[HTM 03-01 A – PDF page 165]

Appendix 3: Hierarchy of cleanliness

Appendix 3: Hierarchy of cleanliness

Airflow rate for bacterial contaminant

dilution

Class Room Nominal pressure (Pa)a Flow in or supply (m3/s) Flow out or extract

(m3/s)

Sterile Preparation room

(a) lay-up

See standard schemes in Appendix 7 for recommended design values

(b) sterile pack store

Operating theatre

Scrub bayb

Clean Sterile pack store

+ve

6 ac/h

–

Anaesthetic roomc

15c

The greater of 15 ac/h or 0.15

The greater of 15 ac/h or 0.15

Scrub room

–

0.10 mind

Transitional Recovery room

15 ac/he

15 ac/he

Clean corridor

(See note f)

7 ac/h

General access corridor

(See note f)

7 ac/h

Changing rooms

7 ac/h

7 ac/h

Dirty Service corridor

–

(See note g)

Utility room

–5 or 0

–

0.40 or 0.10

Notes: a. Nominal room pressures are given to facilitate setting up of pressure-relief dampers, the calculation process, and the sizing

of transfer devices. In practice, the resultant pressures are not immutable provided the desired airflow rates and movement directions are achieved.

b. An open or semi-open bay is considered to be part of the operating theatre; a low-level extract under the scrub trough is

required. (See Chapter 8 paragraph 8.45 onwards and “Note” for more information.)

c. For design purposes, anaesthetic should be assumed to be at 15 Pa. When commissioning, equal to or greater than 10 Pa is

considered suitable.

d. May need to be increased if scrub is large to promote scouring.

e. 15 ac/h is considered necessary for the control of anaesthetic gas (see Appendix 9).

f. Supply airflow rate necessary to make up 7 ac/h after taking into account secondary air from cleaner areas.

g. No dilution requirement. Temperature control requirements only.

[HTM 03-01 A – PDF page 166]

Appendix 4: Leakage flows in m3/s through closed door gaps

Type Pressure difference (Pa)

Single door 0.03 0.05 0.06 0.06 0.07 0.08 0.09 0.10

0.04 0.06 0.07 0.08 0.09 0.10 0.11 0.12

Single door + half

0.05 0.08 0.10 0.11 0.12 0.13 0.14 0.15

Double door

Designers’ notes:

The door gaps assumed are 4 mm along the bottom, 3 mm at the top and sides, and 2 mm between double leaves.

If doors are fitted with cold smoke seals, these will significantly reduce the door leakage rate when new and undamaged. It is therefore recommended that provision for the design leakage be factored into the size of the appropriate transfer grille or pressure stabiliser. Failure to do this will result in air-gap whistles and doors being held partially open by air pressure.

Factory-assembled door-sets with a steel frame and pre-hung leaves are becoming common. There is effectively no leakage across these doors when closed. Therefore, when this type of door assembly is fitted, the door leakage can be ignored and the design airflow into the room reduced accordingly. The design airflow would then become that required either (i) for open door protection (Appendix 5), or (ii) to achieve the specified air-change rate – whichever is the greater.