[HTM 03-01 A – PDF page 17]

1.0 Introduction

1.0 Introduction

1.4 Ventilation may also be installed:

The needs of the building occupants

• to ensure compliance with the quality assurance requirements of items processed in pharmacies and sterile services departments;

• to protect staff from airborne microorganisms and toxic substances (for example, in laboratories and anaesthetic rooms);

1.1 Ventilation is used extensively in all types of healthcare premises to provide a safe and comfortable environment for patients and staff and control odours. More specialised ventilation is provided to help reduce airborne infection risks in areas such as operating departments, critical care facilities, isolation rooms and primary patient treatment areas.

• to contain the spread of smoke between fire compartments as part of the fire strategy.

1.5 Healthcare buildings are continuously occupied, intensively used and because of the specialised nature of the facilities it may be extremely difficult to provide the service elsewhere if the ventilation fails. In order to ensure continuity of service, ventilation systems should be designed and installed so that they can be quickly and easily maintained. The resilience of the proposed system in the event of service outage should also be considered.

1.2 The Health and Social Care Act places a duty of care on healthcare providers. Increased health risks to patients will occur if ventilation systems do not achieve and maintain the required standards. The link between surgical site infection and theatre air quality has been well established. If the ventilation plant has been installed to dilute or contain harmful substances, its failure may expose people to unacceptable levels of risk. Proven breaches of the statutory requirements can result in prosecution and may also give rise to a civil suit against the operators.

The building environment

1.3 Healthcare buildings are visited and used by large numbers of people. Many will be unwell or anxious so a well-ventilated environment with a fresh feel and an absence of noxious odours is essential.

1.6 The ventilation of healthcare facilities consumes a significant portion of their energy load, so wherever possible natural ventilation is the preferred option. Where mechanical ventilation is used, sustainable design concepts allied to good-quality installation and the provision of controls that maintain the desired environment when the facility is in use will result in the

[HTM 03-01 A – PDF page 18]

minimum energy input for the maximum benefit.

Substances Hazardous to Health Regulations (COSHH) (for example, woodworking dust, welding fumes, chemical vapours).

Airborne risks to staff

1.8 A well-designed ventilation system can mitigate the airborne risks to staff. It should:

• supply sufficient unvitiated air to dilute the possible contaminants;

1.7 Most healthcare staff are no more at risk from airborne hazards when at their workplace than they are when not in a healthcare environment; however, certain groups as detailed below may be exposed to a variety of airborne contaminants.

• have air terminals located to efficiently scour the ventilated space;

• move the air from the clean to the less clean space and/or out of the building;

• Staff who administer anaesthetic agents or who work in areas where they are routinely used will be at risk of casual exposure to these agents.

• supply the air at high level and remove it at low level so that the breathing zone of staff is in a clean airflow path.

• Staff who routinely work in areas where they may come into close contact with patients who have respiratory symptoms will be at risk of exposure to the microorganisms causing the symptoms.

• Staff who routinely work in areas where they may come into close contact with patients that have skin lesions, an infectious disease or a dermatological condition will be at risk of exposure to the microorganisms causing the condition.

1.9 Adoption of these principles will be sufficient to control the general risk to the staff identified above in their particular working environment. More specific airborne hazards should be captured at source and removed by local exhaust ventilation (LEV) systems provided under the COSHH Regulations (see paragraphs 3.3–3.5).

• Staff who routinely process pathology specimens.

Airborne risks to patients

• Staff who decant, mix and/or process chemicals used as reagents for the setting or processing of pathology specimens.

1.10 In general terms an environment that is satisfactory for staff will be satisfactory for patients. There are, however, exceptions as below:

• intensive treatment units of any type;

• Staff who harvest organs, tissues and specimens at a post-mortem.

• haematology/oncology units;

• Staff who handle drugs or the components of drugs.

• transplant units and units treating patients that have had their immune system compromised;

• bone marrow transplant units (BMT);

• Staff who pre-clean used scopes, surgical instruments and equipment prior to decontamination.

• burns units;

• cystic fibrosis units;

• Staff who may be routinely exposed to airborne hazards listed in EH40 issued under the Control of