12. Fire/smoke doors

In healthcare premises, all fire door sets must be fitted with an appropriate means of preventing the passage of fire and smoke.

Fire doors, including frame, hardware and glazing should be tested and certified to BS 476-22: Fire tests on building materials and structures or BS EN 1634-1: Fire resistance test for door and shutter assemblies and openable windows.

Fire doors should be installed in accordance with BS 8214: Timber-based fire door assemblies.

In addition to ensuring the correct fire safety performance criteria of fire doors, the door sets should be robust enough for their chosen application. This should take account of potential damage caused by everyday activity such as moving patients by wheelchairs and bed trolleys.

All fire and smoke doors, including each leaf of double doors, should be provided with an identification disc. The disc should be a minimum of 45mm in diameter clearly indicating the level of fire safety performance of the door.

Automatic doors on an escape route should be installed in accordance with BS 7036: Power operated pedestrian door sets and the technical handbook non-domestic.

Door swings should not obstruct the designed width of the circulation space or escape route. However, storeroom doors, which are normally locked, may open on to circulation and escape routes; it is recommended that storeroom doors should open through 180° to avoid obstruction.

Fire doors across escape routes should open in the direction of escape, however, fire doors across escape routes providing alternative means of escape should be double swing.

Vision panels

Where doors on escape routes sub-divide corridors or doors that are double swing, they should be provided with a vision panel at a suitable height and position for all possible users, installed in accordance with BS 8214.

Self-closing devices

Self-closing devices should be fitted to fire and smoke doors including half leafs and installed in accordance with BS EN 1154: Building hardware - Controlled door closing devices.

To facilitate operational needs and patient comfort, self-closing doors serving patient bedrooms should be of the free swing arm type that normally stand open in any position but fully close when the fire alarm actuates.

Acoustically actuated systems are not acceptable in newly built hospitals.

[SHTM 81 part 1 – PDF page 21]

Electrically powered hold open devices

One of the main causes of damage to fire doors is due to wheelchairs, beds and trolleys colliding with partially open doors.

In order to minimise the operational impact, whilst maintaining the effectiveness of protective measures self-closing fire doors may be fitted with electromagnetic hold open devices, linked to the fire alarm. They should be designed in accordance with BS 5839-3: Specification for automatic release mechanisms and EN 1155: Building hardware: Electrically powered hold-open devices for swing doors.

Electromagnetic hold open devices should not be installed on:

an emergency door;

fire and smoke doors serving the only escape stair in the building;

fire and smoke doors serving the only escape stair for part of the building;

fire and smoke doors serving a fire-fighting shaft;

Acoustically actuated systems are not acceptable in newly built hospitals.

Further guidance is available in BS 7273-4: Actuation of release mechanisms for doors.

Transfer grilles and vents

To reduce the possibility of smoke transfer between compartments and sub- compartments, the installation of transfer grilles in fire resisting door sets or other fire- resistant construction should be avoided. However, where they are an essential component of an air transfer system they should be provided with remotely resettable fire and smoke dampers actuated by automatic smoke detection.

Fire doors, frame and hardware (including transfer grilles and vents) should be tested and certified to BS 476-22 or BS EN 1634-1 and installed in accordance with BS 8214.