HTM 03-01 A: _Hlk37000395 – Cabinet AHU

Specialised ventilation for healthcare premises Part A: The concept, design, specification, installation and acceptance testing of healthcare ventilation systems · PDF pages 162–169 of 213 · Source file: HTM0301-PartA-accessible-F6.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 03-01 A – PDF page 162]

Cabinet AHU

Figure A4 Schematic of typical cabinet-style AHU with energy recovery by run-around coil

Extract

Intake

Supply

Motorised damper

Motorised damper

Fog coil

Filter

Return air filter

Final filter

Run-around coil

Extract

fan

Heater battery

Run-around coil

Supply

fan

Motorised

damper

Cooling coil with

drainage system

Discharge

Note: Other types of compact vertical AHUs are possible

[HTM 03-01 A – PDF page 163]

Appendix 2: Summary of design conditions

Appendix 2: Summary of design conditions

Application Ventilation Air-change

Supply filter

Temp

rate (ac/h)

Pressure (Pascal – Pa)

Noise (dB(A))

(°C)

Comments (for further information

grade (BS EN 16798)

see Chapter 8)

S/N – SUP2 18–28

General ward (level 0 and 1 care)

E –ve – –

Communal ward toilet

Single room S/E/N 0 or –ve SUP2 18–28

Single room WC E –ve – –

Clean utility S +ve SUP3 18–22

Dirty utility E –ve – –

S Lobby +10

Room 0

Ward isolation room (PPVL)

SUP2 – See Health Building Note 04-01 (Supplement 1)

E –5 SUP2 – See Table 4

Infectious diseases isolation room

S +10 H12 – See Table 3

Neutropaenic patient ward

Critical care areas (Level 2 and 3 care)

S +10 SUP1 – Isolation room may be –ve pressure or PPVL. See Table 3

Birthing room S & E SUP2 20–25 See Table 5

NICU/SCBU S & E +ve SUP1 20–28 Isolation room may be –ve pressure

For general and UCV operating suites and associated rooms, see specific guidance in Chapter 8 and typical design solutions in Appendix 7

S & E SUP2 18–25 Provide clean airflow path

Operating department recovery room

S & E +ve SUP2 18–22

Catheterisation room

[HTM 03-01 A – PDF page 164]

Application Ventilation Air-change

Supply filter

Temp

rate (ac/h)

Pressure (Pascal – Pa)

Noise (dB(A))

(°C)

Comments (for further information

grade (BS EN 16798)

see Chapter 8)

S & E +ve SUP2 – Stable conditions as specified for the imaging equipment

Interventional or non- interventional Imaging room of any type

S & E S/E SUP2 18–28

Sedation recovery room as in paragraph 8.16

S & E -5 SUP2 20–25 See Table 2

Endoscopic procedure room

E –ve – –

Endoscope reprocessing wash room

S & E Neutral SUP2 20–25 See Table 2

General treatment room

S & E – SUP2 – 18–25 See Table 2

Emergency department waiting area

Containment level 3 laboratory >20 H14* – 18–22 # See ACDP guide; *Filter in extract See Table 4

Post-mortem room

S & E S = 10 E = 12

–ve SUP2 18–22 Provide clean airflow path

Specimen store E – –ve – – – Fan accessible from outside of store

Notes:

Waiting and circulation areas should be directly or indirectly ventilated to provide a comfortable environment and control airborne contamination and odours.

18–22°C indicates the range over which the temperature may float.

18-22°C indicates the range over which the temperature should be capable of being controlled.

S = Suppy

E = Extract

N = Natural ventilation where possible

[HTM 03-01 A – PDF page 165]

Appendix 3: Hierarchy of cleanliness

Appendix 3: Hierarchy of cleanliness

Airflow rate for bacterial contaminant

dilution

Class Room Nominal pressure (Pa)a Flow in or supply (m3/s) Flow out or extract

(m3/s)

Sterile Preparation room

(a) lay-up

See standard schemes in Appendix 7 for recommended design values

(b) sterile pack store

Operating theatre

Scrub bayb

Clean Sterile pack store

+ve

6 ac/h

–

Anaesthetic roomc

15c

The greater of 15 ac/h or 0.15

The greater of 15 ac/h or 0.15

Scrub room

–

0.10 mind

Transitional Recovery room

15 ac/he

15 ac/he

Clean corridor

(See note f)

7 ac/h

General access corridor

(See note f)

7 ac/h

Changing rooms

7 ac/h

7 ac/h

Dirty Service corridor

–

(See note g)

Utility room

–5 or 0

–

0.40 or 0.10

Notes: a. Nominal room pressures are given to facilitate setting up of pressure-relief dampers, the calculation process, and the sizing

of transfer devices. In practice, the resultant pressures are not immutable provided the desired airflow rates and movement directions are achieved.

b. An open or semi-open bay is considered to be part of the operating theatre; a low-level extract under the scrub trough is

required. (See Chapter 8 paragraph 8.45 onwards and “Note” for more information.)

c. For design purposes, anaesthetic should be assumed to be at 15 Pa. When commissioning, equal to or greater than 10 Pa is

considered suitable.

d. May need to be increased if scrub is large to promote scouring.

e. 15 ac/h is considered necessary for the control of anaesthetic gas (see Appendix 9).

f. Supply airflow rate necessary to make up 7 ac/h after taking into account secondary air from cleaner areas.

g. No dilution requirement. Temperature control requirements only.

