SHTM 81 part 1: 15. Emergency escape lighting / 16. Fire signs and notices
[SHTM 81 part 1 – PDF page 24]
15. Emergency escape lighting
In the event of a local or general power failure it is important that escape routes remain illuminated to aid the safe evacuation of occupants in an emergency, therefore, an emergency escape lighting system should be installed in accordance with the technical handbook non-domestic, BS 5266-1: Code of practice for the emergency lighting of premises and BS EN 1838: Lighting applications - Emergency lighting.
Due to the difficulties and dangers associated with the emergency evacuation of patients, the emergency escape lighting systems should activate within 0.5 seconds of a mains failure in all healthcare premises.
A three-hour duration emergency escape lighting system should be installed in all healthcare premises.
To maintain patient comfort, it is unlikely that ‘maintained’ emergency escape lighting would be suitable for bed patient wards, as the luminaires remain permanently illuminated with this type of system.
[SHTM 81 part 1 – PDF page 25]
16. Fire signs and notices
Fire signs and notices should be sited in conspicuous locations throughout healthcare premises and should be installed in accordance with the guidance within SHTM 85: Fire precautions in existing healthcare premises, sections 7.12 to 7.19.