[HTM 03-01 A – PDF page 37]

4.0 The design and specification process

pressure quoted is the total or static pressure.

4.71 A new AHU fully compliant with current standards will normally be required. The existing AHU should only be retained if it is not more than 10 years old and is (or can be made) fully compliant with current standards.

4.68 Upon completion of the resistance calculation exercise, the designer should make allowances for calculation and construction tolerances as indicated below:

Total pressure loss margin:

a. for leakage and balancing

requirement = +5%

b. for uncertainties in calculation = +5%

Combined total pressure loss margin = +10%.

The application of the ErP regulations may mean that new plant could be physically larger than that previously installed. If the replacement plant cannot be accommodated in the existing plant space, the plantroom may need to be expanded or a new plant space created. It may be that reconsidering how the ventilation load is determined, whether it can be shared, which type of AHU configuration will fulfill the design need, etc, will provide a satisfactory solution rather than just specifying like- for-like replacement plant.

All installed ductwork whether new or reused should be subject to a leakage test on site prior to the application of any insulation. The leakage test should be to BESA DW144 but with a permissible leakage rate of not greater than 3%.

Refurbishment of existing facilities and fitting out shell schemes

4.72 The most commonly used original standard operating theatre design solutions from previous versions of this HTM have been revised and updated (see Appendix 7). They have been retained in this guidance as they will remain applicable to older theatre suites that are being refurbished within their original footprint. They may also be applicable where a pre-built “shell” is being fitted out.

4.69 When refurbishing existing facilities or fitting out “shell” schemes, every effort should be made to achieve full compliance with this HTM and current Health Building Notes (HBNs).

Change of use of existing facilities

4.73 When a change of use of existing facilities is contemplated, the ventilation requirement should be completely revised to suit the new use (see paragraph 4.63).

4.70 The physical constraints of the building may mean that some derogation in terms of layout and room dimensions are unavoidable, but it is vital that the infection control aspects, clean airflow paths, cascade of air from clean to less clean areas and fire and smoke requirements are not compromised and that the complete facility will be fit for purpose. The VSG should be consulted and agree in writing to any derogations.

4.74 A new AHU fully compliant with current standards will normally be required. The existing AHU should only be retained if it is not more than 10 years old and is (or can be made) fully compliant with current standards.

[HTM 03-01 A – PDF page 38]

Computer-aided design (CAD) and building information modelling (BIM)

4.75 If the ventilation load is to be increased or reduced and the existing system is retained, its output should be adjusted to suit. This will necessitate a recalculation of the heater and cooler loads and resizing of the control valves to match the new loads. It may also necessitate a change in fan size. Failure to carry out this exercise will carry an energy penalty and loss of control function.

4.77 The design of new ventilation systems should be created using a CAD package, and the information generated should be incorporated into the BIM for the project. The client should have access to the BIM model as the project progresses; it will be transferred over to the client on completion (see paragraph 13.28 onwards).

4.76 The area/zone fire strategy should be reassessed to suit the new layout and purpose.

[HTM 03-01 A – PDF page 39]

5.0 Ventilation strategies

5.0 Ventilation strategies

5.1 In order to reduce energy costs and provide a more sustainable healthcare estate and support the declared zero- carbon target, ventilation selection should be as follows:

• first choice – natural ventilation

natural ventilation is limited. Some types of window (for example, vertical sliding) can enhance single-sided air change by temperature difference, and these will improve the overall rate of natural ventilation in protected or sheltered areas where the effect of wind pressure is likely to be minimal.

• second choice – mixed mode ventilation

• final option – mechanical ventilation.

Natural ventilation

5.5 Current healthcare building design philosophy suggests that windows are provided to allow light into and a view out of a healthcare building. Ventilation should be provided by purpose-made openings with appropriate consideration for thermal comfort and air quality. The airflow may need to be controlled by motorised dampers linked to temperature and/or occupancy sensors in the ventilated space.

5.2 Natural ventilation is usually created by the effects of wind pressure. It will also occur if there is a temperature difference between the inside and the outside of a building. The “thermo-convective” effect frequently predominates when the wind speed is low, and will be enhanced if there is a difference in height between inlet and outlet openings.

5.3 Ventilation induced by wind pressures can induce high air-change rates through a building, provided air is allowed to move freely within the space from the windward to the leeward side. However, in most healthcare applications, internal subdivisions will restrict or prevent this effect.

Natural cross-flow ventilation can provide reasonable air distribution for a distance of up to 6 m inwards from the external facade, provided that reasonably clear air paths are maintained. Beyond this distance – in areas where clear air paths cannot be maintained and in areas where high minimum air-change rates are specified – mechanical ventilation should be provided.

