HTM 03-01 A: _Hlk37000395 – Local exhaust ventilation (LEV)

Specialised ventilation for healthcare premises Part A: The concept, design, specification, installation and acceptance testing of healthcare ventilation systems · PDF pages 119–121 of 213 · Source file: HTM0301-PartA-accessible-F6.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 03-01 A – PDF page 119]

9.0 Equipment selection factors

appear on any point of use indicator or control panel.

Local exhaust ventilation (LEV)

9.233 Devices that use an inflow of air to control exposure of staff to hazardous substances are classified as LEV systems under the COSHH Regulations.

9.229 Visual indication that the AHU is operating within its prescribed parameters should be provided in critical areas at a manned staff location, for example, the reception or staff base. These need only take the form of a green light to show the system is operational and a red light to show that it is not.

Room temperature control

9.234 An LEV system will typically comprise a unit where the airborne hazard is captured, ductwork to convey the extract air to the fan and a discharge stack. The extract air may be filtered or centrifugally separated to remove any particulate material prior to discharge. HSG 258 produced by the Health & Safety Executive gives detailed guidance.

9.230 The limits for room temperature set point are generally between 18ºC and 25ºC depending on the particular application, and in some specialised instances (for example, operating departments) are adjustable within a predetermined range by the user.

9.235 It is important to recognise at the design stage whether an extract is being provided for comfort, to remove odours or to remove hazards, in which case it will be an LEV system. Chapter 8 lists typical devices used in healthcare applications.

9.236 The quantity and location of the terminals supplying the make-up air is an important factor in the design of LEV systems.

9.237 LEV systems are statutory items that will be subject to an independent examination and test at least every 14 months by a competent person.

9.231 The selection of temperature set point for each room or zone may be by a control facility in the room/zone, or remotely at the control panel or BMS. Where the control device is mounted within the room/zone and adjustable by the user, it should be marked either “raise” and “lower” or “+” and “–“. It should control within a specified temperature range to suit the user requirement with a control tolerance of +1 K. All other control set points should be selectable either on the control panel or at the BMS interface.

Extract ductwork and fan

9.238 Extract ductwork for an LEV system should, where possible, be installed outside of a building. Where it has to be inside, it should take the most direct route through, with as few bends or changes of direction as possible.

9.232 Where local control is provided, an indication of temperature will be required locally, or at a staff base (if appropriate), using an analogue or digital indicator. The indicator should be large enough to be read from the normal working position (for example, at the operating table in a theatre). This may be mounted in a supervisory control panel, with the signal repeated on the main system control panel or BMS. It is important that this indicator displays the actual measured temperature and not the selected temperature.

9.239 All ductwork joints should be sealed and ideally there should be no access hatches. Where access hatches have to be provided, they should be of a type that has a hermetic seal.

[HTM 03-01 A – PDF page 120]

9.246 If extract filters are fitted in the ductwork the system design should allow them to be changed safely.

9.240 Some substances are particularly corrosive, so the choice of material for the ductwork, and type of extract fan fitted, should reflect the nature of the substance being conveyed.

9.247 Current standards permit the installation of microbiological safety cabinets with integral fans, provided that the extract ductwork can be kept short (that is, less than 2 m); such an installation, however, is likely to be noisy and is not recommended for use in new buildings.

9.241 The ductwork should either be fire rated or fitted with intumescent collars where it passes through fire compartments within the building. This will ensure that the extract system is unobstructed and always open to atmosphere up to the discharge point.

LEV discharge stack arrangements

9.242 Some LEV systems (for example, microbiological safety cabinets) HEPA-filter the extract air within the cabinet unit, but it should not be assumed that the exhaust air will be totally free from microbiological or other hazardous material.

9.248 Roof-level discharge, wherever practicable, is preferred since it removes much of the uncertainty over air re- entering the building through ventilation inlets or windows. In such an installation, the extract fan should be situated separate from the LEV captor unit and close to the discharge stack to maintain the duct within the building under negative pressure.

9.243 The extract ductwork should as far as practicable be kept under negative pressure while inside the building. The extract fan should be located outside of the building or if this is not practicable, as close as possible to the outside so that any ductwork on the discharge side inside the building is kept to an absolute minimum.

9.249 The discharge point on a flat roof should be through a terminal at least 3 m above roof level. This will protect those who may need to access the roof. Terminals at other roof types need to be high enough to prevent the wind blowing across the roof from causing downdrafts.

9.244 The extract fan drive motor should be out of the airstream and it should be possible to change the motor without disturbing the fan or its casing.

9.250 Where there are adjacent buildings with opening windows, or where downdraughts are likely to occur, it may be necessary to increase the height of the discharge stack in order to achieve adequate dispersal. In complex locations, airflow modelling or wind tunnel tests may be required to determine the optimum height

9.245 Duplex fans are only required when several LEV systems share a common extract system (for example, multiple fume cupboards in a large pathology department where it can be anticipated that at least one cupboard will always be in use or need to be available for use). In such a situation each cupboard should be fitted with a non-return damper at the point that it joins the common system and be capable of being isolated from the common extract system. The common extract duct should be large enough to handle the combined extract volume from all the systems that feed into it.

9.251 The discharge stack should have an open end. It may be fitted with a collar to reduce its area and so increase the air efflux velocity at the point of discharge (known as the venturi effect). To ensure that air leaving the terminal is not deflected down but allowed to disperse freely, the terminal cannot be fitted with any sort of cover or

[HTM 03-01 A – PDF page 121]

9.0 Equipment selection factors

LEV system information and identification

hat. A drain may be required at the base of the discharge stack to remove any rain that enters (see photograph).

Typical LEV discharge stacks

9.252 Once installed, all elements of each LEV system should be uniquely identified with a permanent label as described in Chapter 13.

9.253 There is a statutory requirement to have information on the design and required operational performance of an LEV system available to those who are responsible for its operation and maintenance. The designer should ensure that this information is available at handover.