SHTM 58: Description / Glazing

Building component series - Internal doorsets (SHTM 58) · PDF pages 9–10 of 26 · Source file: shtm-58-v1-dec-2006.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHTM 58 – PDF page 9]

Width requirements can be specified as follows:

Room/space Co-ordinating width of doorset (mm)

Ducts, small cupboards 600

WCs, bathrooms, bedrooms, small offices 800

900

Larger offices, areas subject to frequent pedestrian movement, minimum width for wheelchairs

1000

Areas subject to frequent movement of wheelchairs, trolleys and mobile equipment

1300

Minimum width for single bedrooms as assisted bathrooms

1500

Preferred width for assisted bathroom, single bedrooms and minimum for multi-bed areas

1700

Corridors, multi-bed areas and treatment areas

1900

Heavily trafficked corridors, preferred width of bed areas and treatment areas

(See also HBN 40: Common activity spaces – Volume 4 for additional information about access for wheelchairs)

Thickness

Doorsets should be capable of accommodating permissible deviations in partition or wall thickness of ±5 mm.

Description

Grades of doorset

There is an established need for the following grades of doorset in health buildings:

heavy duty;

severe duty;

fire-resisting;

fire-resisting with smoke containment;

smoke containment;

X-ray resisting.

[SHTM 58 – PDF page 10]

The grade of doorset should relate to functional requirements, bearing in mind the distinction between a heavily used doorway and a heavily used door. Doors, which are normally held open, for example, will be used only lightly however much traffic passes through the opening.

Sensible economies can be achieved by carefully matching the characteristics of doorsets to the demands placed upon them.

Examples of use for those grades are:

heavy duty – frequent and very frequent use. Used by the general public and by people with little incentive to exercise care. Frequent passage of heavy trolleys, beds, or other bulky items;

severe duty – subject to frequent violent usage – doors of stockroom, opened by driving trolleys against them;

fire-resisting – used in designated positions to limit the spread of fire and to protect escape routes;

fire-resisting with smoke containment – for use where fire doors are required to contain smoke at ambient temperature;

smoke containment – for use where heavy duty doors are required to contain smoke at ambient temperature;

X-ray resisting – used to contain scatter from X-ray equipment.

In certain applications, such as residential accommodation, light or medium duty grades may be appropriate, but such doorsets are not dealt with in this SHTM (refer to BS 4787-1:1980 and DD 171:1987)

‘High security’ duty grades of doorset may occasionally be required, for example in mental health wards or drug stores. Consult individual doorset manufacturers for their range/type of ‘high security’ duty grade doorset.

Thresholds

Raised thresholds are not normally specified in health buildings as they tend to inhibit free movement of trolleys and to limit the use of floor-cleaning machinery.

However, on large doorsets the incorporation of a permanent threshold ensures its overall shape by securing the feet of the frame and, where the door is set on floor springs, allows them to be fitted at the joinery works. Such thresholds should be set flush with the floor screed and covered by the floor finish.

Glazing

Section 4 of the Building (Scotland) Regulations 2004 lays down certain criteria (including visibility) relating to access for disabled users.