3.0 Legal requirements – applicable legislation

3.0 Legal requirements – applicable legislation

Health and Safety at Work etc Act

protect their staff and others affected by the work activity. These methods may include both safe systems of work and the provision of a specialised ventilation system. In laboratories the requirements are often met by the provision of fume cupboards and microbiological safety cabinets.

3.1 The Health and Safety at Work etc Act 1974 is the core legislation that applies to ventilation installations. As these installations are intended to prevent contamination, closely control the environment, dilute contaminants or contain hazards, their very presence indicates that potential risks to health have been identified.

3.4 Where specialised ventilation plant is provided as part of the control measures, there is a statutory requirement that it be correctly designed, installed, commissioned, operated and maintained. The local exhaust ventilation (LEV) section of COSHH requires that the system be examined and tested at least every 14 months by a competent person (P601 certified) and that management maintain comprehensive records of its performance, repair and maintenance.

3.2 The Act places a duty of care on ALL to provide and maintain a safe workplace. This includes designers and suppliers of goods or services. Those trading as competent designers or suppliers are therefore liable to provide outcomes that meet the client’s needs and are without hazard to staff, patients and others who may be affected by the work activity.

Control of Substances Hazardous to Health Regulations

3.5 Certain substances have workplace exposure limits (WELs) as set out in the Health and Safety Executive’s (2005) Guidance Note EH40 – ‘Workplace exposure limits’. This contains the list of workplace exposure limits for use with the Control of Substances Hazardous to Health Regulations 2002 (as amended). If specialised ventilation systems are provided in order to achieve these standards, they will be subject to the COSHH Regulations.

3.3 The Control of Substances Hazardous to Health (COSHH) Regulations 2002 place upon management an obligation to ensure that control measures are in place to

[HTM 03-01 A – PDF page 26]

Workplace (Health, Safety and Welfare) Regulations

risk of, and prevent, detect and control the spread of, infections, including those that are healthcare associated.

3.6 These state that:

• All enclosed workplaces must be ventilated by natural or artificial means.

3.9 Appropriate standards of cleanliness and hygiene should be maintained in premises used for the regulated activity. DH (2015) issued ‘The Health and Social Care Act 2008 Code of Practice on the prevention and control of infections and related guidance’ (the HCAI Code of Practice), which contains statutory guidance about compliance with regulation 12(2)(h).

• Any plant provided under this legislation must include an effective device to give an audible or visual warning of plant failure where necessary for health and safety.

3.10 Regulation 15 of the Act states that:

(1) All premises and equipment used by the

service provider must be:

• The Regulations require that ventilation systems are maintained in an efficient state, in efficient working order and in good repair.

a. clean,

b. secure,

The Building Regulations

3.7 Approved documents L and F:

c. suitable for the purpose for which

they are being used,

• apply to domestic and non-domestic buildings;

d. properly used

e. properly maintained, and

f. appropriately located for the purpose

• clarify satisfactory methods of providing ventilation and give ventilation rates;

for which they are being used.

• set minimum standards for:

(2) The registered person must, in relation

– the protection of the supply position

– precautions against Legionella

to such premises and equipment, maintain standards of hygiene appropriate for the purposes for which they are being used.

– the purity of recirculated air

– access for service and maintenance

– documentation and proof of performance

– energy performance.

The “registered person” means, in respect of a regulated activity, the person who is the service provider or a registered manager in respect of that activity. A “service provider” means a person registered with the CQC under Chapter 2 of Part 1 of the Health and Social Care Act 2008 as a service provider in respect of that regulated activity.

Health and Social Care Act 2008 (Regulated Activities) Regulations 2014

3.8 Regulation 12(2)(h) of the Act decrees that registered providers must assess the