[HTM 03-01 A – PDF page 166]

Appendix 4: Leakage flows in m3/s through closed door gaps

Type Pressure difference (Pa)

Single door 0.03 0.05 0.06 0.06 0.07 0.08 0.09 0.10

0.04 0.06 0.07 0.08 0.09 0.10 0.11 0.12

Single door + half

0.05 0.08 0.10 0.11 0.12 0.13 0.14 0.15

Double door

Designers’ notes:

The door gaps assumed are 4 mm along the bottom, 3 mm at the top and sides, and 2 mm between double leaves.

If doors are fitted with cold smoke seals, these will significantly reduce the door leakage rate when new and undamaged. It is therefore recommended that provision for the design leakage be factored into the size of the appropriate transfer grille or pressure stabiliser. Failure to do this will result in air-gap whistles and doors being held partially open by air pressure.

Factory-assembled door-sets with a steel frame and pre-hung leaves are becoming common. There is effectively no leakage across these doors when closed. Therefore, when this type of door assembly is fitted, the door leakage can be ignored and the design airflow into the room reduced accordingly. The design airflow would then become that required either (i) for open door protection (Appendix 5), or (ii) to achieve the specified air-change rate – whichever is the greater.

[HTM 03-01 A – PDF page 167]

Appendix 5

Appendix 5: Recommended airflow rates in m3/s through a doorway between rooms of different cleanliness to control cross-contamination

Room class Dirty Transitional Clean Sterile

Sterile Hatch

0.3

0.24

0.18

Single door

0.47

0.39

0.28

0 or 0.28a

Double door

0.95

0.75

0.57

0 or 0.57a

Clean Single door

0.39

0.28

0 or 0.28a

Double door

0.75

0.57

0 or 0.57a

Transitional Single door

0.28

0 or 0.28a

Double door

0.57

0 or 0.57a

Dirty Single door

Open single door = 0.80 m x 2.01 m high

Double door

Open double door = 1.80 m x 2.01 m high

Designers’ notes:

The degree of protection required at an open doorway between rooms is dependent on the degree of difference in cleanliness between them.

Flow-rate required between rooms within the same class tends to zero as class reduces.

a. If two rooms are of equal cleanliness, no flow is required (in practice there will be an interchange in either direction) and the

design of the air movement will assume zero airflow. In certain cases, however, interchange is not permitted, and a protection airflow of 0.28 is assumed in the design – for example, in the case of a preparation room used as a “lay up”.

[HTM 03-01 A – PDF page 168]

Appendix 6: Typical approximate pressures in an operating suite when a given door is open

Typical approximate effect on other rooms

Door open between Typical approximate resultant

pressure in these rooms (Pa) Room Pressure (Pa)

Anaesthetic

Operating theatre and corridor

Preparation – lay-up

or

Utility

–6

Scrub bay and corridor

Preparation – sterile pack store

Preparation – lay-up

Utility

–9

Operating theatre and anaesthetic room (or other series room with double doors)

Preparation – sterile pack store

No change

Operating theatre and Utility room

or

Operating theatre and preparation room

Preparation – lay-up

Utility

–6

Anaesthetic room and corridor (or other series room with double doors)

Operating theatre

Preparation – sterile pack store

No change

Preparation room and corridor

or

Utility room and corridor

Utility room and outer corridor No change

Notes:

The room differential pressure protects against reverse flows when the door is closed.

The flow of air through a doorway protects against reverse airflow when the door is open.

Pressure stabilisers control flow and ensure a known airflow path between rooms when doors are closed and also reduce backflow between rooms when doors to other rooms are open.

[HTM 03-01 A – PDF page 169]

Appendix 7: Operating suite design logic

Appendix 7: Operating suite design logic

Is it a new build operating suite?

NO

YES

It is a refurbishment

Is it a conventional suite?

Is it a scheme based on a standard

layout from

YES

NO

a previous

HTM?

YES

NO

NO

Does it have a “lay-up” prep?

Use appropriate stand- ard layout information

1 to 8

YES

NO

Do the room sizes accord with

HBN 10-01?

YES

Use standard layout

information 1 or 3

Is it a UCV suite?

NO

YES

NO

Does it have an SPS prep?

YES

NO

Do the room sizes accord with

HBN 10-01?

YES

Use standard layout

information

2 or 4 Apply basic design principles and/or use

the design method in Appendix 8