Home › Scotland (NHS Scotland Assure / HFS) › SHTM 81 part 1 › 17. Portable fire-fighting equipment / 18. Fire and rescue service facilities

SHTM 81 part 1: 17. Portable fire-fighting equipment / 18. Fire and rescue service facilities

Fire safety - Precautions in new healthcare premises (SHTM 81 part 1) · PDF pages 26–28 of 42 · Source file: shtm-81-part-1-v5.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHTM 81 part 1 – PDF page 26]

17. Portable fire-fighting equipment

All healthcare buildings should be designed with location points for portable firefighting equipment in accordance with the requirements of BS 5306-8: Selection and positioning of portable fire extinguishers, these points should be easily accessible to staff and should not cause an obstruction to operational activity or the means of escape routes.

Portable fire-fighting equipment should be installed in accordance with the requirements of BS 5306-8.

Hose reel installations should not be installed in healthcare premises.

Further information is available in SHTM 85: Fire precautions in existing healthcare premises, sections 7.167 to 7.177.

[SHTM 81 part 1 – PDF page 27]

18. Fire and rescue service facilities

General

The design and construction of healthcare premises should ensure that there is suitable access and provision of facilities for firefighting in accordance with the technical handbook non-domestic.

Hospital streets

Where a hospital street has two or more escape stairs, Fire and Rescue Service facilities should be provided in accordance with the table below.

Table 18.1: Fire and Rescue Service Facilities

Height and depth of storey

Facilities on escape stair Technical handbook non

domestic; clause

above or below fire and rescue service access level

Basements at a depth more than 10m below access level.

2.14.3 2.14.4 2.14.5 2.14.6 2.14.7

Fire-fighting stair; Fire-fighting lift; Fire-fighting lobby; Ventilation to stair and lobby; Dry fire main (outlet located at every departmental entrance)

Basements at a depth not more than 10m below access level.

Fire-fighting stair; Ventilation to stair; Unvented fire-fighting lobby; Dry fire main (outlet located at every departmental entrance)

2.14.3 2.14.6 2.14.5 2.14.7

Topmost storey height not more than 18m above access level.

Fire-fighting stair; Ventilation to stair; Unvented fire-fighting lobby; Dry fire main (outlet located at every departmental entrance)

2.14.3 2.14.6 2.14.5 2.14.7

Topmost storey height not more than 50m above access level.

2.14.3 2.14.4 2.14.5 2.14.6 2.14.7

Fire-fighting stair; Fire-fighting lift; Fire-fighting lobby; Ventilation to stair and lobby; Dry fire main (outlet located at every departmental entrance)

Topmost storey height not more than 60m above access level.

2.14.3 2.14.4 2.14.5 2.14.6 2.14.7

Fire-fighting stair; Fire-fighting lift; Fire-fighting lobby; Ventilation to stair and lobby; Wet fire main (outlet located at every departmental entrance)

The access level is the level at which the Fire and Rescue Services enter the building to commence fire fighting and rescue operations.

[SHTM 81 part 1 – PDF page 28]

Table notes

If an automatic fire suppression system is installed throughout a building, no point on the storey should be more than 60m from a dry or wet rising main outlet, measured along an unobstructed route for laying fire hose.

If an automatic fire suppression system is not installed throughout the building, no point on the storey should be more than 45m from a dry or wet rising main outlet.

Scottish Fire and Rescue Service should be consulted to ensure that access and firefighting facilities meet with their operational requirements.