HTM 03-01 A: _Hlk36670561 – Relief of excess air from operating theatre when all doors are closed (pages 185–192)
[HTM 03-01 A – PDF page 185]
Appendix 8: Design of air-movement control schemes for operating theatres
(ii) take steps to reduce the heat
gains;
By transfer devices via the anaesthetic room
(iii) if the door is to a corridor, the
flow through the open door will be larger than the value given in Appendix 6. Calculate on WS3, assuming it is the “key door” with door-flow unknown, and the supply as known;
(iv) if the door leads to a room with
mechanical supply, install a trimmer heater in the supply to the room controlled by either a differential thermostat or a thermostat slaved to the operating theatre thermostat to ensure that T is minimised;
A8.50 The transfer device (pressure stabiliser or transfer grille) between the theatre and anaesthetic room needs to accommodate an air volume of 0.46 m³/s at 20 Pa (see Appendix 6) when the door between the anaesthetic room and corridor is open. An additional 0.11 m³/s will pass through the door gaps of the theatre to anaesthetic door to give a total door flow protection figure of 0.57 m³/s through the open door between the anaesthetic room and corridor. The optimum duty for this device with all the doors closed would be 0.33 m³/s at the room differential of 10 Pa. The following equation shows how this figure is arrived at:
(v) if the door leads to a room with
Q = Q1
no mechanical supply, increase the door protection flow as follows:
(√
Qnew = Qold
[∆T + 1]
∆P2) ∆P1 = 0.46
∆20 ) ∆10
(√
= 0.33 m3/s
where:
A8.48 These options should be considered in this order, and (i), (ii) and (iii) should be investigated thoroughly before proceeding to (iv) or (v). The mechanical supply may need to be increased in order to achieve the desired air-change rates.
Q = excess air to be vented with
doors closed
Q1 = airflow required for door protec
tion through the transfer device
Relief of excess air from operating theatre when all doors are closed
ΔP1 = nominal differential pressure
with door to operating theatre closed and door to corridor closed
ΔP2 = nominal differential pressure
between the operating theatre and anaesthetic room when the corridor door is open.
A8.49 As the mechanical supply to the operating theatre is sized to provide an appropriate flow outwards through any door which is opened, it follows that when all doors are closed, there will be more air supplied to the operating theatre than can exit from it via leaks etc. This “excess” air can be relieved by either of the two methods described in paragraphs A8.50– 8.54.
A8.51 If the excess air is less than 0.33 m3/s, a pressure stabiliser is required to ensure that the correct pressure and protection airflow is available to pass through the door.
[HTM 03-01 A – PDF page 186]
A8.52 If the excess air is greater than 0.33 m3/s, a transfer grille is acceptable because at all times the airflow will exceed the flow required for pressure and door protection.
By pressure stabilisers to the corridor
should be adopted, as it provides the simplest solution and, once set up, will require no further maintenance. With less excess air, it is recommended that the air be passed through the anaesthetic room via the pressure stabilisers as at paragraph A8.51, thus keeping the number of pressure stabilisers to a minimum. Both these solutions increase the air-change rate in the anaesthetic room, but care should be taken to avoid passing excessive amounts through that would cause discomfort to the occupants.
A8.53 If it is undesirable to pass all the extra remaining air volume through the anaesthetic room after the door flow- protection volumes have been achieved, it may be passed from the theatre directly to the corridor via a separate pressure stabiliser.
A8.54 If there is sufficient excess air, the transfer grille solution at paragraph A8.52
Figure A5 Pressure stabilisers performing two tasks
Flow rate
A
B
Pressure difference P2 P1
[HTM 03-01 A – PDF page 187]
Appendix 8: Design of air-movement control schemes for operating theatres
Figure A6 An example of an air-flow network
Transitional
Corridor patients/staff
Pass through
Supply
hatch
Clean
Sterile
Preparation (sterile supply
Scrub
Anaesthetic
store)
Sterile bay (semi-open)
Sterile
Parallel/series
multi-flow Series multi-flow
(balanced)
Operating
room
Disposal hatch
Pass through
Dirty
Service corridor
[HTM 03-01 A – PDF page 188]
Figure A7 Air-flow design procedures
Step Description Worksheet
Show nominal room pressures and airflow directions on the plan of the theatre suite and WS1 WS1
Enter heat/loss/gain data and calculate supply air flow rates for temperature control only. Categorise room types, eg sterile, clean etc WS1
Enter air flows required for bacterial contamination control or air change rate, whichever is the greater; add supply and extract volumes (SD, ED) on the plan WS1
Define peripheral room types, see paragraphs A8.5–A8.11, and select appropriate worksheets
Select from WS2a to WS2e
Selected worksheets
from WS2a to WS2e
Locate air transfer devices, enter details on worksheets and locate on the plan and Figure A6
For each peripheral room, determine air flows through doors when open and calculate mechanical supply or extract and transfer device flows as above
Select “Key Door” and calculate air supply for operating theatre WS3
NO
Does this door produce solution with greatest flow?
