[HTM 03-01 A – PDF page 19]

1.0 Introduction

• operating theatres.

Specialist equipment environment

Patients being treated in these areas will need an environment supplied with good- quality filtered air and that is maintained at a positive pressure with respect to surrounding areas.

1.13 Imaging and other non-invasive scanning equipment will require stable environmental conditions to stay within calibration and provide accurate repeatable results. Health Building Note 06-01 and Health Building Note 10 (2021) give detailed guidance and the equipment manufacturers should be consulted.

Health Building Note 26 – ‘Facilities for surgical procedures’ (2004) and Health Building Note 10-02 – ‘Facilities for day surgery units’ (2007) are under revision at the time of writing and will become Health Building Note 10-01 once updated.

Patients who are particularly at risk from airborne microorganisms will normally be placed in an isolation room or suite that is maintained at a positive pressure. Patients who have a condition that could be transmitted to others are normally placed in a negative pressure isolation suite. When the patient’s exact condition is unknown they may be placed in a neutral pressure (PPVL) isolation suite (see Health Building Note 04-01 Supplement 1 – ‘Isolation facilities for infectious patients in acute settings’ for detailed guidance).

Health Building Note 06-01 (2001) on diagnostic imaging and interventional radiology is also under revision at the time of writing.

Medicinal products environment

1.11 A more general airborne risk will result from poorly designed and constructed air handling units (AHUs) that allow water to stagnate inside; they can then become a source of microorganisms such as Legionella. If their intake is badly sited or housekeeping in the area is poor, fungal spores such as aspergillus can be drawn in. The ventilation system will then become a means of spreading these microorganisms and fungal spores around the healthcare building.

1.14 Pharmacists are required to ensure that any manufacture or preparation activities involving medicinal products undertaken in their units conform with the requirements of the Medicine Act. Processes must be carried out in a suitable facility usually termed an aseptic preparation facility. The quality of air supply and design of the ventilation cascade are essential to ensure a suitable environment for the activities undertaken.

1.12 All ventilation systems should conform to the principles set out in the Health and Safety Executive’s (HSE) Approved Code of Practice and guidance document HSG274 ‘Legionnaires’ disease: the control of Legionella bacteria in water systems’ and Health Technical Memorandum 04-01 – ‘Safe water in healthcare premises’.

Fire and smoke control fundamentals

1.15 Health Technical Memorandum 05 is the base document for fire aspects. When designing a ventilation system, a fire and

[HTM 03-01 A – PDF page 20]

the design and installation of a system is not reduced during the subsequent operation and maintenance of the equipment.

smoke control strategy should be developed that is relevant to the site and its function. The fire and smoke strategy should take account of the planned activity within the area, the type of patient present, staff-to- patient ratio and treatment being delivered (see also Chapters 5 and 7).

1.20 The number and location of fire and smoke dampers can be problematic. Fire- rated ductwork within fire zones will reduce the need for fire and smoke dampers. It will eliminate the need to provide access for routine damper testing and the infection control problems associate with reversed airflow paths resulting from damper failures and nuisance tripping (see also Chapter 7 for ventilation control in the event of fire).

1.16 When ventilation systems are originally designed, they will conform to an agreed fire strategy. This will determine the compartmentation, provision of fire-rated ductwork, fitting of sprinklers, the siting of fire and smoke dampers and an agreed control action for the ventilation in the event of a fire. The agreed fire and smoke control strategy must be clearly set out as part of the design specification.

1.17 The fire regulations require that, if ventilation ductwork penetrates the fabric of a building, it should be designed and installed to contain the spread of fire (see Health Technical Memorandum 05-02 – ‘Guidance in support of functional provisions for healthcare premises’ for further guidance).

1.18 If a ventilation system is upgraded or altered to suit a change of use, it will be necessary to reassess the fire strategy.

In developing a fire and smoke containment strategy the design of ventilation for infection control cannot be ignored. Over-compartmentation and poorly chosen fire lines can prevent air moving from clean to less clean areas and thus increase the infection risk. This can be a particular problem in operating departments where the desire to create a protected escape route can be at odds with the need to cascade air through a suite of rooms and out into a corridor in order to control the airborne infection risk.

1.19 It is management’s responsibility to ensure that the fire strategy applied during