HTM 03-01 A: _Hlk36670561 – Relief of excess air from operating theatre when all doors are closed (pages 193–200)

Specialised ventilation for healthcare premises Part A: The concept, design, specification, installation and acceptance testing of healthcare ventilation systems · PDF pages 193–200 of 213 · Source file: HTM0301-PartA-accessible-F6.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 03-01 A – PDF page 193]

Appendix 8: Design of air-movement control schemes for operating theatres

Air movement control

Worksheet WS2d

Reference:

Peripheral room ................................. type, series multi-flow (balanced)

Nominal pressure: Pa

Note: In this type of room the supply and extract air flow rates are equal and take no part in the air movement control (AMC)

First, open door to higher pressure area.

Room pressure then becomes or or Pa (see Appendix 6)

Air flow, m3/s

Out In Remarks

Flow required through open doorway to give protection. See Appendix 6

At above pressures leaks through closed doors are: Pa ∆P

Total

Q1 ( ∑IN – ∑OUT ) (+ve inwards)

Next, open door to lower pressure area.

Room pressure then becomes or or Pa

Out In Remarks

Flow required through open doorway to give protection

At above pressures leaks through closed doors are: Pa ∆P

Total

Q2 ( ∑OUT – ∑IN ) (+ve outwards)

Flow through transfer device (TD1) to protect

door 1 = Q1 at resultant ∆P .................................

Flow through transfer device (TD2) to protect

door 2 = Q2 at resultant ∆P .................................

Designer ........................................................................................................... Date ......................................................

[HTM 03-01 A – PDF page 194]

Air movement control

Worksheet WS2e

Peripheral room ................................. type bay (semi-open)

Reference:

Nominal pressure: Pa

Note: If the room is of the open bay type (ie opening is larger than normal single doorway), the room should be considered part

of the main room. No air movement control considerations need then be made, and this sheet can be discarded. Supply and/or extract flow will be based on air distribution considerations.

Consider permanent opening

Air flow, m3/s

Out In Remarks

Flow required through opening to give protection

Leaks through closed doors to: Pa ∆P

Total

EAMC or flow outward through transfer device ( ∑IN – ∑OUT )

Transfer SAMC or EAMC to WS1

Transfer device – transfer grille – pressure stabiliser

Size select transfer device for flow rate @ ∆P

Note: A door from the bay is considered with the peripheral room to which it leads or, if it leads to the corridor, it is considered

with the main room

Designer ........................................................................................................... Date ......................................................

[HTM 03-01 A – PDF page 195]

Appendix 8: Design of air-movement control schemes for operating theatres

Air movement control

Worksheet WS3

Operating room

Reference:

Nominal pressure: Pa

Note: To avoid considering each door open in turn, the “key door” concept is introduced. This is the door which requires the

greatest mechanical flow when open. See paragraph A8.33

Select “key door” (see above).

Consider this door open – room pressure now becomes Pa (see Appendix 6)

See Appendix 7 for room pressures

Air flow, m3/s

Out In Remarks

Flow required through doorway to give protection

Air flow “out” or “in” via doors, transfer devices etc Pa ∆P

Mechanical extract

Total

SAMC ( ∑OUT – ∑IN ) transfer SAMC to WS1

Consider all doors closed.

Return SF from WS1 Room pressure now Pa (nominal)

Air flow “out” or “in” via door leakage, transfer devices etc Pa ∆P Out In Remarks

Mechanical extract and supply

Total

Flow ( ∑IN – ∑OUT ) through transfer device @ ∆P to ...............................................

For final selection of transfer device see paragraphs A8.50–A8.54

Designer ........................................................................................................... Date ......................................................

[HTM 03-01 A – PDF page 196]

Air movement control

Worksheet WS4

Corridor

Reference:

Nominal pressure: Pa

Consider all doors closed

Air flow, m3/s

Out In Remarks

Flow required through doorway to give protection

Leaks through closed doors, transfer devices, permanent openings etc Pa ∆P

Total flow inwards (S1)

Add mechanical input (S2) if necessary to increase S1 to give 7 AC/hr

Total flow outwards and inwards

SAMC = ( ∑OUT – ∑IN + S2) Transfer to WS5

or EAMC = ( ∑IN – ∑OUT + S2) Transfer to WS5

Note: this sheet to be used for each individual operating theatre suite (or pair of suites if they share a preparation room)

Designer ........................................................................................................... Date ......................................................