5.4 Current guidance restricts the opening of windows for safety reasons; also, as many designs are top-hung, their ability to permit

If natural ventilation is single-sided, it will usually only be effective for a

[HTM 03-01 A – PDF page 40]

ensure a minimum airflow rate while taking advantage of natural ventilation effects when present.

3 m depth within the space. Beyond that it should be supplemented by mixed- mode or mechanical ventilation.

5.11 Where natural or mixed mode ventilation is adopted with complex air paths, the designer should produce an airflow diagram in order to ensure correct provision of air-transfer devices. CIBSE’s Applications Manual AM13 – ‘Mixed mode ventilation’ gives guidance. Modelling of the airflows under a range of conditions should be undertaken to establish the airflow paths.

Mechanical ventilation

Central versus local plant

5.6 With natural ventilation, it is almost impossible to maintain consistent flow rates and ensure that minimum ventilation rates will be achieved at all times. However, this variability is normally acceptable in non-clinical spaces such as office accommodation, staff areas, library/seminar rooms and dining rooms, and some clinical areas such as level 0 and 1 care spaces and waiting and consulting rooms where risk of airborne infections is likely to be low. Where it is essential to achieve a minimum ventilation rate at all times, mixed mode or mechanical methods will be needed.

5.12 Mechanical ventilation is expensive so it should only be provided when the space being served requires close control of its environmental conditions.

5.7 Constraints caused by a building’s shape and/or the functional relationships of specific areas will inevitably result in some measure of deep planning, thus reducing the opportunity for natural ventilation.

5.8 In all cases, for natural ventilation to be effective it will be necessary to take steps to reduce any solar gain to a minimum. Outdoor air-quality, excessive heat gain, indoor air-quality requirements or external noise are all factors that may limit or preclude the use of natural ventilation.

5.9 Further information can be found in Health Building Note 00-10 Part D – ‘Windows’, BS 5925 and CIBSE’s Applications Manual AM10 – ‘Natural ventilation in non-domestic buildings’.

Mixed mode ventilation

5.13 If the ventilation loads throughout a department or building are in phase, or are not significant, a central plant with single zone control may be adopted. However, this is rarely the case, so the condition or quantity of supply air to different areas or zones of the building will be varied accordingly. This may be achieved by either providing individual plant to each zone or providing separate controls for each zone such as provided by a variable air volume (VAV) system. Where there is a high density of rooms with similar ventilation requirements in an area of a building or department, it is usually economical to combine them into a central system; however, the operational resilience should be considered.

5.14 In large buildings, a choice between a small number of large ventilation systems located in centralised plant areas, or a larger number of smaller locally distributed systems, may arise.

5.10 Mixed mode ventilation is an assisted form of natural ventilation. Fans are fitted in purpose-made damper-controlled ventilation openings. Alternatively, a separate draw- or blow-through ventilation unit may be installed. In both cases the dampers and fans are controlled by temperature and occupancy sensors to

[HTM 03-01 A – PDF page 41]

5.0 Ventilation strategies

problems in non-clinical and office areas, but in clinical areas and patient bedrooms, routine access will be a major problem in an operational hospital.

5.19 Chilled beams should not be installed in clinical areas without the agreement in writing of the VSG.

Patient bedrooms are classed as clinical areas as treatment is often delivered at the bedside rather than in a designated treatment room.

5.15 Large distribution systems and their plant can have the advantage of lower capital costs, but because they operate to a fixed supply condition, reheating or cooling may be locally required which will reduce energy efficiency. The distribution system will require more space for vertical shafts. In general, very long runs of ducting should be avoided to prevent undue heat losses or gains, excessive leakage and difficulties in balancing during commissioning. As the pressure losses in the long runs will be greater and a higher initial static pressure will be required, this may lead to a more expensive class of ductwork.

5.20 Where chilled beams are installed in non-clinical areas, they should be positioned to ensure that cold draughts are avoided.

5.16 Decentralised AHUs feeding multiple smaller distribution systems may be more expensive in capital costs but as they avoid long runs, large ducts and vertical shafts, this may reduce overall costs. They can provide a more robust service, as the failure of an individual system does not prevent the use of the rest of the building. Future refurbishment or replacement of AHUs is also simpler. See also Chapters 4 and 9.

Horizontal and vertical AHUs

5.21 In order to avoid condensation on the beam coils and the potential for mould growth, the temperature of the secondary chilled water circuit needs to be kept above dew-point (usually 15ºC). With active beams the supply air may, under some outside air conditions, need to be dehumidified. Manufacturers of these devices can provide specific advice on the design limits and siting of their equipment.

