HTM 03-01 A: _Hlk37000395 – Standard layout 1 – Two-corridor conventional operating suite with “lay-up” prep / _Hlk37000395 – Standard layout 2 – two-corridor UCV operating suite with SPS prep
[HTM 03-01 A – PDF page 170]
Standard layout 1 – Two-corridor conventional operating suite with “lay-up” prep
Room Size (m3)‡ Air-change rate (ac/h) Nominal pressure (Pa) Flow rate (m3/s)
Theatre
≥22 Primary = 0.73 From Prep = 0.28 Total = 1.010
Anaesthetic
Design 15
0.24
Commissioned ≥10
Lay-up prep ≥22 0.28**
Scrub * – –
Notes:
‡ Derived from Health Building Note 10-01 (2021). If room sizes differ from those given, recalculate the design air flows to achieve
the air change rate or door protection.
*This is a separate scrub and is not considered as being part of the theatre volume.
** Interchange is not permitted between the theatre and lay-up prep; therefore, as in Appendix 5, an airflow protection of 0.28 m3/s is required as a minimum (but see also the “designers’ notes” in Appendix 4).
N.B.If the lay-up prep also has a door or hatch to the corridor, its supply airflow volume would increase to 0.35 m3/s
The volume of air to be extracted from the theatre should be determined by subtracting the airflow required for door protection at the key door from the total air entering the space. The balance should be equally divided between the passive or active extract locations.
The extracts within the theatre and scrub may be either passive and fitted with pressure stabilisers or active and connected to the extract system. They should where possible be located at low level and positioned to promote the active ventilation and scouring of all areas of the space (see paragraph 8.92). Air transfer from theatre to anaesthetic room may be by pressure stabiliser or transfer grilles (see paragraphs A8.51 and A8.52 in Appendix 8). The anaesthetic room extract will be at low level (see Appendix 9).
Corridor
KEY TO SYMBOLS
0.24
Supply volume (m3/s)
Anaesthetic Scrub
0.24
Extract volume (m3/s)
Nominal room pressure (Pa)
Air change rate (ac/h)
0.73
Pressure stabiliser
Operating theatre
0.28
≥22
LLE
Low-level active extract or pressure stabiliser to assist air distribution in theatre
Prep (lay up)
Transfer grille
LLE
≥22
Service corridor
Fire door
[HTM 03-01 A – PDF page 171]
Appendix 7: Operating suite design logic
Standard layout 2 – two-corridor UCV operating suite with SPS prep
Room Size (m3)‡ Air-change rate (ac/h) Nominal pressure (Pa) Flow rate (m3/s)
Theatre ≥22 # 1.01
Anaesthetic
Design 15
0.24
Commissioned ≥10
Sterile pack store prep 0.10
Scrub * – –
Notes:
‡ Derived from Health Building Note 10-01 (2021). If room sizes differ from those given, recalculate the design air flows to
achieve the air change rate or door protection.
* This is a separate scrub and is not considered as being part of theatre volume.
# Primary fresh-air volume to UCV canopy only or ≥22 or door protection
The volume of air to be extracted from the theatre should be determined by subtracting the airflow required for door protection at the key door from the total air entering the space. The balance should be equally divided between the passive or active extract locations.
The extracts within the theatre and scrub may be either passive and fitted with pressure stabilisers or active and connected to the extract system. They should where possible be located at low level and positioned to promote the active ventilation and scouring of all areas of the space (see paragraph 8.92). Air transfer from theatre to anaesthetic room may be by pressure stabiliser or transfer grilles (see paragraphs A8.51 and A8.52 in Appendix 8). The anaesthetic room extract will be at low level (see Appendix 9).
Corridor
KEY TO SYMBOLS
0.24
Supply volume (m3/s)
Anaesthetic Scrub
0.24
Extract volume (m3/s)
Nominal room pressure (Pa)
Air change rate (ac/h)
1.01
Pressure stabiliser
UCV primary air flow rate (m/s)
0.10
LLE
Low-level active extract or pressure stabiliser to assist air distribution in theatre
Prep (SPS)
UCV operating theatre
Transfer grille
LLE
≥22
Service corridor
Fire door