2. The User Requirements

Patient treatment falls into four basic categories:

surgical procedures – physical interventions to diagnose, repair, remove or rebuild damaged or infected tissue;

medical care – the administering of drugs or various forms of practical, non- invasive treatment to diagnose, cure or reduce the severity of an infection or condition;

mental health – the use of counselling, often in conjunction with drugs, to control or alleviate abnormal behavioural or false perception issues in patients;

palliative care – treatment to temporarily or partially relieve or mitigate long-term conditions;

In all cases a patient may require treatment in one or more of the categories as either an in-patient or an out-patient.

Surgical procedures

It is thought that up to 25% of infections that occur as a result of a surgical intervention are caused by the airborne route. The source of these infections are predominantly as a result of airborne microorganisms, typically skin scales, liberated during the surgical procedure becoming airborne and landing in the wound or on surgical instruments. These then become a means of inoculating the patient with the contaminant. There are five possible routes that may result in airborne infections:

skin scales liberated by the surgical team during the procedure;

organic material liberated from the patient as a result of the procedure;

microorganisms remaining from a previous use of the space becoming airborne;

airborne microorganisms liberated outside of the space entering during the procedure;

microorganisms in the supply air from a ventilation system that has been contaminated with biological material.

The level of airborne organic material present or biological burden (bioburden) is typically defined in terms of the number of colony forming units (cfus) present at the wound site during the procedure. It will be dependent on:

the number of persons present;

the completeness and effectiveness of their gowning;

the duration of the procedure;

the type of procedure;

the use of air-driven power tools;

the extent to which a patient contributes to the bioburden in the space;

[SHTM 03-01 Part A – PDF page 17]

the general cleanliness of the space;

the discipline of the surgical team;

the measures that have been taken to prevent or control contaminants from outside sources entering the space;

the quality and volume of the incoming supply air;

the efficiency of the incoming air to “scour” the space;

the means of removing contaminated air from the space.

Good surgical discipline, effective patient preparation, the cleanliness of the space and control of the entry and exit of personnel during the procedure will all contribute to reducing the bioburden present.

A well-designed ventilation scheme that provides a suitable quality of air and efficiently scours the space will further reduce the bioburden. If the ventilation maintains the space at a positive pressure to adjoining areas, the risk of contaminants originating outside of the space entering will be reduced.

In addition to controlling the bioburden, the ventilation should provide comfortable conditions for the staff and patient.

The ventilation system should also control the risks to staff from anaesthetic agents and other hazardous fumes and emissions typically found in surgical facilities (see paragraphs 1.10–1.12).

Minor procedures may be carried out in a treatment room or at the bedside so surgical procedures are not exclusive to the operating department. (See Humphreys et al (2012) for further guidance on facilities for minor surgical procedures and minimal access interventions).

Medical care

In general the main requirement will be to ensure that staff and patients are kept in comfortable conditions.

There are specific instances where staff can be at risk of contracting an illness by the airborne route from a patient. This is the case in infectious disease units where the ventilation will be designed to maintain the unit and individual patient rooms at negative pressure relative to adjacent areas. This will protect persons outside of the unit from infection by the airborne route but not staff entering and working in the unit, who may need to take additional precautions to protect themselves.

The opposite problem occurs when patients are neutropenic, that is, they have a reduced or extremely low resistance to infection. They are then at risk of infection by the airborne route from other persons such as staff and visitors. This will be the case in cancer/oncology units, critical care areas, and bone marrow and general transplant units. The ventilation in these areas will need a higher air quality and be set to maintain a positive pressure to adjacent areas.

[SHTM 03-01 Part A – PDF page 18]

Mental health

Any specific patient needs should be assessed and addressed. The main requirement will be to ensure that staff and patients are kept in comfortable conditions (see comments on other types of healthcare facility in the Executive Summary).

The fire risk may be considered more likely and additional steps may need to be taken to control it.

Palliative care

The main requirement is to ensure that staff and patients are kept in comfortable conditions. Temperature control may be more stringent for patients with long-term and/or end of life conditions (see the Executive Summary for further information).

Difficulties with evacuating patients in the event of fire may need to be considered.

Diagnostic and support services

Imaging and Interventional imaging

There are major advances in diagnosis and minimally invasive treatment involving imaging. It may be necessary during these invasive or non-invasive procedures to provide sedation or general anaesthesia to help with anxiety or pain. This may involve the use of inhaled anaesthetic agents and/or nitrous oxide (N2O). Staff working in these areas may be exposed to these anaesthetic agents when they are administered or subsequently when they are exhaled as the patient is recovered.

A similar situation occurs in maternity units, where a mixture of nitrous oxide and oxygen (N2O/O2) (Entonox) is used as an inhaled analgesic.

In both of the above cases ventilation should be designed to provide a clean airflow path and dilute any casual spillages of the gas. This approach will help control the casual exposure of staff to the anaesthetic agent (see paragraphs 3.3–3.5).

Post-mortem and pathology

Staff who harvest organs and specimens at a post-mortem and place them into preservative solutions may be exposed to the microorganisms present and fumes from the preservative.

Staff who section organs and prepare specimens for analysis may be exposed to the microorganisms present and the chemicals used for staining and fixing the specimens.

In both of the above situations local exhaust ventilation (LEV) in the form of downflow benches, safety cabinets and fume cupboards need to be provided to control the risk.

Pharmacy

Exposure to the active ingredients of drugs represents a hazard to pharmacy staff who are involved in their production. These activities are carried out in an aseptic

[SHTM 03-01 Part A – PDF page 19]

preparation facility to ensure that the drugs themselves are not contaminated. The actual production typically takes place inside an isolator so that there is a physical barrier between the hazard and the operator.

Alcohol sprays are used and staff exposure may be controlled by the provision of downflow LEV systems to remove the hazard.

Comfortable conditions are essential for staff working in preparation facilities as they need to be fully gowned, and entry and exit is restrictive.

Decontamination facilities

Staff may be exposed to airborne biological material and chemicals when handling and processing used scopes, surgical instruments and equipment as part of the decontamination process. The ventilation should provide a clean airflow path to control staff exposure. The quality, quantity and flow pattern of the air are also critical to the protection of the decontaminated items.

Estates and facilities

Staff may be engaged in welding, soldering, machining wood or paint- spraying. They may also decant chemicals in quantity (for example, for boiler treatment or hydrotherapy-pool dosage). LEV systems are routinely used to control the hazards arising.