5.17 AHUs may be configured as horizontal or linear units that are single or double- stacked in the case of combined supply and extract units. They may also be configured more compactly as vertical or cabinet-style units. Selection will be dependent on the plant space available and where the unit is to be located. Whichever style is selected, good access for service and maintenance is essential. See legal requirements in paragraphs 3.6 and 3.10.

5.22 Where chilled beams are installed in rooms with opening windows, the window should be fitted with a switch to automatically turn off the beam when the window is open. To avoid condensation, chilled beams should not be installed in entry lobbies that directly connect to the outdoors.

Chilled beams

5.23 Active and passive chilled beams require regular cleaning if they are to remain efficient. They should be of a design that allows full access to the beam coils for cleaning and be positioned where they will be accessible for maintenance and not installed above fixed items of equipment.

5.18 Active chilled beams can provide an energy-efficient means of controlling environmental conditions. They are, however, subject to increased maintenance requirements due to the need for regular cleaning if they are to remain working efficiently. Access for this will not pose

[HTM 03-01 A – PDF page 42]

or 10 L/s/person − whichever is the greatest − should be provided.

5.24 There is no benefit in installing chilled beams if the resources to keep them in efficient working order over their entire life cycle will not be available. The maintenance aspects of using chilled beams should be discussed and the decision to use them agreed in writing with the client.

5.28 Whether single or multiple systems are used, it is essential that the designer give due consideration to the source of electrical supply, location of the heat rejection unit, environmental effects and flammability of the refrigerant used, and drainage provision for the cooling-coil condensate.

Maintenance access to chilled beams will require the use of pulpit steps or wheel- around access equipment. The use of such equipment in a working hospital is very restricted.

Stand-alone air-conditioners

5.29 Stand-alone air conditioners require regular cleaning if they are to remain efficient and not become a source of airborne bio-hazards. If they incorporate an open water drainage system, they must be risk assessed under L8/HSG274 as part of the Legionella assessment (see the Health & Safety Executive’s (HSE) Approved Code of Practice and guidance document HSG274 ‘Legionnaires’ disease: the control of Legionella bacteria in water systems’). They should be easily accessible for maintenance and should not be installed above fixed items of equipment which would make access difficult.

5.25 Stand-alone air conditioners include fan coil units, split-comfort air-conditioners, room conditioners and cassette units. All of these devices recirculate air which affects indoor air quality and may increase the risk of healthcare-associated infections (HAIs). Therefore they should not be installed in clinical areas.

Notes:

Patient bedrooms are classed as clinical areas as treatment is often delivered at the bedside rather than in a designated treatment room.

1. Maintenance access to stand-alone air-conditioners will require the use of pulpit steps or wheel-around access equipment. The use of such equipment in a working hospital is very restricted.

5.26 Stand-alone air conditioners may be installed in suitable non-clinical areas, but they should be positioned to ensure that cold draughts are avoided. The control settings should ensure that the external elements of the units are always above dew-point. Manufacturers of these devices can provide specific advice on the siting and design limits of their equipment.

2. Traditional refrigerants are being phased down because of their effects on the environment and are becoming ever more expensive. Their replacements at the time of writing have a degree of flammability. Both these factors pose serious consideration as to whether stand-alone air-conditioners are suitable devices to choose. In scanning and control equipment rooms, the use of chilled racks, shelves and embedded panels supplied with water above dew- point would be a more suitable option.

5.27 Stand-alone air-conditioners recirculate air, therefore, a primary fresh air supply of at least 20% of the room air-change rate, or that required by the Building Regulations,

[HTM 03-01 A – PDF page 43]

5.0 Ventilation strategies

System selection

5.33 Where the ventilation system is not merely tempering the air, but also providing the heating and/or cooling requirements (air-conditioning) the following additional factors should be considered:

• internal or peripheral location;

• orientation of windows;

5.30 Natural ventilation is always the preferred solution for a space, provided that the quantity and quality of air required, and consistency of control to suit the requirements of the space, are achievable. If this is not the case, mixed mode or a mechanical ventilation system will be required.

• variation of internal loads;

• level of control required.

5.31 Ventilation costs can be minimised by ensuring that, where practicable, core areas are reserved for those rooms that need to have mechanical ventilation. Examples are:

• sanitary facilities, dirty utilities and those rooms where clinical or functional requirements have specific environmental needs; and

5.34 For single-zone plant in staff areas, local control (with a run-on-timer if required) is recommended, as the system can be turned off when the space is not in use, thus saving both thermal and electrical energy. Most clinical-zone supply and extract systems, conversely, are required to operate continuously while the department is occupied; thus some form of time or use control is necessary.

