Home › England (NHS England estates) › HTM 03-01 A › _Hlk37000395 – Appendix 7: Operating suite design logic / _Hlk37000395 – 5.0 Ventilation strategies (pages 39–46) / _Hlk37000395 – 5.0 Ventilation strategies (pages 47–54) / _Hlk37000395 – 5.0 Ventilation strategies (pages 55–62) / _Hlk37000395 – 5.0 Ventilation strategies (pages 63–70) / _Hlk37000395 – 5.0 Ventilation strategies (pages 71–78) / _Hlk37000395 – 5.0 Ventilation strategies (pages 79–86) / _Hlk37000395 – 5.0 Ventilation strategies (pages 87–94) / _Hlk37000395 – 5.0 Ventilation strategies (pages 95–102) / _Hlk37000395 – 5.0 Ventilation strategies (pages 103–110) / _Hlk37000395 – 5.0 Ventilation strategies (pages 111–118) / _Hlk37000395 – 5.0 Ventilation strategies (pages 119–126) / _Hlk37000395 – 5.0 Ventilation strategies (pages 127–134) / _Hlk37000395 – 5.0 Ventilation strategies (pages 135–142) / _Hlk37000395 – 5.0 Ventilation strategies (pages 143–150) / _Hlk37000395 – 5.0 Ventilation strategies (pages 151–158) / _Hlk37000395 – 5.0 Ventilation strategies (pages 159–166) / _Hlk37000395 – 5.0 Ventilation strategies (pages 167–173)

HTM 03-01 A: _Hlk37000395 – Appendix 7: Operating suite design logic / _Hlk37000395 – 5.0 Ventilation strategies (pages 39–46) / _Hlk37000395 – 5.0 Ventilation strategies (pages 47–54) / _Hlk37000395 – 5.0 Ventilation strategies (pages 55–62) / _Hlk37000395 – 5.0 Ventilation strategies (pages 63–70) / _Hlk37000395 – 5.0 Ventilation strategies (pages 71–78) / _Hlk37000395 – 5.0 Ventilation strategies (pages 79–86) / _Hlk37000395 – 5.0 Ventilation strategies (pages 87–94) / _Hlk37000395 – 5.0 Ventilation strategies (pages 95–102) / _Hlk37000395 – 5.0 Ventilation strategies (pages 103–110) / _Hlk37000395 – 5.0 Ventilation strategies (pages 111–118) / _Hlk37000395 – 5.0 Ventilation strategies (pages 119–126) / _Hlk37000395 – 5.0 Ventilation strategies (pages 127–134) / _Hlk37000395 – 5.0 Ventilation strategies (pages 135–142) / _Hlk37000395 – 5.0 Ventilation strategies (pages 143–150) / _Hlk37000395 – 5.0 Ventilation strategies (pages 151–158) / _Hlk37000395 – 5.0 Ventilation strategies (pages 159–166) / _Hlk37000395 – 5.0 Ventilation strategies (pages 167–173)

Specialised ventilation for healthcare premises Part A: The concept, design, specification, installation and acceptance testing of healthcare ventilation systems · PDF pages 169–173 of 213 · Source file: HTM0301-PartA-accessible-F6.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 03-01 A – PDF page 169]

Appendix 7: Operating suite design logic

Appendix 7: Operating suite design logic

Is it a new build operating suite?

NO

YES

It is a refurbishment

Is it a conventional suite?

Is it a scheme based on a standard

layout from

YES

NO

a previous

HTM?

YES

NO

NO

Does it have a “lay-up” prep?

Use appropriate stand- ard layout information

1 to 8

YES

NO

Do the room sizes accord with

HBN 10-01?

YES

Use standard layout

information 1 or 3

Is it a UCV suite?

NO

YES

NO

Does it have an SPS prep?

YES

NO

Do the room sizes accord with

HBN 10-01?

