SHTM 58: Special features / Ironmongery

Building component series - Internal doorsets (SHTM 58) · PDF pages 11–13 of 26 · Source file: shtm-58-v1-dec-2006.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHTM 58 – PDF page 11]

The selection of glazing in doors should be based on considerations of observation and of safety, for example the need to avoid collision between users approaching the door from opposite sides, bearing in mind that users may be adults or children, ambulant or in wheelchairs, and in the case of staff, may be carrying objects or pushing or pulling mobile equipment. These needs can be met by the provision of vision panels or glazing as illustrated in Figure 4. Security glazing may be required in areas such as mental health accommodation. Laminated or plastic glazing types should be specified to prevent breakage.

Figure 4

Consideration should be given to providing a lower panel of glazing which may increase visibility in busy areas or where children are present.

The inclusion of a vision panel in fire-resisting doorsets is recommended as it will facilitate early warning and assessment of a fire.

Any vision panels in X-ray resisting doorsets should be restricted to the smallest practicable size.

There is often a conflict of interest between nursing staff’s need for supervision and the patient’s expectations of privacy. The provision of glazing in doors should be very carefully considered in this context. It may be suitable to fit curtains or to use ‘venetian mirrored’ glass; proprietary devices are also available to allow controlled observation by staff. Panels should be glazed in accordance with BS 6262:1982.

Special features

Buffer strips

Noise from the closing of doors can be a considerable nuisance in health buildings. This problem can be reduced by the inclusion of a continuous buffer strip to the frame. These are available in the form of self-adhesive foam, V sections or P sections.

[SHTM 58 – PDF page 12]

Buffer strips, by contributing to a snug fit between door and frame, may also contribute to fire resistance, smoke containment, sound insulation and sound deadening.

Door-protection systems are available to protect against trapping of fingers in the hinged reveal of the door frame. This is particularly beneficial to children, disabled people, people with mental health disorders and older people.

Air transfer grilles

Air transfer grilles in doorsets should be avoided wherever possible as they will materially affect the performance of the doorset in terms of sound insulation and impact resistance.

If it is required to balance air pressure across a door opening, alternative solutions should be adopted. For example, if the door is in frequent use or normally held open, either a grille will not be required or it may be fitted into the partition near the door opening. Alternatively it may be sufficient to cut short the door leaf if sound insulation, fire resistance or smoke containment is not required.

There may be occasions when placing the transfer grille in an adjacent partition may not be a suitable solution, and in order to ensure a satisfactory air movement pattern it will be necessary to mount a transfer grille at low level in a door. Applications could include WC/en-suite doors in isolation rooms, internal doors between rooms in an operating suite, and some laboratory situations. Also in some of these applications the use of buffer strips and other seals may prevent a satisfactory flow of air and result in excessive door closure pressures and wind noise.

Ironmongery

Selection and correct fitting of appropriate ironmongery are essential to the correct functioning of any doorset. The specifier should refer to SHTM 59 – ‘Ironmongery’ and select and specify ironmongery as an integral part of each doorset.

All ironmongery attached to the doorset should be factory-fitted by the doorset manufacturer. For convenience of packaging and transport, the specifier may wish to agree with the doorset supplier that projecting items, such as handles, be factory-fitted and then removed and packaged separately for delivery. Those items will then be refixed to the prepared housings/positions by site labour.

Fire precautions

Fire-resisting doorsets in health buildings must meet the requirements of the Building (Scotland) Regulations 2004 and guidance specifically concerned with fire precautions in Firecode. The most common requirement is for half-hour and

[SHTM 58 – PDF page 13]

one-hour grades referred to as FD30 and FD60. A suffix(s) indicates that the doors are fitted with a flexible neoprene or nylon brush smoke seal e.g. FD30(s) and FD60(s). Fire-resisting doorsets complete with ironmongery, when tested in accordance with BS 476-20:1987, BS 476-22:1987 and BS EN 1634-1:2000, must achieve the following performance:

Designated Period

½ hour FR 1 hour FR

Integrity 30 minutes 60 minutes

Insulation No requirement No requirement

Fire-resisting doors are normally required to be self-closing and may only stand open if controlled by ‘fail-safe’ mechanisms linked to an automatic fire alarm and detection system. However, exceptions do occur, for example with hospital accommodation for older people (see HBN 37: ‘In-patient accommodation for older people’).

Doors provided solely for means of escape in case of fire are not necessarily required to be fire-resisting.

Any perforations, such as grilles, or undercutting a door to facilitate air transfer, will invalidate the fire resistance of the doorset, and an alternative method of air transfer should be used, such as ducting and a fire damper located in the partition.

When the use of an air transfer grille in a fire/ smoke-containing doorset is unavoidable, it is important to specify an appropriate grade of grille (see SHTM 59: ‘Ironmongery’).

Note: Site fitting of an air transfer grille may invalidate the fire performance standard to which the door originally complied. Where such a grille is required, it is recommended that the door is replaced by one manufactured and approval tested to the standard required.

Identification

Fire-resisting doorsets must be supplied with an identification plate on the door leaf showing the name of the manufacturer and the date of manufacture. In addition, each fire-resisting doorset must be identified as shown in Figure 5. The functional performance of all fire resisting doorsets should be in conformity with an accredited test and/or certification method:

• an independent test;

• a UKAS accredited test laboratory;