HTM 03-01 A: _Hlk37000395 – Cabinet AHU
[HTM 03-01 A – PDF page 162]
Cabinet AHU
Figure A4 Schematic of typical cabinet-style AHU with energy recovery by run-around coil
Extract
Intake
Supply
Motorised damper
Motorised damper
Fog coil
Filter
Return air filter
Final filter
Run-around coil
Extract
fan
Heater battery
Run-around coil
Supply
fan
Motorised
damper
Cooling coil with
drainage system
Discharge
Note: Other types of compact vertical AHUs are possible
[HTM 03-01 A – PDF page 163]
Appendix 2: Summary of design conditions
Appendix 2: Summary of design conditions
Application Ventilation Air-change
Supply filter
Temp
rate (ac/h)
Pressure (Pascal – Pa)
Noise (dB(A))
(°C)
Comments (for further information
grade (BS EN 16798)
see Chapter 8)
S/N – SUP2 18–28
General ward (level 0 and 1 care)
E –ve – –
Communal ward toilet
Single room S/E/N 0 or –ve SUP2 18–28
Single room WC E –ve – –
Clean utility S +ve SUP3 18–22
Dirty utility E –ve – –
S Lobby +10
Room 0
Ward isolation room (PPVL)
SUP2 – See Health Building Note 04-01 (Supplement 1)
E –5 SUP2 – See Table 4
Infectious diseases isolation room
S +10 H12 – See Table 3
Neutropaenic patient ward
Critical care areas (Level 2 and 3 care)
S +10 SUP1 – Isolation room may be –ve pressure or PPVL. See Table 3
Birthing room S & E SUP2 20–25 See Table 5
NICU/SCBU S & E +ve SUP1 20–28 Isolation room may be –ve pressure
For general and UCV operating suites and associated rooms, see specific guidance in Chapter 8 and typical design solutions in Appendix 7
S & E SUP2 18–25 Provide clean airflow path
Operating department recovery room
S & E +ve SUP2 18–22
Catheterisation room
[HTM 03-01 A – PDF page 164]
Application Ventilation Air-change
Supply filter
Temp
rate (ac/h)
Pressure (Pascal – Pa)
Noise (dB(A))
(°C)
Comments (for further information
grade (BS EN 16798)
see Chapter 8)
S & E +ve SUP2 – Stable conditions as specified for the imaging equipment
Interventional or non- interventional Imaging room of any type
S & E S/E SUP2 18–28
Sedation recovery room as in paragraph 8.16
S & E -5 SUP2 20–25 See Table 2
Endoscopic procedure room
E –ve – –
Endoscope reprocessing wash room
S & E Neutral SUP2 20–25 See Table 2
General treatment room
S & E – SUP2 – 18–25 See Table 2
Emergency department waiting area
Containment level 3 laboratory >20 H14* – 18–22 # See ACDP guide; *Filter in extract See Table 4
Post-mortem room
S & E S = 10 E = 12
–ve SUP2 18–22 Provide clean airflow path
Specimen store E – –ve – – – Fan accessible from outside of store
Notes:
Waiting and circulation areas should be directly or indirectly ventilated to provide a comfortable environment and control airborne contamination and odours.
18–22°C indicates the range over which the temperature may float.
18-22°C indicates the range over which the temperature should be capable of being controlled.
S = Suppy
E = Extract
N = Natural ventilation where possible
[HTM 03-01 A – PDF page 165]
Appendix 3: Hierarchy of cleanliness
Appendix 3: Hierarchy of cleanliness
Airflow rate for bacterial contaminant
dilution
Class Room Nominal pressure (Pa)a Flow in or supply (m3/s) Flow out or extract
(m3/s)
Sterile Preparation room
(a) lay-up
See standard schemes in Appendix 7 for recommended design values
(b) sterile pack store
Operating theatre
Scrub bayb
Clean Sterile pack store
+ve
6 ac/h
–
Anaesthetic roomc
15c
The greater of 15 ac/h or 0.15
The greater of 15 ac/h or 0.15
Scrub room
–
0.10 mind
Transitional Recovery room
15 ac/he
15 ac/he
Clean corridor
(See note f)
7 ac/h
General access corridor
(See note f)
7 ac/h
Changing rooms
7 ac/h
7 ac/h
Dirty Service corridor
–
(See note g)
Utility room
–5 or 0
–
0.40 or 0.10
Notes: a. Nominal room pressures are given to facilitate setting up of pressure-relief dampers, the calculation process, and the sizing
of transfer devices. In practice, the resultant pressures are not immutable provided the desired airflow rates and movement directions are achieved.
b. An open or semi-open bay is considered to be part of the operating theatre; a low-level extract under the scrub trough is
required. (See Chapter 8 paragraph 8.45 onwards and “Note” for more information.)
c. For design purposes, anaesthetic should be assumed to be at 15 Pa. When commissioning, equal to or greater than 10 Pa is
considered suitable.
d. May need to be increased if scrub is large to promote scouring.
e. 15 ac/h is considered necessary for the control of anaesthetic gas (see Appendix 9).
f. Supply airflow rate necessary to make up 7 ac/h after taking into account secondary air from cleaner areas.
g. No dilution requirement. Temperature control requirements only.
