HTM 03-01 A: _Hlk37000395 – Supply AHUs and associated extract units (pages 111–112)
[HTM 03-01 A – PDF page 111]
9.0 Equipment selection factors
should not be greater than 0.25 m/s. Further guidance on the selection of grilles and diffusers is given in the CIBSE Guide B.
Perforated rectangular diffusers can provide acceptable conditions within the occupied zone at up to 15 ac/h. In areas where a higher air-change rate is required, square or circular ceiling-mounted diffusers should be used.
9.170 In operating theatres, the supply terminals should be able to produce a movement of air in the operating zone 1 m above floor level of between 0.2 and 0.3 m/s:
9.165 The performance of supply air terminal devices is based on three criteria – throw, spread and drop:
• Throw is defined as perpendicular or parallel distance from the terminal to the point at which the air velocity is 0.5 m/s isovel.
• Ceiling-mounted diffusers with fixed directional vanes that provide a downward turbulent airflow are the preferred option: 600 × 600 four-way blow or circular “air-master” style.
• Spread is defined as the width of the 0.5 m/s isovel.
• Plenum boxes fitted with perforated screens to produce a laminar downflow are also acceptable.
• Drop is defined as the vertical distance from the centre line of the terminal to the bottom edge of the 0.25 m/s isovel.
• Linear ceiling-mounted diffusers that provide a downward-flowing air curtain around the operating theatre may also be used (additional supply terminals may be located within the area bounded by the linear diffusers to provide ventilation within the air-curtained zone).
9.166 It is necessary to consider each of these parameters in both summer and winter conditions to ensure satisfactory operation of the air terminal device, as warm jets behave very differently from cold jets.
9.171 The following terminal types are not suitable for use in operating theatres because they do not produce an appropriate pattern of air distribution:
• swirl diffusers;
• single- or multi-outlet adjustable directional nozzles or jets of any type;
9.167 A warm jet tends to rise until it attaches itself to a horizontal surface, while a cold jet falls. Care should be taken to ensure that this does not lead to unacceptable temperature gradients in winter, or excessive air velocities in the occupied zone in summer.
• sidewall-mounted linear diffusers that utilise the coanda effect to send air across the ceiling and “droop” it into the operating zone.
9.168 In order to ensure satisfactory air movement within a space, it is necessary to consider interaction between air movement from adjacent terminals, and ceiling- mounted fixtures (light fittings, etc), as well as interaction between air movement and room surfaces.
9.169 If the supply and extract terminals are too close, short-circuiting may occur, while if they are too far apart, stagnant zones may be formed. Where two opposing air streams meet, the individual velocities
9.172 Extract terminals should be of an easy-to-clean design and, in order to assist identification when commissioning and subsequently measuring, be of a different design style to the supply terminals. Extract terminals mounted at low level should be of the spring clip retained, pull off face type to enable ease of cleaning. The terminal should be mounted on an angled face to
[HTM 03-01 A – PDF page 112]
cannot be relied upon to permit even quite small airflows. Failure to make adequate provision for air to move from room to room will result in excessive pressure differentials and “door whistle”.
prevent it becoming occluded by movable equipment or stores (see Appendix 9 for examples). Perforated plates are not to be fitted in extract terminals or extract plenums as they quickly become blocked with lint. Extract terminals do not need any directional adjustment so fixed-vane or “egg-crate” styles are preferred.
UCV terminal canopy
9.178 Transfer grilles are required in locations where there is a significant imbalance between the supply and extract rates in a room. They will relieve any pressure differentials which may affect the operation of the spaces and/or the ventilation system and permit airflow in a known direction.
9.173 UCV canopies should be fitted with one or more non-electronic, mechanical, direct reading pressure gauge(s) to indicate the pressure drop across either a representative terminal EPA filter or the pressure in each zone of the canopy.
9.179 Care needs to be taken to ensure that the positioning of transfer grilles does not interfere with the fire or smoke integrity of the building. In general, the air transfer grilles should not be installed within fire- resisting boundaries, although if this is unavoidable, they should be fitted with fire or smoke dampers.
9.174 If a UCV canopy incorporates a method of adjusting the air discharge direction so that the canopy can be “tuned” to the room in which it is installed, the directional adjustment device(s) are to be capable of being locked in position once commissioning is complete to prevent future casual alteration.
9.180 Where installed, transfer grilles should be of the non-vision type, sized for a maximum face velocity of 1.5 m/s.
Cross-talk attenuators may be necessary where noise intrusion between adjacent spaces can arise and where individual room confidentiality is required.
Pressure stabilisers: size and location
9.175 Ceiling-mounted canopy diffusion screen(s) can become contaminated with blood spatter when in use. If the UCV canopy is fitted with perforated diffusion screens the blood spatter can penetrate, so the screens should be capable of being hinged down for cleaning between theatre cases. The screen retaining mechanism will have a double action to release the screen. Mono-filament diffusion screens should be retained by clip-in profiles or an alternative system that allows them to be easily removed when necessary.
9.176 For the validation of UCV terminal canopies, see Chapter 12.
9.181 Pressure stabilisers are required in areas where it is necessary to maintain a pressure differential between adjacent rooms and to prevent reversal of airflows – for example, in operating suites, isolation facilities and clean rooms (see paragraph 8.24).
Transfer grille: size and location
9.177 Air transfer grilles in walls, partitions or doors form an integral part of the building’s air distribution system. Modern door sets have very low leakage rates so
9.182 Fire precautions for pressure stabilisers are the same as for transfer grilles. If the pressure stabiliser is fitted with a fire and smoke damper, the damper test