HTM 03-01 A: _Hlk37000395 – Palliative care
[HTM 03-01 A – PDF page 23]
2.0 The user requirements
Palliative care
to the microorganisms present and fumes from the preservative.
2.20 Staff who section organs and prepare specimens for analysis may be exposed to the microorganisms present and the chemicals used for staining and fixing the specimens.
2.14 The main requirement is to ensure that staff and patients are kept in comfortable conditions. Temperature control may be more stringent for patients with long-term and/or end of life conditions (see the Executive Summary for further information).
2.15 Difficulties with evacuating patients in the event of fire may need to be considered.
2.21 In both of the above situations local exhaust ventilation (LEV) in the form of downflow benches, safety cabinets and fume cupboards need to be provided to control the risk.
Pharmacy
Diagnostic and support services
Imaging and Interventional imaging
2.22 Exposure to the active ingredients of drugs represents a hazard to pharmacy staff who are involved in their production. These activities are carried out in an aseptic preparation facility to ensure that the drugs themselves are not contaminated. The actual production typically takes place inside an isolator so that there is a physical barrier between the hazard and the operator.
2.16 There are major advances in diagnosis and minimally invasive treatment involving imaging. It may be necessary during these invasive or non-invasive procedures to provide sedation or general anaesthesia to help with anxiety or pain. This may involve the use of inhaled anaesthetic agents and/ or nitrous oxide (N2O). Staff working in these areas may be exposed to these anaesthetic agents when they are administered or subsequently when they are exhaled as the patient is recovered.
2.23 Alcohol sprays are used and staff exposure may be controlled by the provision of downflow LEV systems to remove the hazard.
2.17 A similar situation occurs in maternity units, where a mixture of nitrous oxide and oxygen (N2O/O2) (Entonox) is used as an inhaled analgesic.
2.24 Comfortable conditions are essential for staff working in preparation facilities as they need to be fully gowned, and entry and exit is restrictive.
Decontamination facilities
2.18 In both of the above cases ventilation should be designed to provide a clean airflow path and dilute any casual spillages of the gas. This approach will help control the casual exposure of staff to the anaesthetic agent (see paragraphs 3.3–3.5).
Post-mortem and pathology
2.25 Staff may be exposed to airborne biological material and chemicals when handling and processing used scopes, surgical instruments and equipment as part of the decontamination process. The ventilation should provide a clean airflow path to control staff exposure.
2.19 Staff who harvest organs and specimens at a post-mortem and place them into preservative solutions may be exposed
[HTM 03-01 A – PDF page 24]
Estates and facilities
2.26 Staff may be engaged in welding, soldering, machining wood or paint- spraying. They may also decant chemicals in quantity (for example, for boiler treatment or hydrotherapy-pool dosage). LEV systems are routinely used to control the hazards arising.