2. User requirements

General

All doorsets for health buildings should comply with the guidance and performance standards described in this SHTM. The standards are based on extensive research and evaluation of doorsets in use and are the minimum required to ensure satisfactory performance.

Research has shown that the functional requirements for doorsets in health buildings can be met by a limited range of options, and their selection should be based upon consideration of the following key characteristics:

size;

configuration and handing;

grade;

glazing;

leaf finish;

frame finish;

special features, for example air transfer grilles;

fire rating and smoke detection requirements;

acoustic requirements.

Doorsets

The high performance standards required of door leaves, frames and ironmongery in health buildings can best be met when these components are accurately fitted and matched in a factory and delivered to site as a complete unit.

Frames

Different frame constructions are available to suit any thickness of partition or wall, and variations in frame width do not affect other key characteristics of a doorset.

Doorsets with a traditional one-piece frame are usually provided with loose architraves for fitting on-site. Alternative designs use a split frame which includes integral architraves (see Figure 3). Designers should notice the different plane of door leaf in these two alternatives.

[SHTM 58 – PDF page 8]

Figure 3

Dimensions

General

Work sizes of doorsets are subject to the permissible deviations stated in BS 4787-1:1980.

Doorsets and glazed screens should form part of a co-ordinated interior design proposal.

Height

All internal doorsets should have a co-ordinating structural opening height of 2100 mm unless specifically required to be different. Doorsets without transoms or overpanels meet most health building requirements, are economical, and simplify the selection and fitting of ironmongery.

Width

Doorset widths should relate to functional requirements after allowing for the thickness of frame, stop, leaf thickness and projecting ironmongery when the leaf is in the open position. These allowances can reduce the clear opening width by 300 mm. The effective clear width through a doorway should comply with the recommendations of BS 8300:2001 ‘Design of buildings and their approaches to meet the needs of disabled people’.