Home › England (NHS England estates) › HTM 03-01 A › _Hlk36670561 – Relief of excess air from operating theatre when all doors are closed (pages 185–192)

HTM 03-01 A: _Hlk36670561 – Relief of excess air from operating theatre when all doors are closed (pages 185–192)

Specialised ventilation for healthcare premises Part A: The concept, design, specification, installation and acceptance testing of healthcare ventilation systems · PDF pages 185–192 of 213 · Source file: HTM0301-PartA-accessible-F6.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 03-01 A – PDF page 185]

Appendix 8: Design of air-movement control schemes for operating theatres

(ii) take steps to reduce the heat

gains;

By transfer devices via the anaesthetic room

(iii) if the door is to a corridor, the

flow through the open door will be larger than the value given in Appendix 6. Calculate on WS3, assuming it is the “key door” with door-flow unknown, and the supply as known;

(iv) if the door leads to a room with

mechanical supply, install a trimmer heater in the supply to the room controlled by either a differential thermostat or a thermostat slaved to the operating theatre thermostat to ensure that T is minimised;

A8.50 The transfer device (pressure stabiliser or transfer grille) between the theatre and anaesthetic room needs to accommodate an air volume of 0.46 m³/s at 20 Pa (see Appendix 6) when the door between the anaesthetic room and corridor is open. An additional 0.11 m³/s will pass through the door gaps of the theatre to anaesthetic door to give a total door flow protection figure of 0.57 m³/s through the open door between the anaesthetic room and corridor. The optimum duty for this device with all the doors closed would be 0.33 m³/s at the room differential of 10 Pa. The following equation shows how this figure is arrived at:

(v) if the door leads to a room with

Q = Q1

no mechanical supply, increase the door protection flow as follows:

(√

Qnew = Qold

[∆T + 1]

∆P2) ∆P1 = 0.46

∆20 ) ∆10

(√

= 0.33 m3/s

where:

A8.48 These options should be considered in this order, and (i), (ii) and (iii) should be investigated thoroughly before proceeding to (iv) or (v). The mechanical supply may need to be increased in order to achieve the desired air-change rates.

Q = excess air to be vented with

doors closed

Q1 = airflow required for door protec

tion through the transfer device

Relief of excess air from operating theatre when all doors are closed

ΔP1 = nominal differential pressure

with door to operating theatre closed and door to corridor closed

ΔP2 = nominal differential pressure

between the operating theatre and anaesthetic room when the corridor door is open.

A8.49 As the mechanical supply to the operating theatre is sized to provide an appropriate flow outwards through any door which is opened, it follows that when all doors are closed, there will be more air supplied to the operating theatre than can exit from it via leaks etc. This “excess” air can be relieved by either of the two methods described in paragraphs A8.50– 8.54.

A8.51 If the excess air is less than 0.33 m3/s, a pressure stabiliser is required to ensure that the correct pressure and protection airflow is available to pass through the door.

[HTM 03-01 A – PDF page 186]

A8.52 If the excess air is greater than 0.33 m3/s, a transfer grille is acceptable because at all times the airflow will exceed the flow required for pressure and door protection.

By pressure stabilisers to the corridor

should be adopted, as it provides the simplest solution and, once set up, will require no further maintenance. With less excess air, it is recommended that the air be passed through the anaesthetic room via the pressure stabilisers as at paragraph A8.51, thus keeping the number of pressure stabilisers to a minimum. Both these solutions increase the air-change rate in the anaesthetic room, but care should be taken to avoid passing excessive amounts through that would cause discomfort to the occupants.

A8.53 If it is undesirable to pass all the extra remaining air volume through the anaesthetic room after the door flow- protection volumes have been achieved, it may be passed from the theatre directly to the corridor via a separate pressure stabiliser.

A8.54 If there is sufficient excess air, the transfer grille solution at paragraph A8.52

Figure A5 Pressure stabilisers performing two tasks

Flow rate

A

B

Pressure difference P2 P1

[HTM 03-01 A – PDF page 187]

Appendix 8: Design of air-movement control schemes for operating theatres

Figure A6 An example of an air-flow network

Transitional

Corridor patients/staff

Pass through

Supply

hatch

Clean

Sterile

Preparation (sterile supply

Scrub

Anaesthetic

store)

Sterile bay (semi-open)

Sterile

Parallel/series

multi-flow Series multi-flow

(balanced)

Operating

room

Disposal hatch

Pass through

Dirty

Service corridor

[HTM 03-01 A – PDF page 188]

Figure A7 Air-flow design procedures

Step Description Worksheet

Show nominal room pressures and airflow directions on the plan of the theatre suite and WS1 WS1

Enter heat/loss/gain data and calculate supply air flow rates for temperature control only. Categorise room types, eg sterile, clean etc WS1

Enter air flows required for bacterial contamination control or air change rate, whichever is the greater; add supply and extract volumes (SD, ED) on the plan WS1

Define peripheral room types, see paragraphs A8.5–A8.11, and select appropriate worksheets

Select from WS2a to WS2e

Selected worksheets

from WS2a to WS2e

Locate air transfer devices, enter details on worksheets and locate on the plan and Figure A6

For each peripheral room, determine air flows through doors when open and calculate mechanical supply or extract and transfer device flows as above

Select “Key Door” and calculate air supply for operating theatre WS3

NO

Does this door produce solution with greatest flow?

