HTM 03-01 A: _Hlk37000395 – Standard layout 3 – single-corridor conventional operating suite with “lay-up” prep / _Hlk37000395 – Standard layout 4 – single-corridor UCV operating suite with SPS prep

Specialised ventilation for healthcare premises Part A: The concept, design, specification, installation and acceptance testing of healthcare ventilation systems · PDF pages 172–173 of 213 · Source file: HTM0301-PartA-accessible-F6.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 03-01 A – PDF page 172]

Standard layout 3 – single-corridor conventional operating suite with “lay-up” prep

Room Size (m3)‡ Air-change rate (ac/h) Nominal pressure (Pa) Flow rate (m3/s)

Theatre

≥22 Primary = 0.73 From Prep = 0.28 Total = 1.01

Anaesthetic

Design 15

0.24

Commissioned ≥10

Lay-up prep ≥22 0.35**

Scrub * – –

Utility – –5 0.40

Notes:

‡ Derived from Health Building Note 10-01 (2021). If room sizes differ from those given, recalculate the design air flows to

achieve the air change rate or door protection.

* This is a separate scrub and is not considered as being part of the theatre volume.

** Interchange is not permitted between the theatre and lay-up prep; therefore, as in Appendix 5, an airflow protection of 0.28 + 0.07 closed-door airflow is required as a minimum (but see also the “designers’ notes” in Appendix 4).

The volume of air to be extracted from the theatre should be determined by subtracting the airflow required for protection at the key door from the total air entering the space. The balance should be equally divided between the passive or active extract locations.

The extracts within the theatre and scrub may be either passive and fitted with pressure stabilisers or active and connected to the extract system. They should where possible be located at low level and positioned to promote the active ventilation and scouring of all areas of the space (see paragraph 8.92). Air transfer from theatre to anaesthetic room may be by pressure stabiliser or transfer grilles (see paragraphs A8.51 and A8.52 in Appendix 8). The anaesthetic room extract will be at low level (see Appendix 9).

LLE

Scrub

KEY TO SYMBOLS

0.73

Supply volume (m3/s)

Operating theatre

0.24

Extract volume (m3/s)

Anaesthetic

≥22

0.24

Nominal room pressure (Pa)

LLE

Air change rate (ac/h)

–5

0.40

0.35

Pressure stabiliser

>20

Utility

Prep (lay up)

LLE

≥22

Low-level active extract or pressure stabiliser to assist air distribution in theatre

Exit bay

Transfer grille

[HTM 03-01 A – PDF page 173]

Appendix 7: Operating suite design logic

Standard layout 4 – single-corridor UCV operating suite with SPS prep

Room Size (m3)‡ Air-change rate (ac/h) Nominal pressure (Pa) Flow rate (m3/s)

Theatre ≥22 #1.01

Anaesthetic

Design 15

0.24

Commissioned ≥10

Sterile pack store prep 0.10

Scrub * – –

Utility – –5 0.4

Notes:

‡ Derived from Health Building Note 10-01 (2021). If room sizes differ from those given, recalculate the design air flows to achieve the air change rate or door protection.

* This is a separate scrub and is not considered as being part of the theatre volume.

# Primary fresh-air volume for the UCV canopy or ≥22 ac/h or door protection

The volume of air to be extracted from the theatre should be determined by subtracting the airflow required for protection at the key door from the total air entering the theatre space. The balance should be equally divided between the passive or active extract locations.

The extracts within the theatre and scrub may be either passive and fitted with pressure stabilisers or active and connected to the extract system. They should where possible be located at low level and positioned to promote the active ventilation and scouring of all areas of the space (see paragraph 8.92). Air transfer from theatre to anaesthetic room may be by pressure stabiliser or transfer grilles (see paragraphs A8.51 and A8.52 in Appendix 8). The anaesthetic room extract will be at low level (see Appendix 9).

LLE

UCV operating theatre Scrub

KEY TO SYMBOLS

1.01

Supply volume (m3/s)

0.24

UCV primary air flow rate (m/s)

Extract volume (m3/s)

Anaesthetic

0.24

Nominal room pressure (Pa)

≥22

LLE

Air change rate (ac/h)

–5

0.40

Pressure stabiliser

>20

0.10

Utility

Prep (SPS)

LLE

Low-level active extract or pressure stabiliser to assist air distribution in theatre

Exit bay

Transfer grille