13. Emergency evacuation

Escape routes from bed-patient areas should be designed to permit the use of mattress and other evacuation aids should it become necessary in an extreme fire situation.

To facilitate this, an escape stair width should be a minimum of 1300mm and the landing should be designed to ensure it is of sufficient width to manoeuvre mattresses and other evacuation aids.

Consideration should be given to additional width of stairways, if required for ambulant persons to pass whilst a mattress evacuation is taking place.

Escape lifts

In hospitals, escape bed lifts provide an option for the vertical evacuation of patients and they play an important part in the overall evacuation strategy. Therefore, the requirement for escape bed lifts should be considered at the initial design stage, and the rationale fully documented in the fire strategy proposal.

Evacuation lifts should be considered for all healthcare premises, as it is likely many patients with mobility issues will not be able to negotiate stairs to make their escape from a building. Evacuation lifts should have the same system protection measures as escape bed lifts.

Escape bed lifts should comply with SHTM 08-02: Specialist Services Lifts and SFPN 3: Escape bed lifts.

External stairways

Unenclosed external stairways should not be provided for escape purposes from patient access areas.

Escape routes

All escape routes should lead directly to:

A place of safety, or

A protected zone, or

An unprotected zone in another compartment or sub-compartment (this facilitates progressive Horizontal Evacuation where patients may be moved to another ward in a different compartment or sub-compartment).

Escape routes including door widths from bed-patient areas should have a minimum unobstructed width of 1500mm to accommodate bed-patient evacuation.

[SHTM 81 part 1 – PDF page 23]

14. Locks

Healthcare premises can present challenges when assessing the requirement for locked doors in secure units whilst ensuring all occupants can evacuate safely in the event of fire. Additionally, healthcare premises may have patients at risk of harm from falling down stairs, e.g. a patient ward on an upper floor providing accommodation for elderly patients.

In such cases, a variation from ‘Firecode’ and ‘Technical Handbook: Non-Domestic’ may be appropriate provided it does not diminish the means of escape provision. Where a variance is proposed, it should be supported with a robust management procedure that will ensure the following factors:

staff have a failsafe method of unlocking exit doors;

there will be sufficient staff available to ensure all exit doors can be unlocked;

staff will be made aware of their responsibilities and receive comprehensive training;

staff will be in constant communication with each other during a fire evacuation, and there will always be someone present with the responsibility of managing and coordinating an evacuation.

The safety and security measures including management procedures should be considered at the design stage onwards and form part of the buildings fire strategy.

Further information is available in SHTM 85: Fire precautions in existing healthcare premises, sections 7.133 to 7.137.

Electrically powered locks

Electrically powered locks should not be installed on a protected door serving the only escape stair in the building, or

The only escape stair serving part of the building, or

On any door, that provides the only route of escape from the building or part of the building.

Further information is available in SHTM 85: Fire precautions in existing healthcare premises, sections 7.138 to 7.145.