HTM 03-01 A: _Hlk37000395 – Distributed air-conditioning elements / _Hlk37000395 – AHUs: automatic control
[HTM 03-01 A – PDF page 113]
9.0 Equipment selection factors
theatre to prevent perturbation of the UCV canopy air pattern.
switch should be easily accessible from, in airflow terms, the least clean side of the damper.
Baffles should be easy to clean and where radiological or laser protection is not required can be made of a rigid transparent material so that the action of the pressure stabiliser can be easily observed.
9.183 Pressure stabilisers should be of the balanced blade type, with the facility to make fine adjustment of the pressure setting. They should be silent in operation and give a seal as tight as practicable when closed. The materials of construction and method of assembly should allow for cleaning and disinfection.
Distributed air-conditioning elements
Active and passive chilled beams
9.184 Pressure stabilisers should be wall- mounted in a visible location so that their operation can be readily observed. For sizing criteria, refer to the manufacturer’s information. When fitted at low level, they may require a stand-off cage to prevent occlusion (see photograph).
Pressure stabiliser with stand-off cage
9.186 See paragraph 5.18 onwards for information on the use of these devices in healthcare premises and CIBSE Guide B for technical guidance.
Constant volume boxes
9.187 These are units fitted in or at the termination of ductwork that contain a mechanism to maintain a constant output air volume regardless of variation in the air pressure to the supply side of the unit. Where fitted they should be accessible for maintenance as the internal mechanism that controls the constant output will need periodic cleaning.
Variable Air Volume (VAV) boxes
9.188 Variable air volume systems are all-air systems which achieve local control by varying (throttling) the amount of air being supplied to each space, room or zone.
Standard type VAV systems deliver air that has been cooled to a set temperature (usually 13ºC) and then control the temperature in a space by varying the quantity of air supplied rather than the supply air temperature – which is kept constant.
9.185 Pressure stabilisers may need to be fitted with a stand-off baffle on their discharge side to prevent a sight line in situations where a laser will be used, and may be lead-lined for radiological protection if required (see photograph after paragraph 8.35). Baffles may also be needed to preserve privacy or prevent discharge air causing draughts within an anaesthetic room or bedroom. A stand-off baffle will always be needed on the theatre side of the pressure stabiliser between a “Lay-up” preparation room and a UCV
[HTM 03-01 A – PDF page 114]
VAV boxes are used as terminal devices at the supply end of ductwork to modulate the quantity of supply air to the space.
9.192 They are not suitable for use in patient bedrooms due to the fan noise and maintenance access issues.
AHUs: automatic control
There are variations to standard VAV systems which allow air supply temperatures to modulate upwards with the aim of:
• reducing energy usage by allowing higher air supply temperatures at part-load conditions;
• improving ventilation effectiveness at part-load by having higher airflows – VAV can be as low as 10% of peak at low-load conditions depending on the equipment used;
9.193 Chapter 6 of this document gives guidance on energy control strategies and Chapter 7 gives guidance on the point of use factors. Chapter 8 contains guidance to specific healthcare departments and their environmental and functional requirements. This section gives guidance on the control of the AHU and its subsystems. When developing a “controls specification”, the designer should consider the guidance given in all of these chapters.
9.194 Various options for control of single- and multi-zone air-conditioning systems are given in CIBSE Guide B.
• allowing the system to operate using warm air in winter for pre-heating warm-up in well-insulated buildings where heating is only used in very cold weather and for building pre- heat.
General requirements
9.195 The basic requirements for an automatic control system are as follows:
9.189 In most critical areas of a hospital a fixed air-change rate is required when they are in use. VAV is therefore generally limited to non-clinical applications.
• plant start, run, set-back and stop sequence;
Stand-alone air-conditioners
• control of the volumetric airflow;
• control of the system or room pressure;
• temperature control and indication;
• humidity control and indication;
9.190 See paragraph 5.25 onwards for information on these units. The ceiling void should never be used as a plenum either for the primary air supply or fan coil supply or return air paths. (See CIBSE Guide B for installation notes.)
• devices to monitor and indicate the plant’s operating state;
Powered air terminal filter units
• alarms to indicate plant failure, low airflow, and filter state;
• the facility to collect data of actual usage and energy consumption.
9.191 This is an air-distribution-supply terminal box fitted with a fan and EPA or HEPA filter. Their use in the healthcare setting would be confined to spaces where a high air quality is required for a single room in an area supplied by a general AHU (for example, a local clean room).
The control functions actually provided will depend on the purpose of the ventilation system.
[HTM 03-01 A – PDF page 115]
9.0 Equipment selection factors
9.196 The designer should consider whether it is necessary for the supply and extract fans to be interlocked, either so that the supply fan will not operate unless airflow is established within the extract system, or vice-versa depending on the required pressures within the rooms being served.
evacuated if necessary. A similar situation occurs for patients in critical care areas and other units where a certain amount of preparation is required before patients can be safely moved. In all of these cases the ventilation to the critical area should continue to operate unless the AHU starts to draw in smoke. For these departments, a notice should be affixed to the fire control panel drawing attention for the need to liaise with departmental staff before switching off fan units.