• those rooms where – for reasons of privacy, absence of solar gain, etc – windowless accommodation is acceptable.

5.35 The control of individual plant items is covered in Chapter 9, with examples of typical control strategies in Chapters 6 and 7. For control parameters of particular critical ventilation and air-conditioning systems, see Chapter 8.

• Other spaces appropriate to core areas are those which have only transient occupation and therefore require little or no mechanical ventilation (for example, circulation and storage areas).

Zoning of the building

5.36 On rare occasions a duplicate standby air-handling plant may be justified. If installed, it should be provided with a gas-tight damper (see BS EN 1751) at its junction with the supply distribution duct so that no back-flow can occur. Standby plant can become sources of contamination if warm, moist air is allowed to dwell within them. Their design and control system should ensure that this cannot happen.

5.32 The efficiency and effectiveness of any ventilation or air-conditioning installation depends largely on the zoning and control of the installation. The factors to consider when determining the zoning of a ventilation system for a building or department are:

• periods of occupancy;

• the service delivery resilience;

The presence of duplicate plant should be reflected in the fire strategy.

• fresh-air/ventilation requirements;

• the fire and smoke control strategy for the area.

[HTM 03-01 A – PDF page 44]

Fire and smoke control

Local exhaust ventilation

5.40 There is a statutory requirement under the COSHH regulations to prevent or control the escape of chemicals, toxic fumes, biological materials or quantities of dust into the general environment. For airborne hazards to people, control may be by the provision of an LEV system designed to the standard set out in HSG 258.

5.37 Within a designated departmental fire zone, the total mechanical supply and extract ventilation volumes should be approximately equal so that in the event of a fire, smoke is neither drawn into nor blown out of the zone. Note that individual sub-zones within the departmental zone may be positively or negatively pressured to suit the clinical need (for example, isolation rooms, operating theatres).

Ventilation for general areas

5.41 Chapter 8 and Appendix 2 provide recommended air-change rates, temperatures and pressures for general areas requiring mechanical ventilation in healthcare buildings.

Mechanical extract ventilation

5.42 General extract systems can vary in complexity from a single wall-mounted fan to a central ducted air system with dual extract fans.

In atria, stairwells and designated escape routes, dedicated smoke clearance fans may be installed to keep evacuation routes clear in the event of a fire. These together with their associated smoke dampers do not form part of the building’s general ventilation system and their operation will be automatically initiated by the building’s fire detection system and/or manually controlled by fire service personnel (see Health Technical Memorandum 05 Firecode).

Air-conditioning

5.43 Replacement air is provided by either a central supply system or enters the building through gaps in the structure or purpose- made openings. The design should ensure that the latter does not result in an unacceptable level of draughts occurring in winter.

5.38 Air-conditioning is the facility to filter, heat, cool, dehumidify and if required humidify the supply air to maintain an internal condition regardless of changes in the external conditions or internal load. It is expensive in plant and energy.

5.44 If individual systems are used, the ventilation can be operated intermittently, provided it continues to run for at least 15 minutes after the room is vacated (as with light-switch-operated fans in individual toilets).

5.39 Due to capital and running costs, air-conditioning should only be used in essential areas. These include operating departments, critical care areas, manufacturing pharmacies and areas with particularly sensitive equipment. Information on system performance requirements for individual departments is given in Chapter 8.

5.45 If general exhaust systems are used, filtered and tempered replacement air should be provided to adjoining lobbies or corridors, to prevent the risk of discomfort caused by the ingress of cold air. Fire compartmentation requirements should be maintained.

5.46 Information on specialised extract systems is given in Chapters 8 and 9.

[HTM 03-01 A – PDF page 45]

5.0 Ventilation strategies

Infectious diseases units and bronchoscopy rooms are similar.

Mechanical tempered-air-supply systems

Recirculation systems

5.47 Where mechanical supply systems are required, the fresh air should be tempered and filtered before being delivered to the space in order to avoid discomfort.

5.53 Air recirculation systems are normally used in HEPA-filtered clean rooms where the return air is significantly cleaner than the outside supply and where odour levels are not significant.

5.48 The majority of space air temperature heating load will be provided by the energy-recovery device with the balance from a constant or variable temperature battery. In most instances, the low pressure hot water (LPHW) heating system should offset any fabric loss so that set-back room temperatures can be maintained during unoccupied periods without the need for the ventilation system to operate.

5.54 Recirculation is also routinely used in the canopy section of ultra-clean operating theatre ventilation systems (UCV). The recirculated air is EPA filtered to ensure that biological contaminants released by the surgical team are not discharged back into the clean zone.