YES

Use standard layout

information

2 or 4 Apply basic design principles and/or use

the design method in Appendix 8

[HTM 03-01 A – PDF page 170]

Standard layout 1 – Two-corridor conventional operating suite with “lay-up” prep

Room Size (m3)‡ Air-change rate (ac/h) Nominal pressure (Pa) Flow rate (m3/s)

Theatre

≥22 Primary = 0.73 From Prep = 0.28 Total = 1.010

Anaesthetic

Design 15

0.24

Commissioned ≥10

Lay-up prep ≥22 0.28**

Scrub * – –

Notes:

‡ Derived from Health Building Note 10-01 (2021). If room sizes differ from those given, recalculate the design air flows to achieve

the air change rate or door protection.

*This is a separate scrub and is not considered as being part of the theatre volume.

** Interchange is not permitted between the theatre and lay-up prep; therefore, as in Appendix 5, an airflow protection of 0.28 m3/s is required as a minimum (but see also the “designers’ notes” in Appendix 4).

N.B.If the lay-up prep also has a door or hatch to the corridor, its supply airflow volume would increase to 0.35 m3/s

The volume of air to be extracted from the theatre should be determined by subtracting the airflow required for door protection at the key door from the total air entering the space. The balance should be equally divided between the passive or active extract locations.

The extracts within the theatre and scrub may be either passive and fitted with pressure stabilisers or active and connected to the extract system. They should where possible be located at low level and positioned to promote the active ventilation and scouring of all areas of the space (see paragraph 8.92). Air transfer from theatre to anaesthetic room may be by pressure stabiliser or transfer grilles (see paragraphs A8.51 and A8.52 in Appendix 8). The anaesthetic room extract will be at low level (see Appendix 9).

Corridor

KEY TO SYMBOLS

0.24

Supply volume (m3/s)

Anaesthetic Scrub

0.24

Extract volume (m3/s)

Nominal room pressure (Pa)

Air change rate (ac/h)

0.73

Pressure stabiliser

Operating theatre

0.28

≥22

LLE

Low-level active extract or pressure stabiliser to assist air distribution in theatre

Prep (lay up)

Transfer grille

LLE

≥22

Service corridor

Fire door

[HTM 03-01 A – PDF page 171]

Appendix 7: Operating suite design logic

Standard layout 2 – two-corridor UCV operating suite with SPS prep

Room Size (m3)‡ Air-change rate (ac/h) Nominal pressure (Pa) Flow rate (m3/s)

Theatre ≥22 # 1.01

Anaesthetic

Design 15

0.24

Commissioned ≥10

Sterile pack store prep 0.10

Scrub * – –

Notes:

‡ Derived from Health Building Note 10-01 (2021). If room sizes differ from those given, recalculate the design air flows to

achieve the air change rate or door protection.

* This is a separate scrub and is not considered as being part of theatre volume.

# Primary fresh-air volume to UCV canopy only or ≥22 or door protection

The volume of air to be extracted from the theatre should be determined by subtracting the airflow required for door protection at the key door from the total air entering the space. The balance should be equally divided between the passive or active extract locations.

The extracts within the theatre and scrub may be either passive and fitted with pressure stabilisers or active and connected to the extract system. They should where possible be located at low level and positioned to promote the active ventilation and scouring of all areas of the space (see paragraph 8.92). Air transfer from theatre to anaesthetic room may be by pressure stabiliser or transfer grilles (see paragraphs A8.51 and A8.52 in Appendix 8). The anaesthetic room extract will be at low level (see Appendix 9).

