SHTM 58: Smoke containment / Sound insulation

Building component series - Internal doorsets (SHTM 58) · PDF pages 14–15 of 26 · Source file: shtm-58-v1-dec-2006.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHTM 58 – PDF page 14]

• a third party certification scheme such as TRADA Q Monk product certification.

Specifiers should ensure that fire doors, as installed, meet an appropriate performance standard i.e. BS476 Part 22, BS EN1634-1, BS476 Part 23, ISO 3008.

Figure 5

Smoke containment

Section 2 of the Building (Scotland) Regulations 2004 highlights requirements in respect of smoke containment. Doorset provision include:

doors in a compartment wall;

doors that are part of the enclosure of a:

(i) protected stairway;

(ii) protected lobby approach to a stairway; or

(iii) protected corridor;

doors sub-dividing corridors connecting alternative exits;

doors separating a dead-end from a corridor;

doors forming part of the enclosure to a communal area in sheltered housing.

Unless pressurisation techniques complying with BS 5588-4:1998 are used, smoke-containing doorsets should have a leakage rate not exceeding 3m3 m–1 hr–1 (head and jambs only) when tested at 25 Pa under BS 476: Section 31.1. Suitable tested fire-resisting smoke-containing doorsets are available from doorset suppliers; to ensure proper performance it is essential to seal the junction between frame and partition. Regulations do not require the threshold to be smoke sealed; in some situations, however (for example where there is a

[SHTM 58 – PDF page 15]

requirement for rooms or areas to be pressurised), complete sealing may be required. Suitable threshold seals can be obtained from manufacturers.

The edge seals fitted to smoke-containing doorsets are commonly of the ‘wiper blade’ type; they may be combined with intumescent seals. The tolerances on such seals are very fine, and doors are likely to bind if not accurately fitted; doors which do not close properly offer little resistance to smoke.

Careful installation and regular maintenance are of paramount importance if smoke containment is to be assured.

The gap between the door leaf edge and the frame should not exceed 4mm. A longer gap is acceptable between the bottom of the door and the threshold. No specific size is specified in the standard and a larger gap may often be necessary to accommodate floor finishes such as carpets. 10mm is generally accepted as a reasonable maximum between the bottom of the leaf and finished floor covering (BS 8214: 1990 refers).

Refer to SHTM 59: ‘Ironmongery’ for advice on selection of closers for use on smoke-containing doorsets.

BS8214: 1990, Code of Practice for fire door assemblies with non-metallic leavers provides comprehensive guidance on the specification, design, construction, installation and maintenance of fire door assemblies.

Sound insulation

Any perforation in a partition will reduce the overall sound insulation performance of the partition as a whole, and sound transmission through a doorset will invariably be greater than that through the partition in which it is fixed. Guidance on levels of sound insulation that can be achieved with internal partitions is given in SHTM 56: ‘Partitions’.

Hygrothermal performance

Hygrothermal conditions can affect the performance of doorsets.

Normal conditions likely to be met in health buildings are:

25% to 65% relative humidity over a temperature range of 10°C to 25°C.

In areas of high humidity, such as laundries and shower rooms, the conditions would be:

25% to 100% relative humidity over a temperature range of 10°C to 30°C.

The selected doorsets must be able to withstand these conditions without loss of performance or appearance.