SHTM 81 part 1: 4. Classification of patient dependency / 5. Progressive horizontal evacuation
[SHTM 81 part 1 – PDF page 8]
4. Classification of patient dependency
The passive and active fire precautions specified in this document recognise the need to minimise disruption to patient care in the event of fire.
The level of fire precautions and fire evacuation procedures should be based on patient dependency and the fire loading of adjacent areas.
Firecode classifies patient dependency into three distinct groups:
very high dependency - Patients for whom movement or evacuation would severely affect their medical care and may prove life threatening. This will include those in intensive care areas, operating theatres, coronary care, special care baby units etc.;
dependent - Patients whose clinical treatment or condition creates a dependency on staff to evacuate in the event of fire. Evacuation of this patient group is unlikely to prove life threatening although it will most likely be necessary to move them to an adjoining compartment or sub-compartment, where their care can be continued;
independent - Patients are considered as independent if their mobility is such that they can evacuate a premises unaided or with minimal assistance from another person. This would include being sufficiently able to negotiate stairs as well as being able to comprehend the emergency wayfinding signage around the healthcare facility.
[SHTM 81 part 1 – PDF page 9]
5. Progressive horizontal evacuation
The immediate and total evacuation to outside of the building may not be practicable or desirable for the following reasons:
patients may be dependent on medical, electrical or mechanical equipment and cannot be moved easily or quickly as the act of doing so may incur harm;
patients ability to respond to an alarm of fire may be limited by mental health; visual or aural impairments;
patients with restricted mobility may not be able to negotiate escape routes, particularly stairways, without assistance;
the effects of medication may restrict patients’ response.
Progressive horizontal evacuation is a systematic process of moving patients away from the area affected by fire to an adjoining compartment or sub compartment on the same level, where the patients and staff are protected from the immediate dangers of fire and smoke and patient medical care can be continued. The adjoining compartment/sub compartment should be capable of holding the occupant capacity of the vacated compartment in addition to its own occupancy. Patients and staff may remain in the adjoining compartment / sub compartment until the fire is extinguished.
If necessary due to fire development, occupants should have the facility to move continually away from the area of fire, either, to the next adjoining compartment / sub compartment, or to an escape stair or escape lift that leads to a place of safety, or directly to a place of safety.
Every storey containing bed-patient areas within hospitals should be designed to provide for progressive horizontal evacuation.
The facility for progressive horizontal evacuation should be considered for any healthcare premises or area that will provide treatment, medication or anaesthetic that could result in delayed patient evacuation. Where this is the case, a clear fire strategy should be agreed between the designer and the Health Boards fire safety advisers on the elements required to facilitate PHE from specified areas.
Factors that should be considered include:
the dependency of patients;
the mobility of patients and others that effect their ability to evacuate premises in a fire emergency;
fire hazards within the premises;
management policies, including the availability of sufficient and adequately trained staff.