[HTM 03-01 A – PDF page 48]

6.0 Energy control strategies

6.3 The system should only run at full output when needed to achieve and maintain the defined “in-use” operating condition

6.1 The operation of ventilation systems should be monitored through a building management system (BMS). The basic objective should be to provide the necessary service utilising the minimum energy. To this end, switching a system “Off” when not required is the most energy-efficient policy.

6.4 Care should be taken when specifying plant to discover the true “in-use operating condition”. Overstating the condition will lead to oversized plant, unstable control and excessive energy consumption.

6.2 If the system is needed to maintain a minimum background condition, reducing its output by “Setting back”, to the minimum necessary to achieve and maintain the desired condition, is the next best option.

6.5 The design and selection of set points for an AHU and associated extract system will have a significant impact on the overall energy consumption and efficiency of the system as a whole (see Chapter 9 for detailed information).

Note on “Set back”:

Timed control

6.6 Switch the AHU “On” and “Off” at fixed times using a time clock or BMS programme. The AHU needs to come on early enough in the morning to bring the space up to temperature by the normal start time.

6.7 As above but with an “Optimum start” control that uses the outside temperature to determine the start time. In the winter, the lower the outside temperature, the earlier the AHU starts. In summer, the higher the outside temperature above that desired, the earlier the AHU starts.

In previous times when fan motors only had two speeds, turning the system to “Set back” meant switching to the lower fan speed. With modern fans the speed is widely variable so “Set back” is not a fixed fan speed but rather a control strategy that reduces the system output in order to maintain a desired minimum condition. This may be related to the air velocity at a fixed point, air-change rate, pressure differential, temperature, humidity or a combination of these parameters. Providing a dew- point sensor in an internal space that brings the system on to “Set back” is a simple way of maintaining a minimum condition.

[HTM 03-01 A – PDF page 49]

6.0 Energy control strategies

6.8 As above but link the AHU to a temperature sensor in the space. If out of hours the temperature inside drops to the dew-point, typically 16ºC in winter, or rises above 25ºC in summer, the AHU will start and run at “Set back” (see definition in the Note after paragraph 6.2).

In Ultra Clean Ventilated (UCV) operating theatres the UCV terminal should be linked to the AHU control so that when the AHU goes to “Set back” the UCV also goes to “Set back”, and if the AHU goes “Off”, the UCV terminal fans also switch “Off”. There is no aerobiological benefit in keeping the UCV terminal fans running when the theatre is not in use, it results in wasted energy.

6.9 Any combination of the above or any other appropriate and applicable method that uses the least energy to maintain the specified condition is valid. Various options for the control of single- and multi-zone air-conditioning systems are given in CIBSE Guides F and H.

Occupancy control – user triggered

6.13 An alternative strategy in operating suites is to link the AHU control to the lighting. If the theatre general lights are switched “On” the AHU switches “On” in “Set back” mode. If the main operating lamp is then switched “On” the AHU goes to “Full speed”. If all the lights are out the AHU goes “Off”.

6.10 The ventilation system output should be linked to occupancy detectors. These may take the form of movement, CO2, passive infrared (PIR) or other sensing technologies that can detect that the area served is in use and switch the system “On” or “Off” and/or adjust the ventilation output to suit the actual load.

There are occasions when this approach may need to be used with caution; for example, if a type of surgical procedure requires the operating or general lights to be “Off” during a part of the operation, an override timer or plant extension switch will be needed. The operating department manager and VSG should be consulted for approval before adopting this strategy.

User control

6.11 In intermittently used spaces such as operating suites, movement sensors (for example, PIR or similar) should be installed in the space with a “double knock” program so that if movement is detected twice within 10 minutes the AHU will switch “On” to full speed. If no movement is detected for 30 minutes, the AHU switches “Off”. Double-knock detection prevents the system from switching on in situations where a person has briefly entered a space when it is not in use.

6.12 The above may be combined so that if there is no movement for 15 minutes, the AHU switches to “Set back” (see definition in the Note after paragraph 6.2) during the working day and “Off” outside of normal hours.

6.14 Some applications require intermittent mechanical ventilation, frequently at a high air-change rate (for example, in certain types of treatment room for odour control). Local controls to facilitate this mode of operation if required should be placed in a prominent position to encourage economical use. Specifying timers that shut the system down after a suitable operating period and need to be reset manually will reduce energy waste.

[HTM 03-01 A – PDF page 50]

6.15 Local controls that enable the user to select more than one mode of operation should be clearly labelled to identify the particular mode selected.

above floor level, adjacent to the selector control unit to provide an independent confirmation of the resultant mode of operation. A permanent notice giving a clear description of the selectable modes of operation should be mounted adjacent to the control unit.

6.16 Where the system allows different room pressures to be selected, a direct- reading pressure gauge should be fitted within the eyeline of the users, 1.5 m