[HTM 03-01 A – PDF page 166]
Appendix 4: Leakage flows in m3/s through closed door gaps
Type Pressure difference (Pa)
Single door 0.03 0.05 0.06 0.06 0.07 0.08 0.09 0.10
0.04 0.06 0.07 0.08 0.09 0.10 0.11 0.12
Single door + half
0.05 0.08 0.10 0.11 0.12 0.13 0.14 0.15
Double door
Designers’ notes:
The door gaps assumed are 4 mm along the bottom, 3 mm at the top and sides, and 2 mm between double leaves.
If doors are fitted with cold smoke seals, these will significantly reduce the door leakage rate when new and undamaged. It is therefore recommended that provision for the design leakage be factored into the size of the appropriate transfer grille or pressure stabiliser. Failure to do this will result in air-gap whistles and doors being held partially open by air pressure.
Factory-assembled door-sets with a steel frame and pre-hung leaves are becoming common. There is effectively no leakage across these doors when closed. Therefore, when this type of door assembly is fitted, the door leakage can be ignored and the design airflow into the room reduced accordingly. The design airflow would then become that required either (i) for open door protection (Appendix 5), or (ii) to achieve the specified air-change rate – whichever is the greater.
[HTM 03-01 A – PDF page 167]
Appendix 5
Appendix 5: Recommended airflow rates in m3/s through a doorway between rooms of different cleanliness to control cross-contamination
Room class Dirty Transitional Clean Sterile
Sterile Hatch
0.3
0.24
0.18
Single door
0.47
0.39
0.28
0 or 0.28a
Double door
0.95
0.75
0.57
0 or 0.57a
Clean Single door
0.39
0.28
0 or 0.28a
Double door
0.75
0.57
0 or 0.57a
Transitional Single door
0.28
0 or 0.28a
Double door
0.57
0 or 0.57a
Dirty Single door
Open single door = 0.80 m x 2.01 m high
Double door
Open double door = 1.80 m x 2.01 m high
Designers’ notes:
The degree of protection required at an open doorway between rooms is dependent on the degree of difference in cleanliness between them.
Flow-rate required between rooms within the same class tends to zero as class reduces.
a. If two rooms are of equal cleanliness, no flow is required (in practice there will be an interchange in either direction) and the
design of the air movement will assume zero airflow. In certain cases, however, interchange is not permitted, and a protection airflow of 0.28 is assumed in the design – for example, in the case of a preparation room used as a “lay up”.
[HTM 03-01 A – PDF page 168]
Appendix 6: Typical approximate pressures in an operating suite when a given door is open
Typical approximate effect on other rooms
Door open between Typical approximate resultant
pressure in these rooms (Pa) Room Pressure (Pa)
Anaesthetic
Operating theatre and corridor
Preparation – lay-up
or
Utility
–6
Scrub bay and corridor
Preparation – sterile pack store
Preparation – lay-up
Utility
–9
Operating theatre and anaesthetic room (or other series room with double doors)
Preparation – sterile pack store
No change
Operating theatre and Utility room
or
Operating theatre and preparation room
Preparation – lay-up
Utility
–6
Anaesthetic room and corridor (or other series room with double doors)
Operating theatre
Preparation – sterile pack store
No change
Preparation room and corridor
or
Utility room and corridor
Utility room and outer corridor No change
Notes:
The room differential pressure protects against reverse flows when the door is closed.
The flow of air through a doorway protects against reverse airflow when the door is open.
Pressure stabilisers control flow and ensure a known airflow path between rooms when doors are closed and also reduce backflow between rooms when doors to other rooms are open.
[HTM 03-01 A – PDF page 169]
Appendix 7: Operating suite design logic
Appendix 7: Operating suite design logic
Is it a new build operating suite?
NO
YES
It is a refurbishment
Is it a conventional suite?
Is it a scheme based on a standard
layout from
YES
NO
a previous
HTM?
YES
NO
NO
Does it have a “lay-up” prep?
Use appropriate stand- ard layout information
1 to 8
YES
NO
Do the room sizes accord with
HBN 10-01?
YES
Use standard layout
information 1 or 3
Is it a UCV suite?
NO
YES
NO
Does it have an SPS prep?
YES
NO
Do the room sizes accord with
HBN 10-01?
YES
Use standard layout
information
2 or 4 Apply basic design principles and/or use
the design method in Appendix 8