[SHTM 81 part 1 – PDF page 36]

25. Lightning protection

The need for a lightning protection system should be assessed taking into account the guidance contained within BS EN 62305-1: Protection against lightning.

Where a lightning protection system is installed, surge protection should be provided to all safety services in accordance with BS 7671: Requirements for electrical installations.

[SHTM 81 part 1 – PDF page 37]

26. Electrical vehicle charging points

Consideration should be given to designated charging areas for cars, large mobile battery-operated equipment such as forklift trucks or patient, staff and visitor mobility scooters.

Internal charging points for electric vehicles and equipment should be located in a fire hazard room.

External charging points should normally be sited at least three metres from the building. However, the final location should always be subject to completion of a fire risk assessment that takes account of the following risk factors:

the type of external wall cladding;

the construction of any canopy to determine if it will contribute to fire spread if ignited;

the likelihood and effect of fire and smoke entering windows or other openings;

the number of vehicles being charged and their proximity to each other with regard to fire spread from one vehicle to another;

the means of identifying a fire in the charging location and the time it would take to give warning to building occupants.

Electric vehicle charging points should be provided with:

clear and prominent notices at each charging point to indicate what equipment or vehicle it is suitable for;

suitable instruction to demonstrate the means for isolating the power;

suitable signage to show the action that should be taking to raise the alarm in the event of fire and to notify the Fire and Rescue Service.

Where charging points are proposed for multi storey carparks, consideration should be given to locating them in open air, on the upper deck to minimise the potential for fire spread.