Balanced ventilation

5.55 Recirculation may also be used for swimming and hydrotherapy pool ventilation.

5.56 Where the designer is considering the installation of an air recirculation system, due account should be taken of:

5.49 A balanced ventilation system is a combination of both a supply and an extract system of equal volume; either a single space or a whole building may be considered to be balanced.

• a 20% minimum fresh air supply volume or that required by the Building Regulations or 10 L/s/person, whichever is the greatest;

5.50 A balanced system is necessary in instances where it is essential to maintain consistent air movement within an area (for example, recovery rooms).

Cascade ventilation

• prevention of supply air contamination from vitiated return air;

• prevention of stratification occurring within plenum chambers and mixing boxes, which may result in freezing of downstream coils;

5.51 In operating departments, it is normal practice to supply air to the operating theatre and allow it to flow through less clean areas – corridors, utility rooms, etc (from where it is eventually extracted). Pharmacy aseptic preparation facilities, maternity delivery rooms and treatment rooms are similar.

• ensuring sufficient velocities through automatic control dampers (ideally 5–6 m/s) where fitted, to provide suitable authority and good shut-off;

• modulating control of mixing to provide optimum on-plant conditions;

5.52 In negative pressure facilities it will be necessary to provide make-up air in order to promote the correct pressure cascade from the clean to the less clean (for example, supply in an outer area – to lobby – to patient’s room – to toilet extract).

• the use of “free cooling” by cycling the dampers to minimum fresh air when the enthalpy of the outside air

[HTM 03-01 A – PDF page 46]

is greater than that of the extract air under conditions when cooling is required.

Note

an additional safeguard. This approach ensures that regarding the ventilation aspects, “all reasonable steps are taken to prevent or control exposure (of staff) to the hazardous substance” as required by COSHH.

Recirculating air can create particular problems when its ductwork breaches fire compartmentation. Designers should ensure that the system complies with the fire strategy in all modes of operation.

In these areas the supply air should be 100% fresh and not recirculated.

Dilution ventilation and clean airflow paths

5.60 In operating theatres, patients will be on a closed breathing circuit in a room with a high air-change rate. Under these circumstances, the dilution effect would be considered sufficient to control any casual exposure of staff to anaesthetic gases.

Displacement ventilation

5.57 In the past dilution ventilation has been used as the sole means of controlling levels of airborne hazardous substances in a space. This approach in itself is no longer considered acceptable. COSHH requires that airborne hazardous substances should be controlled at source by using a closed system (such as an anaesthetic gas scavenging unit) or a protective enclosure (such as a fume cupboard). A good level of background ventilation will assist in diluting any casual release of the substance.

5.61 Displacement ventilation introduces air at low level and removes it at high level. It uses the natural thermal buoyancy resulting from heat gain to achieve air movement throughout a space with minimal or no energy input. Displacement ventilation can be natural, mixed mode or mechanical with the supply untreated, tempered or fully conditioned depending on the application.

5.58 In anaesthetic rooms, the casual exposure of staff to leakage or spillage when administering anaesthetic agents should be dealt with by establishing a clean airflow path. Air should be supplied at high level above or behind the area where the staff will typically stand and extracted at low level directly behind the anaesthetic equipment position (see Figure A8 and photographs in Appendix 9).

5.62 Displacement ventilation can be very energy-efficient and works well in applications that have significant casual heat gains from solar effects, people or equipment. Typical applications in a healthcare setting would be the ventilation of atria, central dining rooms, main kitchens, hydrotherapy pools, computer server rooms, lecture theatres and open- plan waiting or office areas. It is also applicable to non-interventional imaging and scanning suites where there are significant equipment-generated casual gains but no aerobiological infection risks.

5.59 The philosophy of establishing a clean airflow path – from the air-supply point, past the breathing zone of the staff, on to the patient or other source of airborne hazard, and out via a low-level extract – would also apply in recovery rooms, birthing rooms, bronchoscopy rooms, laboratories and post-mortem rooms. A suitable air-change rate (see Chapter 8) will provide background dilution ventilation as

5.63 Supply terminals will be located at low level, usually in the form of large perforated plate style diffusers mounted

[HTM 03-01 A – PDF page 47]

5.0 Ventilation strategies

them. Extract will be at high level through vents or by a ducted extract system. The ventilation rate may be controlled by temperature or CO2 sensor-initiated motorised dampers with or without fan assistance at the extract points. The supply air volume is then slaved to match.

vertically. The supply air terminal face velocity is low so that it does not create draughts. It is essential that they are located in several positions so that they can ventilate the entire space. Care should be taken to ensure that fixed or movable equipment and devices cannot obstruct