[HTM 03-01 A – PDF page 183]

Appendix 8: Design of air-movement control schemes for operating theatres

Door opening

Q2 and P2 are new flow and differential pressure.

A8.37 The transfer grille may be replaced by carefully proportioned door undercuts of the equivalent free area.

A8.32 Whereas the resulting pressures are dependent on ductwork layout, room relationships and characteristics of the fan, the generalisations shown in Appendix 6 may be used to estimate the change in room pressure when a door is opened.

A8.38 The function of the transfer grille is to provide a means of air-flow control by which the volume and pressure loss can be established. If a grille is used, it should have an easily removable core to facilitate cleaning.

A8.33 The “key door” will be the open double door which leaves the operating theatre at the highest pressure, and/or requires the largest air flow. This should be determined using the procedure in worksheet WS3.

Pressure-relief dampers

Transfer grilles

A8.39 The functions of a pressure-relief damper are now carried out by pressure stabilisers. Accordingly, all mention of them has been removed from this document.

Pressure stabilisers

A8.34 These may be used to limit the pressure differences across the closed door of a single-flow room or, in some instances, for protection of a series-flow or parallel- series-flow room. They allow air flow in both directions and may not be suitable for all applications.

A8.35 The free area of a grille is calculated from the following equation:

A8.40 Pressure stabilisers can be adjusted to hold the pressure constant over a wide range of flow rates. They are used where requirements exist for accurate room- pressure control or rapid shut-off on pressure fall.

A = Q 0.84√∆P

where:

A is free area (m2)

Q is flow rate (m3/s)

P is pressure difference (Pa)

A8.41 The installation of a grille or baffle in association with a stabiliser will alter the operating characteristics. It is recommended that a location be chosen to avoid the need for visual screening, for example, at high level. The location should be chosen to minimise the likelihood of damage.

0.84 is the grille's resistance- correction factor.

A8.36 The flow through a grille at a different pressure may be found from the following equation:

∆P1

Q2 = Q1√

∆P2 where:

Q1 and P1 are original flow and differential pressure

A8.42 The stabilisers used should be virtually silent in operation, adjustable on site, maintenance-free and of a type which cannot be wrongly inserted. They should not be used in external walls or where the pressure difference is less than 5 Pa. The required size of a pressure stabiliser is dependent on the design pressure difference across it and flow rate through it. The manufacturer should provide data relating pressure difference to mean velocity (or flow rate per unit area). From

[HTM 03-01 A – PDF page 184]

this, the required area can be calculated and then rounded-up to the nearest size manufactured or nearest combination of smaller sizes.

shown in Appendix 6 are based on the temperature differences that will normally occur in practice, assuming heat gains and losses in accordance with Appendix 4.

A8.46 At step 11 of the air-flow design process, the temperature differences across the doors of all rooms classed as “sterile” are calculated. Worksheet WS6 is recommended for the calculations, using the following criteria:

a. assume that the operating theatre

is being controlled at 20ºC and calculate the incoming air-supply temperature as shown on worksheet WS6;

A8.43 It is sometimes possible to arrange for a pressure stabiliser to perform two tasks. In an anaesthetic room, for example, the two pressure stabilisers may be made to pass the open door protection air, and also control the operating and anaesthetic room pressures with the door closed. To achieve this, the stabilisers are sized for the flow rate required with one of the doors open, but the pressure setting is adjusted to be the value required with the doors closed. This is shown in Figure A5.

b. the calculation should be repeated

Door leakage flows

for both summer and winter conditions, with an operation in progress;

c. assume all doors are closed;

d. use the room supply flow rates from

WS1;

e. use the inward air flows through

air-transfer devices and closed door leakages from WS2a to WS2E;

f. the formula used in worksheet WS6

is as follows:

T = (t1Q1 + t2Q2 + . . . + tnQn) + 0.828H (Q1 + Q2 + . . . Qn) where:

Q = flow rate from source (m3/s)

t = the temperature of source (ºC)

H = the room heat gain (kW).

A8.44 For an air-movement control scheme to work satisfactorily, it is essential that the estimates of door-gap leakage made at the design stage are closely related to those which are achieved in practice. The calculation of gap-flows is complicated by the fact that such flows generally fall into the transition region between laminar and turbulent flow and hence do not follow the normal flow equations. The gaps assumed are 4 mm along the bottom, 3 mm at the top and sides, and 2 mm between double leaves. Doors should not have wider gaps than these. Tighter gaps would result in lower flow-rate requirements and hence lower fan power, but care should be taken to ensure that all doors in the suite have similar gap dimensions. It may be possible to ignore the door leakage and so reduce the air-flow requirement (see the “designers’ notes” in Appendix 4).

Room temperature estimation

A8.47 If the evaluated temperature differences between rooms do not exceed 2ºC, the solution is satisfactory; otherwise proceed as follows:

(i) check the assumption on which

the heat gains are based;

A8.45 The air-flow rate required to prevent back-flow through an open door is dependent on the temperature difference across the door. The design figures