HTM 03-01 A: _Hlk37000395 – Appendix 2: Summary of design conditions
[HTM 03-01 A – PDF page 163]
Appendix 2: Summary of design conditions
Appendix 2: Summary of design conditions
Application Ventilation Air-change
Supply filter
Temp
rate (ac/h)
Pressure (Pascal – Pa)
Noise (dB(A))
(°C)
Comments (for further information
grade (BS EN 16798)
see Chapter 8)
S/N – SUP2 18–28
General ward (level 0 and 1 care)
E –ve – –
Communal ward toilet
Single room S/E/N 0 or –ve SUP2 18–28
Single room WC E –ve – –
Clean utility S +ve SUP3 18–22
Dirty utility E –ve – –
S Lobby +10
Room 0
Ward isolation room (PPVL)
SUP2 – See Health Building Note 04-01 (Supplement 1)
E –5 SUP2 – See Table 4
Infectious diseases isolation room
S +10 H12 – See Table 3
Neutropaenic patient ward
Critical care areas (Level 2 and 3 care)
S +10 SUP1 – Isolation room may be –ve pressure or PPVL. See Table 3
Birthing room S & E SUP2 20–25 See Table 5
NICU/SCBU S & E +ve SUP1 20–28 Isolation room may be –ve pressure
For general and UCV operating suites and associated rooms, see specific guidance in Chapter 8 and typical design solutions in Appendix 7
S & E SUP2 18–25 Provide clean airflow path
Operating department recovery room
S & E +ve SUP2 18–22
Catheterisation room
[HTM 03-01 A – PDF page 164]
Application Ventilation Air-change
Supply filter
Temp
rate (ac/h)
Pressure (Pascal – Pa)
Noise (dB(A))
(°C)
Comments (for further information
grade (BS EN 16798)
see Chapter 8)
S & E +ve SUP2 – Stable conditions as specified for the imaging equipment
Interventional or non- interventional Imaging room of any type
S & E S/E SUP2 18–28
Sedation recovery room as in paragraph 8.16
S & E -5 SUP2 20–25 See Table 2
Endoscopic procedure room
E –ve – –
Endoscope reprocessing wash room
S & E Neutral SUP2 20–25 See Table 2
General treatment room
S & E – SUP2 – 18–25 See Table 2
Emergency department waiting area
Containment level 3 laboratory >20 H14* – 18–22 # See ACDP guide; *Filter in extract See Table 4
Post-mortem room
S & E S = 10 E = 12
–ve SUP2 18–22 Provide clean airflow path
Specimen store E – –ve – – – Fan accessible from outside of store
Notes:
Waiting and circulation areas should be directly or indirectly ventilated to provide a comfortable environment and control airborne contamination and odours.
18–22°C indicates the range over which the temperature may float.
18-22°C indicates the range over which the temperature should be capable of being controlled.
S = Suppy
E = Extract
N = Natural ventilation where possible