SHTM 81 part 1: 11. Means of escape
[SHTM 81 part 1 – PDF page 18]
11. Means of escape
The requirements for means of escape are based on:
the potential for progressive horizontal evacuation, achieved by dividing a storey into compartments and sub-compartments;
height above ground level of the patient access area;
travel distance and escape routes;
provision of an adequate number of exits and escape stairs;
provision of emergency escape lighting;
provision of a fire alarm and detection system;
provision of fire resilient infrastructure.
The number of exits in a hospital should be calculated in accordance with the requirements of the technical handbook non-domestic section 2.9.1 and the additional criteria below.
A minimum of 2 storey exits should be provided from a hospital. The number of storey exits increases in proportion to the number of patient beds:
any storey with more than 100 patient beds should have at least 3 storey exits;
any storey with more than 200 patient beds should have at least 4 storey exits;
any storey with more than 300 patient beds should have at least 5 storey exits.
Compartment exits
In a hospital where a storey is divided into 3 or more compartments, each compartment should have exits to:
an adjoining compartment and a hospital street, or
an adjoining compartment and an escape stair, or
an adjoining compartment and a final exit.
Each sub-compartment should be provided with at least 2 exits by way of protected zones or unprotected zones to adjoining, but separate, compartments or sub- compartments.
Travel distance
Travel distance in patient access areas of healthcare premises should not exceed 15m in one direction of travel and 32m in more than one direction. Travel distance may be measured to a place of safety, a protected zone, an escape stair or a protected door in a compartment wall or a sub-compartment wall however an escape route should not pass through fire hazard rooms.
[SHTM 81 part 1 – PDF page 19]
Travel distance should be measured along the actual escape route and should take account of the location of equipment, items of furniture and other obstructions that will be present when the building is occupied.
Where an escape route passes through an open plan area, the route should be clearly defined.
The travel distances as defined above are a maximum for the occupancy type and an assessment should be made, at the design stage, as to whether this distance should be reduced to take account of parts of the building that will be occupied primarily by persons with mobility issues.
Further guidance is available in the technical handbook non-domestic section 2.9.3 table 2.11.
Access to escape stairs
In a hospital, where an escape stair in a protected zone serves an upper storey containing patient facilities, access to the protected zone should be by way of a protected lobby or by way of a hospital street.