YES

Transfer to WS1 and select final rate SF and EF WS1, WS3

Make provision for relief of excess air with doors closed Selected worksheets

and WS3

Calculate supply and extract flow rates for corridor(s) WS4, WS5

Calculate room temperatures (all doors closed) and ∆T’s WS6a and WS6b

YES

Do any ∆T’s across doors to sterile rooms exceed 1.0ºC?

Rectify as in paragraph A8.47

NO

Make summary of flows WS6a and WS6b

Size transfer devices, size ductwork, central plant etc WS7

Design ductwork layout, control plant etc –

[HTM 03-01 A – PDF page 189]

Appendix 8: Design of air-movement control schemes for operating theatres

Calculation sheet for flow rates Worksheet WS1

Reference:

Room name

1. Summer temperature control Heat gain

kW

2. Acceptable ∆t ºC

m3/s

3. Air flow rate (SG) = Gain ∆t × 1.2

4. Winter temperature control Heat loss kW

5. Acceptable ∆t ºC

m3/s

6. Air flow rate (SL) = Loss ∆t × 1.2

m3/s

7. Dilution of bacterial contaminants Air flow rate

SD or ED

AC/hr

m3/s

8. Desired air change rate AC/hr × room volume (m3)

9. Maximum of SG, SL, SD or ED or air change rate from step 8 m3/s

S m3/s

10. Air movement control Air flow rate for air movement control SAMC or EAMC (from WS2, WS3 or WS4)

E m3/s

11. Final supply flow rate (SF) m3/s

12. Final extract m3/s

13. Total supply m3/s

14. Total extract m3/s

Designer ............................................................................................ Date ...............................................

[HTM 03-01 A – PDF page 190]

Air movement control

Worksheet WS2a

Peripheral room ................................. type, single flow

Reference:

Nominal pressure: Pa

Consider door to .................................. open

Air flow, m3/s

Pa ∆t Out In Remarks

Flow required through doorway to give protection

Total

SAMC ( ∑OUT – ∑IN ) m3/s

or

EAMC ( ∑IN – ∑OUT ) m3/s

Transfer SAMC or EAMC to WS1

Consider door to ................................. closed

Pa ∆t Out In Remarks

Closed door leakage

Total

Return SF and EF to WS1

Flow through transfer grille outward (SF – EF – LOUT)

or

Flow through transfer grille inward (EF – SF – LIN)

Designer ........................................................................................................... Date ......................................................

[HTM 03-01 A – PDF page 191]

Appendix 8: Design of air-movement control schemes for operating theatres

Air movement control

Worksheet WS2b

Peripheral room ................................. type, parallel/series multi-flow

Reference:

Nominal pressure: Pa

Door from this room to .............................................................. (room of equal cleanliness) is not to be protected. A transfer grille is located in, or adjacent to, this door

Consider other door to ...................... open.

Room pressure now becomes or or Pa (see Appendix 6)

Air flow, m3/s

Out In Remarks

Flow required through doorway to give protection

At above pressures leaks through closed doors Pa ∆P

Mechanical supply or extract (SF/EF)

Total

X ( ∑OUT – ∑IN ) or Y ( ∑IN – ∑OUT )

Transfer grille required from high-pressure zone Flow = X

or at ∆Pa

to low-pressure zone Flow = Y

Size of transfer grille (free area) A1

Consider doors and hatch closed – room presssure becomes Pa (nominal)

Closed door leakage from Appendix 4 (assuming no transfer grille) Pa ∆P Out In Remarks

Mechanical supply or extract

Total

Air flow required through transfer grille = IN – OUT = Z´ or OUT – IN = Z˝

Transfer grille required flow Z´ or Z˝ @ ∆P

Size of transfer grille (free area) A2 =

Select larger of A1 or A2

Designer ........................................................................................................... Date ......................................................

[HTM 03-01 A – PDF page 192]

Air movement control

Worksheet WS2c

Reference:

Peripheral room ................................. type, parallel multi-flow high/low or series multi-flow (unbalanced)

Nominal pressure: Pa

Consider door from this room to ...................................... open.

Room pressure now becomes or or Pa (see Appendix 6)

Air flow, m3/s

Out In Remarks

Flow required through open doorway to give protection

At above pressures leaks through closed doors are: Pa ∆P

Total

S1 ( ∑OUT – ∑IN ) or E1 ( ∑IN – ∑OUT )

Consider door from this room to ...................................... open.

Room pressure now becomes or or Pa

Out In Remarks

Flow required through open doorway to give protection

At above pressures leaks through closed doors are: Pa ∆P

Total

S2 ( ∑OUT – ∑IN ) or E2 ( ∑IN – ∑OUT )

Consider doors closed. Closed doors leakage from Appendix 4

Door to: Pa ∆P Out In Remarks

Total

Return SF and EF from WS1

Flow through transfer device outward (SF – LOUT) to ..................................................

or

Flow through transfer device inward (EF – LIN) from ..................................................

Transfer grille Pressure relief damper

Designer ........................................................................................................... Date ......................................................