[SHTM 81 part 1 – PDF page 10]

6. Fire detection and alarm systems

The provision of automatic means for detecting a fire and raising the alarm is of vital importance in healthcare premises, particularly in areas of a building that are not permanently staffed, to provide the maximum available safe egress time (ASET) from the earliest stage of fire development.

An automatic fire detection and alarm system should be installed in all healthcare premises and should be designed and installed in accordance with the guidance in SHTM 82: Fire alarm and detection systems and BS 5839-1: Fire detection and fire alarm systems for buildings.

a category L1 system should be provided throughout all parts of hospital premises;

for healthcare premises other than hospitals, the fire detection and fire alarm system should be appropriate for the risk, but a minimum of L3 standard;

fire alarm zones should be consistent with fire compartment and sub- compartments boundaries;

fire alarm systems should incorporate an automatic means of alerting the fire and rescue service, usually through a third-party alarm-receiving centre (ARC).

All fire alarm systems should have the capability of being fitted with detectors that can differentiate between false alarm triggers such as dust or steam and an actual fire. This will greatly minimise the number of unwanted fire alarm signals and ensure an immediate mobilisation of fire service appliances via an alarm receiving centre. This is of particular importance where it is not possible to check for signs of fire e.g. roof voids, areas not permanently staffed and during periods that premises are unoccupied.

The fire service will always attend any incident where they receive a 999 call that confirms a fire.

Voice alarm systems have been shown to provide significant benefits, and may be considered for use, particularly in areas where large numbers of public congregate e.g. Atriums and retail areas.

Guidance on voice alarm systems is provided in SHTM 82: Fire alarm and detection systems and BS 5839-8: Code of practice for the design, installation, commissioning and maintenance of voice alarm systems.

[SHTM 81 part 1 – PDF page 11]

7. Automatic fire suppression systems

Automatic fire suppression is mandated in prescribed areas, see section 10.

An automatic fire suppression system may be an integral part of a fire-engineered solution to achieve an acceptable standard of fire safety where there is a variation from Firecode and the Building Standards technical handbook non-domestic.

In addition to the mandatory standards, automatic fire suppression systems should be fully considered for all new healthcare premises, extensions or structural refurbishments to existing facilities, and the rationale fully documented in the fire strategy proposal.

Considerations should include:

enhanced life safety provision;

minimising the spread of fire and subsequent disruption to patient services;

the strategic importance of the facility with regard to ensuring the ongoing provision of healthcare;

the geographical location of the building e.g. island or remote area with limited fire service attendance;

availability of mains water supply and whether there is sufficient water pressure;

areas of special fire risk within or adjacent to a hospital e.g. laboratories, a national treatment centre and a national distribution centre;

Fire Service attendance criteria in response to automatic fire alarm activations;

environmental factors e.g. smoke contamination of surrounding atmosphere, large volumes of water used in the operation of firefighting and subsequent contaminated water run off;

cost benefit analyses comparing the cost of reinstatement of services after a fire event compared to the initial cost of installation of a suppression system.

Where installed, sprinkler systems should comply with the requirements of BS EN 12845 Fixed firefighting systems: Automatic sprinkler systems and the Loss Prevention Council (LPC) Rules.

Where other suppression systems are proposed it should be evidenced that they comply with the relevant BS EN standard.