X-ray protection

Doors to rooms containing X-ray equipment will be required to provide resistance to X-rays. The National Radiological Protection Board (now subsumed under the Health Protection Agency) establishes and advises on shielding requirements, and specifiers should discuss project requirements with the local Radiological Protection Adviser.

In most circumstances, sufficient shielding will be provided by 1.5 to 2.5 mm of lead sheet.

The shielding must be continuous across leaf and frame, and gaps at meeting stiles should be masked by an overlapping shielded cover-mould. The optimum solution may well be to adopt sliding doors if space is available.

Vision panels must be restricted in size and should be glazed in accordance with BS 6262:1982 using X-ray resistant glass to give shielding equal to that provided by the door.

Depending upon layout and fire containment requirements, X-ray doorsets may additionally be required to provide fire resistance. Although such doorsets are available, it would be advisable to avoid using X-ray resisting doorsets in fire- rated walls.

Any perforations, such as grilles, or undercutting a door to facilitate air transfer, may nullify the X-ray resistance of a doorset.

[SHTM 58 – PDF page 17]

3. Design guidance and specification

Partition and frame thickness

The first item to be considered when selecting and specifying doorsets is the construction and overall finished thickness of the partitions or walls into which they are to be fitted.

The designer may also wish to decide between one-piece and split frames at an early stage. Different manufacturers offer different frame constructions, but all can be co-ordinated with partition details.

Internal partitions for health buildings are described in SHTM 56: ‘Partitions’. Many will be formed of plasterboard on metal studs to an overall thickness of 100mm.

However, it is essential to pay close attention to the interface between partition and doorset and to the details of fixing. For partitions of up to 150mm thick, the one-piece frame is usually made to match the partition; beyond that thickness, it is usual to add an extension lining (see Figure 6).

Figure 6

The split frame is normally made to suit 100mm partitions but can be extended to suit thicker partitions by inclusion of a make-up piece (see Figure 7).