form part of the project planning.

Note: In all cases the most recent version of any legislation, regulation, standard or guidance document should be consulted.