HTM 03-01 A: _Hlk37000395 – UCV canopy leakage tests / _Hlk37000395 – Vertical flow UCV canopy air velocity tests
[HTM 03-01 A – PDF page 144]
detect the size and number of particles present.
theatre control panel. (For an example of a grid for a 2.8 m × 2.8 m canopy, see Figure 3.)
UCV canopy leakage tests
12.60 Spot readings are taken at several filter faces to establish the smallest non- penetrating particle size. If particles at or above this size are detected when subsequent scans are made, there is deemed to be a significant leak at, or near, the test position.
12.57 The diffuser screen fitted below the face of the canopy terminal filters should be lowered or removed while the leakage tests are being carried out.
UCV canopy clean zone leak test
12.61 The test will confirm that there is no unfiltered air leakage in the canopy.
12.58 The installed terminal EPA filters are to be checked to ensure that their grade accords with the design specification and that their performance has been certified by their manufacturer.
Test equipment
12.62 The construction joints and service penetration points under the UCV canopy within its side walls or boundary air curtain should be scanned to prove that there are no leaks.
12.59 An LSAPC connected to an isokinetic fishtail scanning probe will be used to
Figure 3 Example of a test grid for a 2.8 m × 2.8 m UCV terminal
Theatre control panel
3 4 + A + + + + + + + + +
B +
+ + + + + + + + +
A + 280 mm
x x x + x x x
+ +
280 mm
x x x + x x x
C + D +
x x x + x x x
E +
+
+ + + + + +
x x x + x x x
F +
Measure velocity at 2 m above floor level
x x x + x x x
G +
x
x x x + x x x
+ + + +
H +
Measure velocity at 2 m and 1 m above floor level
+ I + + + + + + + + +
Centre point
+ J + + + + + + + + +
For larger UCV terminals, add extra (280 mm x 280 mm) test squares symmetrically around the periphery of the grid and increase the inner zone in accordance with the guidance in paragraphs 12.50–12.56 of Health Technical Memorandum 03-01 Part A.
[HTM 03-01 A – PDF page 145]
12.0 Acceptance testing: validation
Test instrument
12.63 A leak is defined as a significant and repeatable rise above the background level.
Terminal EPA filter seal leak test
12.64 The test will confirm that there is no unfiltered air bypassing the EPA filter seal.
12.74 The measuring instrument should be a thermal anemometer with a digital readout. The instrument resolution should be at least 0.01 m/s, have a tolerance of ±0.015 m/s or 3% and be calibrated down to 0.15 m/s or lower. An alternative instrument may be used providing it is of no lesser specification.
12.65 Each EPA filter seal should be scanned to prove that there are no leaks.
Test method
12.66 A leak is defined as a significant and repeatable rise above the background level.
EPA filter media leak test
12.75 The instrument should be mounted on a test stand and set to take a mean reading over a 10-second sample interval.
12.67 The test will confirm that the EPA filters have not sustained damage while being installed.
12.76 The test instrument should record readings automatically for later download or be connected to a printer.
12.68 The face of each EPA filter should be scanned to prove that there are no leaks.
12.77 The test stand should be positioned on each test point in turn and the reading taken when the instrument has stabilised.
12.69 A leak is defined as a significant and repeatable rise above the background level.
12.78 When taking a reading, the test person should not stand within the same quadrant as the test instrument.
Vertical flow UCV canopy air velocity tests
Test setup
12.70 The canopy face diffuser screen should be in place for these tests.
12.79 Readings are to be taken at the test positions with the instrument probe facing the wall housing the theatre control panel – commencing at the first test position. Readings are taken either working along the rows from left to right or for all test positions in one quadrant at a time.
12.71 Take spot readings to establish that the room is within the specified temperature and humidity test conditions.
12.72 Set out the test grid as described previously.
12.80 When all test positions under one half of the canopy have been covered, readings of temperature and humidity are taken at the specified height in the centre of the canopy. The readouts from the theatre control panel should be recorded at this time.
12.73 Swing the operating lamp arms and any other stem arms so that they align to present the least resistance to airflow, are perpendicular to the front edge of the test sheet and face the back edge. Any lamp and equipment heads should as far as practicable be outside of the UCV canopy footprint (see photographs).
12.81 Having completed one half of the test grid, the operating lamp arms and any other stem arms should be swung round through 180º and the test stand reversed so that the wall housing the theatre control panel is behind the test person. Readings