SHTM 03-01 Part A: 1. Introduction
[SHTM 03-01 Part A – PDF page 12]
1. Introduction
The needs of the building occupants
Ventilation is used extensively in all types of healthcare premises to provide a safe and comfortable environment for patients and staff and control odours. More specialised ventilation is provided to help reduce airborne infection risks in areas such as operating departments, critical care facilities, isolation rooms and primary patient treatment areas.
The Health and Social Care Act places a duty of care on healthcare providers. Increased health risks to patients will occur if ventilation systems do not achieve and maintain the required standards. The link between surgical site infection and theatre air quality has been well established. If the ventilation plant has been installed to dilute or contain harmful substances, its failure may expose people to unacceptable levels of risk. Proven breaches of the statutory requirements can result in prosecution and may also give rise to a civil suit against the operators.
The building environment
1.3. Healthcare buildings are visited and used by large numbers of people. Many will be unwell or anxious so a well-ventilated environment with a fresh feel and an absence of noxious odours is essential.
Ventilation may also be installed:
to ensure compliance with highly regulated quality assurance requirements of items processed in pharmacies and central decontamination units;
to protect staff from airborne microorganisms and toxic substances (for example, in laboratories and anaesthetic rooms);
to contain the spread of smoke between fire compartments as part of the fire strategy.
Healthcare buildings are continuously occupied, intensively used and because of the specialised nature of the facilities it may be extremely difficult to provide the service elsewhere if the ventilation fails. In order to ensure continuity of service, ventilation systems should be designed and installed so that they can be quickly and easily maintained. The resilience of the proposed system in the event of service outage should also be considered.
The ventilation of healthcare facilities consumes a significant portion of their energy load, so wherever possible natural ventilation is the preferred option. Where mechanical ventilation is used, sustainable design concepts allied to good-quality installation and the provision of controls that maintain the desired environment when the facility is in use will result in the minimum energy input for the maximum benefit.
[SHTM 03-01 Part A – PDF page 13]
Airborne risks to staff
Most healthcare staff are no more at risk from airborne hazards when at their workplace than they are when not in a healthcare environment; however, certain groups as detailed below may be exposed to a variety of airborne contaminants.
staff who administer anaesthetic agents or who work in areas where they are routinely used will be at risk of casual exposure to these agents;
staff who routinely work in areas where they may come into close contact with patients who have respiratory symptoms will be at risk of exposure to the microorganisms causing the symptoms;
staff who routinely work in areas where they may come into close contact with patients that have skin lesions, an infectious disease or a dermatological condition will be at risk of exposure to the microorganisms causing the condition;
staff who routinely process pathology specimens;
staff who decant, mix and/or process chemicals used as reagents for the setting or processing of pathology specimens;
staff who harvest organs, tissues and specimens at a post-mortem;
staff who handle drugs or the components of drugs;
staff who pre-clean used scopes, surgical instruments and equipment prior to decontamination;
staff who may be routinely exposed to airborne hazards listed in EH40 issued under the Control of Substances Hazardous to Health Regulations (COSHH) (for example, woodworking dust, welding fumes, chemical vapours).
A well-designed ventilation system can mitigate the airborne risks to staff. It should:
supply sufficient unvitiated air to dilute the possible contaminants;
have air terminals located to efficiently scour the ventilated space;
move the air from the clean to the less clean space and/or out of the building;
supply the air at high level and remove it at low level so that the breathing zone of staff is in a clean airflow path.
Adoption of these principles will be sufficient to control the general risk to the staff identified above in their particular working environment. More specific airborne hazards should be captured at source and removed by local exhaust ventilation (LEV) systems provided under the COSHH Regulations (see paragraphs 3.3–3.5).
Airborne risks to patients
In general terms an environment that is satisfactory for staff will be satisfactory for patients. There are, however, exceptions as below:
intensive treatment units of any type;
haematology/oncology units;
[SHTM 03-01 Part A – PDF page 14]
transplant units and units treating patients that have had their immune system compromised;
bone marrow transplant units (BMT);
burns units;
cystic fibrosis units;
operating theatres.