9.197 The sequence switching of units in order to prevent transient reverse airflows will be particularly important in laboratory and pharmacy areas that also contain fume cupboards, safety cabinets and other LEV systems.
Location of controls
9.198 There will also be a need to determine the control strategy in the event of a fire either within the zone being served or within an adjoining zone and as detailed in the fire alarm cause and effect statement (see paragraph 7.16 onwards).
9.200 Facilities to start, set-back and stop the plant should be provided in the plantroom. Remote start and set-back control and indication, if required, should be provided at a manned staff location, for example, at the reception or staff base.
9.199 All supply AHUs should have a smoke sensor linked to the fire control panel and mounted in the main supply duct immediately downstream of the AHU. In the event of a fire in the AHU or smoke being drawn into the system from an outside source, it should cause the supply air fire damper to close and shut down the AHU.
9.201 Many ventilation systems may be completely shut down when the area served is not in active use. Alternatively, where there is a need to maintain a background condition, the ventilation output may be reduced by “setting back” the system. This will significantly reduce energy consumption and extend the life of filters and other system components. Controls to facilitate this should be triggered by the actual occupancy of the area rather than by a fixed time program (see paragraph 6.2 and associated Note).
Start up and shut down control sequence
In certain critical departments, it is preferable to maintain the ventilation in the case of a fire within the area. For example, in an operating department while undergoing surgery the patient cannot always be easily moved without significant risk. In the event of a fire in a staff or support area of the department or adjoining zone, the continued supply of air to a theatre will maintain it at a positive pressure and protect the patient and staff from the effects of smoke.
This will allow time for the patient to be stabilised so that they can be safely
9.202 The AHU should start and shut down in a pre-determined sequence. It should ensure that the fan does not start until the main dampers are open and the energy- recovery device is operational. On shut down there may be a need for a “run on” time to purge the area served before stopping the fan and closing the main
[HTM 03-01 A – PDF page 116]
dampers. Whether the supply or extract fan should start first and stop last will be determined by the pressure regime for the area served.
Set-back control
9.206 Steam-supplied fog or frost coils should be operated as an on/off device to ensure that there is no standing condensate at the base of the coil. They should be fitted with a serpentine sensor mounted upstream of the coil but not in contact with it. This will give “open loop” control; a set point of +1ºC is recommended.
Energy-recovery device
9.207 The energy-recovery device is normally controlled by sensors in the air intake downstream of the supply fan, before the cooling coil and the extract duct from the ventilated space.
Supply & extract fans
9.203 In previous times when fan motors only had two speeds, turning the system to “Set back” meant switching to the lower fan speed. With modern fans the speed is widely variable so “Set back” is not a fixed fan speed but rather a control strategy that reduces the system output in order to maintain a desired minimum condition. This may be related to the air velocity at a fixed point, air-change rate, pressure differential, temperature, humidity or a combination of these parameters. Providing a dew-point sensor in an internal space that brings the system onto “Set back” is a simple way of maintaining a minimum condition.
AHU running controls
Fog/frost coil control
9.208 The ErP Directive 1253/2014 requires a means of adjusting the fan speed. For plug fans this is provided by a separate inverter unit; for EC fans the control is integral to the fan motor. It should be remembered that most healthcare applications require known amounts of air to be delivered while the system is in use. Constant volume systems that deliver specified air-change rates are therefore the norm. Duct- or room-pressure-controlled variable-volume systems have a limited application in healthcare. However, fan-speed control is beneficial when “setting back” the system.
9.204 Fog coils supplied by low pressure hot water (LPHW) should be controlled using the Proportional mode. Their sensor should be located downstream of the coil to give “closed loop” control. The coil should raise the incoming air temperature by 2 K in order to ensure that air entering the pre- filter is above its dew-point, thus keeping it dry. The greater the energy put into the incoming air by the fog coil, the lower will be the efficiency of the energy-recovery device.
9.209 Inverters should not be mounted inside the air stream within the AHU. Ideally, they will be mounted on a frame with the control valves. Where inverters are mounted inside a control box with a safety master switch to cut the power supply when the box is opened, the inverter control and indicator pad will be located on the outside of the box. This will allow on- site staff to view the operating parameters and switch the system to manual control if a fault occurs with the automatic control system.
9.205 If the temperature downstream of the fog coil, as sensed by a serpentine thermostat, falls below the required set point over any part of the coil, the plant should automatically shut down in order to prevent damage to the other batteries. The serpentine thermostat cannot be in direct contact with the coil and should cover the entire coil face.
