27. Commissioning and handover

It is essential that, fire safety is an integral consideration, during the commissioning and hand over phases of any project.

As previously stated, NHS Scotland Bodies commissioning new healthcare premises, extensions or structural refurbishments to existing facilities, should ensure that, at the earliest stage of the design process, there is close collaboration between all parties.

The Fire Safety (Scotland) Regulations, section 21 co-operation and co-ordination, outlines statutory duties in relation to jointly owned or occupied premises, it sets out a requirement to consult with others and share fire safety information to ensure that arrangements are properly co-ordinated and implemented.

Key organisational roles and functions should be established to ensure a safe transition from the initial concept design, through the build stage to an operational facility.

The Health Boards Nominated Officer (fire) should ensure:

fire safety procedures are established and relayed to all NHS Staff and others who work within the premises, immediately upon, or prior to occupation;

fire safety induction training and familiarisation is scheduled to take place at the commencement of employment of new staff, ref - SHTM 83 part 2: Fire Safety Training;

fire safety induction training and familiarisation is scheduled for existing employees taking up employment in new premises ref - SHTM 83 part 2: Fire Safety Training;

a pre occupation fire safety risk assessment is undertaken;

an Emergency Fire Action Plan (EFAP) has been established and is available to all NHS Staff and others who work within the premises;

ongoing snagging works do not compromise occupant safety;

fire safety systems are tested individually to ensure they conform to the agreed design specification and are functioning correctly;

fire safety systems are tested collectively to ensure that they are fully integrated.

Commissioning and test certification documentation, including product installation and use, routine testing requirements and performance information, should be retained as a permanent reference record of the installed components.

[SHTM 81 part 1 – PDF page 39]

Appendix 1: Glossary of terms

Active fire precautions: installed fire safety systems.

Addressable fire alarm system: system in which signals from each fire detector and/or fire alarm manual call point are individually identified at the fire alarm control and indicating equipment.

ARC (alarm receiving centre): centralised control room for the automatic receipt of a fire alarm signals, and the onward transmission of the received information to the Fire and Rescue Service.

ASET (available safe egress time): calculated time available between ignition and the time at which tenability criteria are exceeded in a specified space in a building.

CEL (Chief Executive Letter): letter circulated by the Scottish Government. Health Directorates to the Chief Executives of Health Boards, usually to introduce a policy directive or mandate specific course of action.

DL: A letter circulated by the Scottish Government. Health Directorates to the Chief Executives of Health Boards.

Cavity barrier: any construction provided to seal a cavity against the penetration of fire and smoke, or to restrict its movement within the cavity.

Compartment floor: floor with the fire resistance required to ensure compartmentation. Defined in the technical handbook non-domestic annex 2D table 2.19.

Compartment wall: wall with the fire resistance required to ensure compartmentation. Defined in the technical handbook non-domestic annex 2D table 2.19.

Compartmentation: division of a building into fire compartments intended to contain a fire within the compartment of fire origin.

Duct: the structure, trunking, or casing, with any apertures, enclosing a passage, other than a flue, used solely for conveying air, gases, or refuse.

Emergency Fire Action Plan (EFAP): written document detailing the actions to be taken in the event of a fire.

Escape route: means a route by which a person may reach a place of safety.

Escape stair: means a stair forming part of an escape route.

Exit: means a point of egress from a room, storey, protected zone, space, gallery, catwalk or openwork floor that forms part of, or gives access to, an escape route or place of safety.

External wall: includes a part of a roof pitched at an angle of 70º or more to the horizontal.

[SHTM 81 part 1 – PDF page 40]

Firecode: Scottish Health Technical Memorandums relating to fire safety.

Fire detection and alarm systems: alerts occupants of fire incident.

Fire hazard: a set of conditions with the potential for initiating a fire.

Fire hazard room: room enclosed with fire resistant construction.

Fire hazard department: department enclosed with fire resistant construction.