YES
Transfer to WS1 and select final rate SF and EF WS1, WS3
Make provision for relief of excess air with doors closed Selected worksheets
and WS3
Calculate supply and extract flow rates for corridor(s) WS4, WS5
Calculate room temperatures (all doors closed) and ∆T’s WS6a and WS6b
YES
Do any ∆T’s across doors to sterile rooms exceed 1.0ºC?
Rectify as in paragraph A8.47
NO
Make summary of flows WS6a and WS6b
Size transfer devices, size ductwork, central plant etc WS7
Design ductwork layout, control plant etc –
[HTM 03-01 A – PDF page 189]
Appendix 8: Design of air-movement control schemes for operating theatres
Calculation sheet for flow rates Worksheet WS1
Reference:
Room name
1. Summer temperature control Heat gain
kW
2. Acceptable ∆t ºC
m3/s
3. Air flow rate (SG) = Gain ∆t × 1.2
4. Winter temperature control Heat loss kW
5. Acceptable ∆t ºC
m3/s
6. Air flow rate (SL) = Loss ∆t × 1.2
m3/s
7. Dilution of bacterial contaminants Air flow rate
SD or ED
AC/hr
m3/s
8. Desired air change rate AC/hr × room volume (m3)
9. Maximum of SG, SL, SD or ED or air change rate from step 8 m3/s
S m3/s
10. Air movement control Air flow rate for air movement control SAMC or EAMC (from WS2, WS3 or WS4)
E m3/s
11. Final supply flow rate (SF) m3/s
12. Final extract m3/s
13. Total supply m3/s
14. Total extract m3/s
Designer ............................................................................................ Date ...............................................
[HTM 03-01 A – PDF page 190]
Air movement control
Worksheet WS2a
Peripheral room ................................. type, single flow
Reference:
Nominal pressure: Pa
Consider door to .................................. open
Air flow, m3/s
Pa ∆t Out In Remarks
Flow required through doorway to give protection
Total
SAMC ( ∑OUT – ∑IN ) m3/s
or
EAMC ( ∑IN – ∑OUT ) m3/s
Transfer SAMC or EAMC to WS1
Consider door to ................................. closed
Pa ∆t Out In Remarks
Closed door leakage
Total
Return SF and EF to WS1
Flow through transfer grille outward (SF – EF – LOUT)
or
Flow through transfer grille inward (EF – SF – LIN)
Designer ........................................................................................................... Date ......................................................
[HTM 03-01 A – PDF page 191]
Appendix 8: Design of air-movement control schemes for operating theatres
Air movement control
Worksheet WS2b
Peripheral room ................................. type, parallel/series multi-flow
Reference:
Nominal pressure: Pa
Door from this room to .............................................................. (room of equal cleanliness) is not to be protected. A transfer grille is located in, or adjacent to, this door
Consider other door to ...................... open.
Room pressure now becomes or or Pa (see Appendix 6)
Air flow, m3/s
Out In Remarks
Flow required through doorway to give protection
At above pressures leaks through closed doors Pa ∆P
Mechanical supply or extract (SF/EF)
Total
X ( ∑OUT – ∑IN ) or Y ( ∑IN – ∑OUT )
Transfer grille required from high-pressure zone Flow = X
or at ∆Pa
to low-pressure zone Flow = Y
Size of transfer grille (free area) A1
Consider doors and hatch closed – room presssure becomes Pa (nominal)
Closed door leakage from Appendix 4 (assuming no transfer grille) Pa ∆P Out In Remarks
Mechanical supply or extract
Total
Air flow required through transfer grille = IN – OUT = Z´ or OUT – IN = Z˝
Transfer grille required flow Z´ or Z˝ @ ∆P
Size of transfer grille (free area) A2 =
Select larger of A1 or A2
Designer ........................................................................................................... Date ......................................................
[HTM 03-01 A – PDF page 192]
Air movement control
Worksheet WS2c
Reference:
Peripheral room ................................. type, parallel multi-flow high/low or series multi-flow (unbalanced)
Nominal pressure: Pa
Consider door from this room to ...................................... open.
Room pressure now becomes or or Pa (see Appendix 6)
Air flow, m3/s
Out In Remarks
Flow required through open doorway to give protection
At above pressures leaks through closed doors are: Pa ∆P
Total
S1 ( ∑OUT – ∑IN ) or E1 ( ∑IN – ∑OUT )
Consider door from this room to ...................................... open.
Room pressure now becomes or or Pa
Out In Remarks
Flow required through open doorway to give protection
At above pressures leaks through closed doors are: Pa ∆P
Total
S2 ( ∑OUT – ∑IN ) or E2 ( ∑IN – ∑OUT )
Consider doors closed. Closed doors leakage from Appendix 4
Door to: Pa ∆P Out In Remarks
Total
Return SF and EF from WS1
Flow through transfer device outward (SF – LOUT) to ..................................................
or
Flow through transfer device inward (EF – LIN) from ..................................................
Transfer grille Pressure relief damper
Designer ........................................................................................................... Date ......................................................