9.210 It is necessary to ensure that should the computer control system or its software develop a fault, the fan can be switched to
[HTM 03-01 A – PDF page 117]
9.0 Equipment selection factors
requirements of the zone with the highest load;
b. sequential control – used in single-
manual operation. This is particularly important for critical systems serving operating suites, high dependency care units of any type, patient isolation facilities, laboratories and pharmaceutical production suites.
zone systems, or multi-zone systems with averaging sensors where close control is not required. A room or duct temperature sensor controls the cooling coil and heater-battery in sequence to maintain constant room conditions.
In the healthcare setting it is important to recognise that “off-site” software support is no substitute for the ability of “on-site” staff to override the automatic control and keep the system operating in an emergency. Under these circumstances actions that may shorten the life of the plant are considered of secondary importance to that of preserving the health and safety of patients and staff.
9.214 The advantage of off-coil control is that accurate humidity control can be provided without relying on humidity sensors, which are prone to inaccuracy and drift. Off-coil control is expensive to operate in terms of energy consumption because of the lack of feedback of room loads. As a result, at low loads and in systems where there are large zonal variations, significant over-cooling and reheating will occur.
Heater-batteries
9.215 The control logic should prevent the cooling coil and heat recovery and/or heater-battery being on at the same time.
Humidifier control
9.211 The main heater-battery should be controlled in the same manner under the dictates of an off-coil temperature sensor, or a room temperature sensor, or the return air temperature depending on the plant configuration and method of control. Trimmer heater-batteries are generally controlled by a temperature sensor within the room, or by averaging temperature sensors within a zone.
9.216 Accurate humidity control can only be provided on single-zone systems, or multi- zone systems with zonal humidifiers. In the above systems, humidity sensors control the humidifier for low-level humidity control, and override the temperature controls to open the cooling-coil valve for high-level humidity control.
9.212 Heater-battery control valves should drive closed on system shutdown or fan failure. The control system should then automatically set to provide frost protection.
Cooling coils
9.217 Multi-zone systems are more usually controlled by a minimum humidity sensor located in the supply duct(s) following the last heater-battery.
9.213 There are two basic methods of control for cooling coils:
a. off-coil control – used in multi-zone
9.218 Overriding controls separate from the normal plant humidistat should be installed. Their purpose is to prevent excessive condensation in the conditioned space when starting up. A time delay should be incorporated into the humidifier control system such that the humidifier does not
systems or single-zone systems where close humidity control is required, to provide a constant maximum off- plant condition which satisfies the temperature and humidity
[HTM 03-01 A – PDF page 118]
be removed for service or replacement without the need to drain down the system.
9.225 Care should be taken to ensure that the installation of control valves and their associated pipework do not obstruct access to the AHU inspection doors, removable drainage trays, eliminator units and access hatches.
start until 30 minutes after the ventilation/ plant start-up. In addition, a high limit humidistat should be installed to limit the output of the humidifier so that the saturation in the duct does not exceed 70%. This humidistat is to control the added moisture; it is not necessary to install a dehumidifier to reduce the humidity of the incoming air if it already exceeds 70% (part load control).
9.219 The humidifier control valve should close when the ventilation system is in “set back”. In addition, on system shutdown, low airflow or fan failure, the humidifier should be isolated.
There are practical advantages in locating all control valves for an AHU in a bank (at a convenient height) at one end of the unit. (This should not result in an additional control lag.) The bank will hold the control valves and actuators, and fan inverters/controllers as necessary, and can be constructed “off site” (see also paragraph 9.209).
9.220 In a self-generating humidifier, if the humidifier is unused for a period exceeding 48 hours, it should automatically drain its water content, including that contained in the supply pipework, right back to the running main and leave itself empty.
Monitoring and alarms
9.226 Monitoring of the plant performance should be via a BMS to the estates and maintenance department.
9.221 With certain types of steam humidifier, it may be necessary to install a thermostat in the condensate line from the humidifier’s steam supply, to ensure that the steam at the control valve is as dry as possible before it is injected into the air supply.
9.222 The humidifier control system should ensure that it is switched off with the fan. It is preferable to design the control system so that the humidifier is isolated for an adequate time before the fan is turned off to purge humid air from the system.
Control valves: general
9.227 The “plant failure” and “low airflow” alarm should be initiated by a sensor located in the main air supply duct. This should operate when the air quantity fails to reach or falls to around 80% of the design value and will give indication of fan failure, damper closed, access door left open, or any other eventuality that could cause a reduction of air quantity. Monitoring the current drawn by the fan motor is not a substitute for a sensing device that is directly affected by the airflow. The sensing ring fitted to plug and EC fans will fulfil this function.
9.223 The fog/frost battery control valve should fail-safe, that is open in the event of power or airflow failure. All other valves will stop in their current position in the event of power failure and should drive closed in the event of airflow failure.
9.228 The “filter fault alarm” should be initiated by a predetermined increase of pressure differential across the filters, thereby indicating a dirty filter. The filter fault indication and alarm is information for the maintenance department; it should not
9.224 Control valves should be located in an accessible position. Isolation valves should be provided to enable the control valve to