Patients being treated in these areas will need an environment supplied with good- quality filtered air and that is maintained at a positive pressure with respect to surrounding areas
Note: Patients who are particularly at risk from airborne microorganisms will normally be placed in an isolation room or suite that is maintained at a positive pressure. Patients who have a condition that could be transmitted to others are normally placed in a negative pressure isolation suite. When the patient’s exact condition is unknown they may be placed in a neutral pressure (PPVL) isolation suite (see Health Building Note 04-01 Supplement 1 – ‘Isolation facilities for infectious patients in acute settings for detailed guidance).
A more general airborne risk will result from poorly designed and constructed air handling units (AHUs) that allow water to stagnate inside; they can then become a source of microorganisms such as Legionella. If their intake is badly sited or housekeeping in the area is poor, fungal spores such as aspergillus can be drawn in. The ventilation system will then become a means of spreading these microorganisms and fungal spores around the healthcare building.
All ventilation systems should conform to the principles set out in the Health and Safety Executive’s (HSE) Approved Code of Practice and guidance document HSG274 ‘Legionnaires’ disease: the control of Legionella bacteria in water systems’ and Scottish Health Technical Memorandum 04-01 – ‘Safe water in healthcare premises’.
Specialist equipment environment
Imaging and other non-invasive scanning equipment will require stable environmental conditions to stay within calibration and provide accurate repeatable results. Health Building Note 06-01 and Health Building Note 10 (2021) give detailed guidance and the equipment manufacturers should be consulted.
Note: Health Building Note 26 – ‘Facilities for surgical procedures’ (2004) and Health Building Note 10-02 – ‘Facilities for day surgery units’ (2007) are under revision at the time of writing and will become Health Building Note 10-01 once updated.
Health Building Note 06-01 (2001) on diagnostic imaging and interventional radiology is also under revision at the time of writing.
[SHTM 03-01 Part A – PDF page 15]
Medicinal products environment
Pharmacists are required to ensure that any manufacture or preparation activities involving medicinal products undertaken in their units conform with the requirements of the Medicine Act. Processes must be carried out in a suitable facility usually termed an aseptic preparation facility. The quality of air supply and design of the ventilation cascade are essential to ensure a suitable environment for the activities undertaken.
Fire and smoke control fundamentals
Scottish Health Technical Memorandums 81 to 87 (including sub-parts) are the base documents for fire aspects. When designing a ventilation system, a fire and smoke control strategy should be developed that is relevant to the site and its function. The fire and smoke strategy should take account of the planned activity within the area, the type of patient present, staff-to- patient ratio and treatment being delivered (see also Chapters 5 and 7).
When ventilation systems are originally designed, they will conform to an agreed fire strategy. This will determine the compartmentation, provision of fire-rated ductwork, fitting of sprinklers, the siting of fire and smoke dampers and an agreed control action for the ventilation in the event of a fire. The agreed fire and smoke control strategy must be clearly set out as part of the design specification.
The fire regulations require that, if ventilation ductwork penetrates the fabric of a building, it should be designed and installed to contain the spread of fire (see Health Technical Memorandum 05-02 – ‘Guidance in support of functional provisions for healthcare premises’ for further guidance).
If a ventilation system is upgraded or altered to suit a change of use, it will be necessary to reassess the fire strategy.
It is management’s responsibility to ensure that the fire strategy applied during the design and installation of a system is not reduced during the subsequent operation and maintenance of the equipment.
The number and location of fire and smoke dampers can be problematic. Fire- rated ductwork within fire zones will reduce the need for fire and smoke dampers. It will eliminate the need to provide access for routine damper testing and the infection control problems associate with reversed airflow paths resulting from damper failures and nuisance tripping (see also Chapter 7 for ventilation control in the event of fire).
Note: In developing a fire and smoke containment strategy the design of ventilation for infection control cannot be ignored. Over-compartmentation and poorly chosen fire lines can prevent air moving from clean to less clean areas and thus increase the infection risk. This can be a particular problem in operating departments where the desire to create a protected escape route can be at odds with the need to cascade air through a suite of rooms and out into a corridor in order to control the airborne infection risk.