HTM 03-01 A: _Hlk36670561 – General / _Hlk36670561 – Low-level extract installation

Specialised ventilation for healthcare premises Part A: The concept, design, specification, installation and acceptance testing of healthcare ventilation systems · PDF pages 201–202 of 213 · Source file: HTM0301-PartA-accessible-F6.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 03-01 A – PDF page 201]

Appendix 9: Design of air-movement control scheme for anaesthetic room

Appendix 9: Design of air- movement control scheme for anaesthetic room

General

Figure A8 Schematic of suitable supply and extract terminal zones

Wall cupboards and worktop along this wall

Zone for the location of

ceiling-mounted supply terminals

CL CL

Theatre or

imaging

Corridor doorway

room doorway

Patient on bed or trolley

Zone for low-level extract Anaesthetic gas terminals on this wall

The above shows the typical zones for the positioning of ceiling-mounted supply and low-level extracts in an anaesthetic room. The objective is to comply with the COSHH Regulations and HTM 03-01 Part A by providing a clean airflow path for staff working in anaesthetic rooms and so reduce their risk of casual exposure to waste/leaking anaesthetic agents. 1. Supply terminals should not be positioned above wall-mounted cupboards as this will prevent their output being measured directly with a balometer. It will also negatively impact on the air distribution within the room.

2. See photographs below for details of the recommended low-level extract installation.

3. Low-level extracts should have a spring-clip-retained pull-off grille face for ease of cleaning.

[HTM 03-01 A – PDF page 202]

Low-level extract installation

Traditional installation (not recommended)

• Low-level extract easily obstructed by equipment

• Extra corners to clean around

Recommended installation

• Low-level extract cut back at 80º and stops short of the floor.

• No added detail to floor covering or coving.

• No additional corners to clean around.

• Not easily obstructed by equipment.

• Pull-off grille face for ease of cleaning.

• Grille still accessible for airflow measurement.

The photograph is for illustrative purposes only and shows a cutback of approximately 65º. This was found to make airflow measurement quite difficult, hence the change to an 80º cutback so that measurement can be easily taken with a balometer.

Operating theatre to anaesthetic room air-transfer device

The air-transfer device between an operating theatre and anaesthetic room may be either by a transfer grille or pressure stabiliser. The choice will be determined by the volume of air to be transferred. Paragraphs A8.51 and A8.52 in Appendix 8 give details.