Home › England (NHS England estates) › HTM 03-01 A › _Hlk37000395 – Appendix 5: Recommended airflow rates in m3/s through a doorway between rooms of different cleanliness to control cross-contamination / _Hlk37000395 – Appendix 6: Typical approximate pressures in an operating suite when a given door is open

HTM 03-01 A: _Hlk37000395 – Appendix 5: Recommended airflow rates in m3/s through a doorway between rooms of different cleanliness to control cross-contamination / _Hlk37000395 – Appendix 6: Typical approximate pressures in an operating suite when a given door is open

Specialised ventilation for healthcare premises Part A: The concept, design, specification, installation and acceptance testing of healthcare ventilation systems · PDF pages 167–168 of 213 · Source file: HTM0301-PartA-accessible-F6.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 03-01 A – PDF page 167]

Appendix 5

Appendix 5: Recommended airflow rates in m3/s through a doorway between rooms of different cleanliness to control cross-contamination

Room class Dirty Transitional Clean Sterile

Sterile Hatch

0.3

0.24

0.18

Single door

0.47

0.39

0.28

0 or 0.28a

Double door

0.95

0.75

0.57

0 or 0.57a

Clean Single door

0.39

0.28

0 or 0.28a

Double door

0.75

0.57

0 or 0.57a

Transitional Single door

0.28

0 or 0.28a

Double door

0.57

0 or 0.57a

Dirty Single door

Open single door = 0.80 m x 2.01 m high

Double door

Open double door = 1.80 m x 2.01 m high

Designers’ notes:

The degree of protection required at an open doorway between rooms is dependent on the degree of difference in cleanliness between them.

Flow-rate required between rooms within the same class tends to zero as class reduces.

a. If two rooms are of equal cleanliness, no flow is required (in practice there will be an interchange in either direction) and the

design of the air movement will assume zero airflow. In certain cases, however, interchange is not permitted, and a protection airflow of 0.28 is assumed in the design – for example, in the case of a preparation room used as a “lay up”.

[HTM 03-01 A – PDF page 168]

Appendix 6: Typical approximate pressures in an operating suite when a given door is open

Typical approximate effect on other rooms

Door open between Typical approximate resultant

pressure in these rooms (Pa) Room Pressure (Pa)

Anaesthetic

Operating theatre and corridor

Preparation – lay-up

or

Utility

–6

Scrub bay and corridor

Preparation – sterile pack store

Preparation – lay-up

Utility

–9

Operating theatre and anaesthetic room (or other series room with double doors)

Preparation – sterile pack store

No change

Operating theatre and Utility room

or

Operating theatre and preparation room

Preparation – lay-up

Utility

–6

Anaesthetic room and corridor (or other series room with double doors)

Operating theatre

Preparation – sterile pack store

No change

Preparation room and corridor

or

Utility room and corridor

Utility room and outer corridor No change

Notes:

The room differential pressure protects against reverse flows when the door is closed.

The flow of air through a doorway protects against reverse airflow when the door is open.

Pressure stabilisers control flow and ensure a known airflow path between rooms when doors are closed and also reduce backflow between rooms when doors to other rooms are open.