Fire precautions: measures to reduce the likelihood of a fire occurring and to mitigate the consequences should fire occur.

Fire resistance duration: defined in the technical handbook non-domestic annex 2D table 2.19.

Ground storey: means the storey of a building in which there is situated an entrance to the building from the level of the adjoining ground, or, if there is more than one such storey, the lower or lowest of these.

Hospital: healthcare premises with bed – patient facilities.

Hospital Street: protected zone in a hospital provided to assist in facilitating circulation and horizontal evacuation, and to provide a fire-fighting bridgehead.

Intumescent: material with the property of swelling or foaming when exposed to heat, which is designed to maintain the integrity of a fire separating element at the position where services pass through.

Long fire resistance duration: defined in the technical handbook non-domestic annex 2D table 2.19.

Medium fire resistance duration: defined in the technical handbook non-domestic annex 2D table 2.19.

Non-combustible: material that does not contribute to fire growth (European fire classification A1 and A2.).

Passive fire precautions: the structural fire safety elements of a building.

Place of relative safety: - place in which there is no immediate danger from fire, e.g. adjacent compartment.

Place of safety: place outside of the building at a safe distance from the effects of fire and smoke.

Protected enclosure: enclosure separated from adjoining accommodation spaces by fire resistant construction.

Protected lobby: lobby within a protected zone but separated from the remainder of the protected zone.

Protected route: route designated for use as an escape route, which is separated from the remainder of the building by fire resistant construction.

[SHTM 81 part 1 – PDF page 41]

Protected shaft: shaft that is enclosed with fire resistant construction.

Protected stairway: stairway that is enclosed with fire resistant construction.

Protected zone: part of an escape route which is within a building, but not within a room, and to which access is only by way of a protected door and from which there is an exit directly to a place of safety.

Progressive horizontal evacuation (PHE): a systematic process of moving patients away from the area affected by fire to an adjoining compartment or sub compartment on the same level, where the occupants are protected from the immediate dangers of fire and smoke.

Roof space: means any space in a building between a part of the roof and the ceiling below.

Room: means any enclosed part of a storey intended for human occupation or, where no part of any such storey is so enclosed, the whole of that storey, but excepting in either case any part used solely as a bathroom, shower room, washroom, toilet, and stair or circulation area.

Self-closing door: fire and smoke door that closes automatically from all angles of swing.

SHTM: Scottish Health Technical Memorandum.

Short fire resistance duration: defined in the technical handbook non-domestic annex 2D table 2.19.

SFPN: Scottish Fire Practice Note.

Separating floor and separating wall: floor or wall constructed to prevent the spread of fire between buildings or parts of a building.

Service opening: means any opening to accommodate a duct, pipe, conduit or cable (including fibre optics or similar tubing).

Storey: part of a building which is situated between the top of any floor being the lowest floor level within the storey, and the top of the floor next above it being the highest floor level within the storey or, if there is no floor above it, between the top of the floor and the ceiling above it or, if there is no ceiling above it, the internal surface of the roof; and for this purpose a gallery or catwalk, or an openwork floor or storage racking, shall be considered to be part of the storey in which it is situated.

Sub-compartment: part of a building (which may contain one or more rooms, and includes, where relevant, the space above the top storey of the sub-compartment) constructed to aid horizontal evacuation.

Sub-compartment wall: a wall with the specified fire resistance, Defined in the technical handbook non-domestic annex 2D table 2.19.

[SHTM 81 part 1 – PDF page 42]

Temporary waiting space/refuges: are places of relative safety where persons with restricted mobility have access to a communication facility, whereby, they can call upon staff to assist them with their ongoing evacuation.

technical handbook non-domestic: the Building Standards technical handbook non- domestic provides guidance on achieving standards set in the Building (Scotland) Regulations.

Unprotected zone: any part of an escape route, which is separated by walls, glazed screens or any other permanent form of demarcation from any space intended for human occupation, including a protected zone.

Upper storey: any storey that is above the level of the ground storey.