[HTM 03-01 A – PDF page 197]

Appendix 8: Design of air-movement control schemes for operating theatres

Air movement control Worksheet WS5

Reference:

Summary of air supply and extract for an operating suite

Air flow to corridor All doors closed Anaesthetic (key door open)

m3/s m3/s

From preparation

From operating theatre

From scrub

From anaesthetic

Total (a)

Air flow to corridor

From utility

From other source

Total (b)

Other room supplies .................................................................................... Total (c)

Total air supply (a) + (b) + (c)

Consider corridor ventilation (see Appendix 3) and calculate air volume required, based on 7 AC/hr (see Note 1)

m3/s

Air flow required to ventilate corridor

Air flow required to ventilate service corridor (see Note 2)

If the air flow from the operating suite (a) and (b) is greater than the calculated required volume, no further supply air is necessary

m3/s

Additional air to ventilate corridor

Additional air to ventilate service corridor (see Note 2)

Air extract

The size of the extract plant should be of the order of 10% below the supply to assist in maintaining the department under positive pressure relative to the outside departments

m3/s

Extract plant = Supply less leakage

Less 10% of supply

Total extract (see Note 3)

Notes: 1. In the case of a multi-theatre operating department, the air balance for the corridor should be considered as a separate

exercise, taking into account the final dispersal of excess air. 2. Omit these if only one corridor in operating suite. 3. The extract volume includes 0.24 m3/s from the anaesthetic room for a balanced condition

Designer ........................................................................................................... Date ......................................................

[HTM 03-01 A – PDF page 198]

Room temperature – summer Worksheet WS6a

Reference:

Find summer supply temperature TSS = 20 – 0.828 H(O/R) = TSS ºC Q(O/R)

Note: the temperature of a space may be calculated from

t1Q1 + t2Q2 + ........... + tnQn + (0.828H) T = Q1 + Q2 + . . . Qn

Where t1 is temperature of source 1 (ºC)

Q1 is flow from source 1 when all doors are closed (m3/s) H is heat gain in space (kW)

Supply Flows inwards

Temperature

Room Heat gain

From From From From From

kWh

ºC T Q TSS

Q t Q t Q t Q t Q t

Check doors to sterile areas

Maximum ∆T

Door between Calculated room

∆T (ºC)

permitted Remarks

Designer ........................................................................................................... Date ......................................................

[HTM 03-01 A – PDF page 199]

Appendix 8: Design of air-movement control schemes for operating theatres

Room temperature – winter Worksheet WS6b

Reference:

Find winter supply temperature TSW = 20 – 0.828 H(O/R) = TSW ºC Q(O/R)

Note: the temperature of a space may be calculated from

t1Q1 + t2Q2 + ........... + tnQn + (0.828H) T = Q1 + Q2 + . . . Qn

Where t1 is temperature of source 1 (ºC)

Q1 is flow from source 1 when all doors are closed (m3/s) H is heat gain in space (kW)

Supply Flows inwards

Temperature

Room Heat gain

From From From From From

kWh

ºC T Q TSW

Q t Q t Q t Q t Q t

Check doors to sterile areas

Maximum ∆T

Door between Calculated room

∆T (ºC)

permitted Remarks

Designer ........................................................................................................... Date ......................................................

[HTM 03-01 A – PDF page 200]

Transfer grilles, pressure relief dampers and pressure stabilisers Worksheet WS7

Reference:

Transfer grilles – see paragraphs A8.34–A8.38

Flow rate

Free area

No Location

Pressure difference

m3/s

m2 Model Resultant

∆p Pa Remarks

Pa

Pressure relief dampers – see paragraph A8.39

Pressure

Flow rate

Free area

No Location

Pressure difference

setting

Remarks

m3/s

m2

Pa

Pa

Pressure stabilisers – see paragraphs A8.40–A8.43

Note: where a stabiliser is acting both as series room door protection and operating pressure control, “pressure difference” and

“flow rate” are from WS2d; “pressure setting” is from WS3

Pressure

Flow rate

Free area

No Location

Pressure difference

setting

Remarks

m3/s

m2

Pa

Pa

Designer ........................................................................................................... Date ......................................................