Corridor

KEY TO SYMBOLS

0.24

Supply volume (m3/s)

Anaesthetic Scrub

0.24

Extract volume (m3/s)

Nominal room pressure (Pa)

Air change rate (ac/h)

1.01

Pressure stabiliser

UCV primary air flow rate (m/s)

0.10

LLE

Low-level active extract or pressure stabiliser to assist air distribution in theatre

Prep (SPS)

UCV operating theatre

Transfer grille

LLE

≥22

Service corridor

Fire door

[HTM 03-01 A – PDF page 172]

Standard layout 3 – single-corridor conventional operating suite with “lay-up” prep

Room Size (m3)‡ Air-change rate (ac/h) Nominal pressure (Pa) Flow rate (m3/s)

Theatre

≥22 Primary = 0.73 From Prep = 0.28 Total = 1.01

Anaesthetic

Design 15

0.24

Commissioned ≥10

Lay-up prep ≥22 0.35**

Scrub * – –

Utility – –5 0.40

Notes:

‡ Derived from Health Building Note 10-01 (2021). If room sizes differ from those given, recalculate the design air flows to

achieve the air change rate or door protection.

* This is a separate scrub and is not considered as being part of the theatre volume.

** Interchange is not permitted between the theatre and lay-up prep; therefore, as in Appendix 5, an airflow protection of 0.28 + 0.07 closed-door airflow is required as a minimum (but see also the “designers’ notes” in Appendix 4).

The volume of air to be extracted from the theatre should be determined by subtracting the airflow required for protection at the key door from the total air entering the space. The balance should be equally divided between the passive or active extract locations.

The extracts within the theatre and scrub may be either passive and fitted with pressure stabilisers or active and connected to the extract system. They should where possible be located at low level and positioned to promote the active ventilation and scouring of all areas of the space (see paragraph 8.92). Air transfer from theatre to anaesthetic room may be by pressure stabiliser or transfer grilles (see paragraphs A8.51 and A8.52 in Appendix 8). The anaesthetic room extract will be at low level (see Appendix 9).

LLE

Scrub

KEY TO SYMBOLS

0.73

Supply volume (m3/s)

Operating theatre

0.24

Extract volume (m3/s)

Anaesthetic

≥22

0.24

Nominal room pressure (Pa)

LLE

Air change rate (ac/h)

–5

0.40

0.35

Pressure stabiliser

>20

Utility

Prep (lay up)

LLE

≥22

Low-level active extract or pressure stabiliser to assist air distribution in theatre

Exit bay

Transfer grille

[HTM 03-01 A – PDF page 173]

Appendix 7: Operating suite design logic

Standard layout 4 – single-corridor UCV operating suite with SPS prep

Room Size (m3)‡ Air-change rate (ac/h) Nominal pressure (Pa) Flow rate (m3/s)

Theatre ≥22 #1.01

Anaesthetic

Design 15

0.24

Commissioned ≥10

Sterile pack store prep 0.10

Scrub * – –

Utility – –5 0.4

Notes:

‡ Derived from Health Building Note 10-01 (2021). If room sizes differ from those given, recalculate the design air flows to achieve the air change rate or door protection.

* This is a separate scrub and is not considered as being part of the theatre volume.

# Primary fresh-air volume for the UCV canopy or ≥22 ac/h or door protection

The volume of air to be extracted from the theatre should be determined by subtracting the airflow required for protection at the key door from the total air entering the theatre space. The balance should be equally divided between the passive or active extract locations.

The extracts within the theatre and scrub may be either passive and fitted with pressure stabilisers or active and connected to the extract system. They should where possible be located at low level and positioned to promote the active ventilation and scouring of all areas of the space (see paragraph 8.92). Air transfer from theatre to anaesthetic room may be by pressure stabiliser or transfer grilles (see paragraphs A8.51 and A8.52 in Appendix 8). The anaesthetic room extract will be at low level (see Appendix 9).

LLE

UCV operating theatre Scrub

KEY TO SYMBOLS

1.01

Supply volume (m3/s)

0.24

UCV primary air flow rate (m/s)

Extract volume (m3/s)

Anaesthetic

0.24

Nominal room pressure (Pa)

≥22

LLE

Air change rate (ac/h)

–5

0.40

Pressure stabiliser

>20

0.10

Utility

Prep (SPS)

LLE

Low-level active extract or pressure stabiliser to assist air distribution in theatre

Exit bay

Transfer grille