SHTM 58: Layout and planning / Emergency access to patients
[SHTM 58 – PDF page 18]
Figure 7
Layout and planning
The location of door openings will be largely determined by reference to room layouts, and it is important to allow a nib of not less than 50 mm in order to accommodate fixing, full architraves and projecting items of ironmongery (see Figure 8).
Figure 8
[SHTM 58 – PDF page 19]
Consider the interrelationship between door swing and such items as light switches and power points and the positions of furniture and fittings. It may well be advantageous to open a door outwards rather than into a small room or restricted space. Section 3.12 of the Building (Scotland) Regulations indicates relevant layout requirements for WC provision.
Emergency access to patients
Where access to patients may be required in an emergency, for example in WCs and bathrooms, door leaves with the facility to open outwards should be provided. This may be achieved with:
outward-opening, single-swing door leaves;
single-swing door leaves normally opening inwards but with the facility to open outwards by the removal of the stops;
special ironmongery which allows a catch stop to be removed or depressed.
Maintenance manual
An operation and maintenance manual should be compiled and should be handed to the maintenance staff immediately following the practical completion of the contract.
Ironmongery correctly selected and fitted requires very little maintenance (see SHTM 59: ‘Ironmongery’).
Broken or damaged glass in doorsets should be replaced without delay, particularly in the case of fire- resisting doorsets, where the performance of the doorset must be maintained at all times. Intumescent strips on fire-resisting doorsets should be inspected regularly and replaced if damaged.
Hygiene and cleaning
Control and Prevention of Healthcare Associated Infection (HAI) is a priority issue for NHSScotland – both in respect of the safety and well being of patients and staff and also the resources consumed by potentially unavoidable infections.
Healthcare Associated Infection (HAI) is a complex issue involving the many different elements of patient care and provision. Due to its multi-factorial nature there is a need to develop a holistic approach to combating the spread of infection within the built environment.
It is imperative that those involved in the design and planning, construction and refurbishment and on-going maintenance of the healthcare facility have a sound knowledge of prevention and control of infection in the built environment.
[SHTM 58 – PDF page 20]
SHFN 30 and HAI-SCRIBE aim to provide information on the prevention and control of infection, and on the prevention of cross-infection and cross contamination in healthcare facilities, to those responsible for the planning, design and maintenance of such facilities.
Cleaning is an essential part of the multi-disciplinary approach in improving patient, staff and public safety. Safe clinical care is supported through ensuring high standards of hygiene and related measures to tackle HAI in the healthcare environment.
Cleaning regimes including frequency of cleaning should be addressed in line with current national guidance together with any additional local management requirements.
Relevant provisions of current guidance, standards and Codes of Practice for cleaning of healthcare premises and including the latest technical requirements are embodied in the following documents:
Scottish Health Facilities Note (SHFN 30): ‘Infection Control in the built environment: Design and Planning’;
HAI-Scribe (Healthcare Associated Infection System for Controlling Risk in the Built Environment);
The NHSScotland National Cleaning Services Specification;
NHS Quality Improvement, Scotland – Healthcare Associated Infection (HAI) Cleaning Services Standards;
The NHSScotland Code of Practice for the Local Management of Hygiene and Healthcare Associated Infection;
Clinical Standards Board for Scotland Healthcare Associated Infection (HAI) Infection Control Standards
Doorsets should be cleaned and disinfected in accordance with the above specifications.